GOODWE
ET Series
40/50kW | Three Phase | 3/4 MPPTs
Hybrid Inverter (HV)
GoodWe's ET Series inverters, available in 40kW and 50kW capacities, are designed for commercial and industrial PV installations. These adaptable inverters seamlessly integrate into both on-grid and off-grid applications, facilitating parallel connections in either scenario. When paired with the Static Transfer Switch (STS) Box from GoodWe, the inverter not only ensures dependable UPS-level switching to backup mode but also interacts with diesel generators to efficiently replenish batteries. Moreover, the ET Series is compatible with diverse battery capacities and brands, including the GoodWe Lynx C, offering a comprehensive energy storage solution.
Key Features:
-
Flexible & Adaptable Applications
- Supports parallel connection in both on- and off-grid modes
- Up to 150% DC input oversizing
- 4 MPPTs, Max. efficiency up to 98.1%
- 110% unbalanced output
- UPS-level switching
-
Superb Safety & Reliability
- Optional Type I+II SPD on DC side¹
- IP66 protection for outdoor installation safety
- AFCI optional¹
-
Friendly & Thoughtful Design
- Elegant and compact design
- Plug & Play installations
¹ Optional functions or devices are purchased separately.
Technical Data
Battery Input Data
Parameter | GW40K-ET-10 | GW50K-ET-10 |
---|---|---|
Battery Type | Li-Ion | Li-Ion |
Nominal Battery Voltage (V) | 500 | 500 |
Battery Voltage Range (V) | 200 ~ 800 | 200 ~ 800 |
Start-up Voltage (V) | 200 | 200 |
Number of Battery Input | 1 | 1 |
Max. Continuous Charging Current (A) | 100 | 100 |
Max. Continuous Discharging Current (A) | 100 | 100 |
Max. Charging Power (W) | 44000 | 55000 |
Max. Discharging Power (W) | 44000 | 55000 |
PV String Input Data
Parameter | GW40K-ET-10 | GW50K-ET-10 |
---|---|---|
Max. Input Power (W) | 60000 | 75000 |
Max. Input Voltage (V) | 1000 | 1000 |
MPPT Operating Voltage Range (V) | 165~850 | 165~850 |
Start-up Voltage (V) | 200 | 200 |
Nominal Input Voltage (V) | 620 | 620 |
Max. Input Current per MPPT (A) | 42/32/42 | 42/32/42/32 |
Max. Short Circuit Current per MPPT (A) | 55/42/55 | 55/42/55/42 |
Number of MPP Trackers | 3 | 4 |
Number of Strings per MPPT | 2 | 2 |
AC Output Data (On-grid)
Parameter | GW40K-ET-10 | GW50K-ET-10 |
---|---|---|
Nominal Output Power (W) | 40000 | 50000 |
Nominal Apparent Power Output to Utility Grid (VA) | 40000 | 50000 |
Max. Apparent Power Output to Utility Grid (VA) | 44000 | 55000 |
Max. Apparent Power from Utility Grid (VA) | 44000 | 55000 |
Nominal Output Voltage (V) | 380/400, 3L/N/PE | 380/400, 3L/N/PE |
Output Voltage Range (V) | 176~276 | 176~276 |
Nominal AC Grid Frequency (Hz) | 50/60 | 50/60 |
AC Grid Frequency Range (Hz) | 45~65 | 45~65 |
Max. AC Current Output to Utility Grid (A) | 60.6 | 75.8 |
Max. AC Current From Utility Grid (A) | 60.6 | 75.8 |
Power Factor | ~1 (Adjustable from 0.8 leading to 0.8 lagging) | |
Max. Total Harmonic Distortion | < 3% |
AC Output Data (Back-up)*¹
Parameter | GW40K-ET-10 | GW50K-ET-10 |
---|---|---|
Back-up Nominal Apparent Power (VA) | 40000 | 50000 |
Max. Output Apparent Power (VA) | 44000 (48000 at 60sec, 60000 at 10sec) | 55000 (60000 at 60sec, 75000 at 10sec) |
Max. Output Current (A) | 66.7 | 83.3 |
Nominal Output Voltage (V) | 380/400, 3L/N/PE | 380/400, 3L/N/PE |
Nominal Output Frequency (Hz) | 50/60 | 50/60 |
Output THDv (@Linear Load) | < 3% |
Efficiency
Parameter | GW40K-ET-10 | GW50K-ET-10 |
---|---|---|
Max. Efficiency | 98.1% | 98.1% |
European Efficiency | 97.5% | 97.7% |
Max. Battery to AC Efficiency | 99.0% | 99.0% |
MPPT Efficiency | 99.5% | 99.5% |
Protection
PV String Current Monitoring | Integrated | |
PV Insulation Resistance Detection | Integrated | |
Residual Current Monitoring | Integrated | |
PV Reverse Polarity Protection | Integrated | |
Battery Reverse Polarity Protection | Integrated | |
Anti-islanding Protection | Integrated | |
AC Overcurrent Protection | Integrated | |
AC Short Circuit Protection | Integrated | |
AC Overvoltage Protection | Integrated | |
DC Switch | Integrated | |
DC Surge Protection | Type II (Type I + II Optional) | |
AC Surge Protection | Type II | |
AFCI | Optional | |
Rapid Shutdown | Integrated | |
Remote Shutdown | Integrated |
General Data
Operating Temperature Range (°C) | -35~+60 | |
Relative Humidity | 0~95% | |
Max. Operating Altitude (m) | 4000 | |
Cooling Method | Smart Fan Cooling | |
User Interface | LED, WLAN + APP | |
Communication with BMS | CAN | |
Communication with Meter | RS485 | |
Communication with Portal | WIFI + LAN / 4G (Optional) | |
Weight (kg) | 62 | |
Dimension (W x H x D mm) | 520 x 660 x 260 | |
Topology | Non-isolated | |
Self-consumption at Night (W) | < 15 | |
Ingress Protection Rating | IP66 | |
Mounting Method | Wall Mounted |
*¹ Backup function can be only realized with STS Box (Static Transfer Switch Box).
* Please visit GoodWe website for the latest certificates.