Instruction Manual for Value Testers models including: sp100-v, LevelPro ShoPro SP100 Level Display Controller, LevelPro ShoPro SP100, Level Display Controller, Display Controller, Controller

www.valuetesters.com

Quick Start Manual

[PDF] Quick Start Manual - Value Testers

Quick Start Manual. Read the user's manual carefully before starting to use the unit. Producer reserves the right to implement changes without prior notice ...


File Info : application/pdf, 11 Pages, 3.27MB

PDF preview unavailable. Download the PDF instead.

sp100-manual
LevelPro® -- ShoPro® SP100
Level Display | Controller
Quick Start Manual

Read the user's manual carefully before starting to use the unit. Producer reserves the right to implement changes without prior notice.

2F4i-n05d47Q©uaIcolintPyroPcersos Cdounctrtolss LOtdn. line at:

Valuetesters.com

info@valuetesters.com1

LevelPro® -- ShoPro® SP100
Level Display | Controller

Safety Information

 De-pressurize and vent system prior to installation or removal!
 Confirm chemical compatibility before use!
 DO NOT exceed maximum temperature or pressure specifications!
 ALWAYS wear safety goggles or face-shield during installation and/or service!
 DO NOT alter product construction!

Warning | Caution | Danger
Indicates a potential hazard. Failure to follow all warnings may lead to equipment damage, or failure, injury, or death.
Note | Technical Notes
Highlights additional information or detailed procedure.

Basic Requirements & User Safety
? Do not use the unit in areas threatened with excessive shocks, vibrations, dust, humidity, corrosive gasses and oils.
? Do not use the unit in areas where there is risk of explosions.
? Do not use the unit in areas with significant temperature variations, exposure to condensation or ice. ? Do not use the unit in areas exposed to direct sunlight.
? Make sure that the ambient temperature (e.g. inside the control box) does not exceed the recommended values. In such cases forced cooling of the unit must be considered (e.g. by using a ventilator).
? The manufacturer is not responsible for any damages caused by inappropriate installation, not maintaining the proper environmental conditions and using the unit contrary to its assignment.
? Installation should be conducted by qualified personnel . During installation all available safety requirements should be considered. The fitter is responsible for executing the installation according to this manual, local safety and EMC regulations.
? GND input of device should be connected to PE wire. ? The unit must be properly set-up, according to the application. Incorrect configuration can cause defective operation, which
can lead to unit damage or an accident.
? If in the case of a unit malfunction there is a risk of a serious threat to the safety of people or property additional, independent systems and solutions to prevent such a threat must be used.
? The unit uses dangerous voltage that can cause a lethal accident. The unit must be switched off and disconnected from the power supply prior to starting installation of troubleshooting (in the case of malfunction).
? Neighboring and connected equipment must meet the appropriate standards and regulations concerning safety and be equipped with adequate overvoltage and interference filters.
? Do not attempt to disassemble, repair or modify the unit yourself. The unit has no user serviceable parts. Defective units must be disconnected and submitted for repairs at an authorized service center.
The unit is designed for operation in an industrial environment and must not be used in a household environment or similar.

2F4i-n05d47Q©uaIcolintPyroPcersos Cdounctrtolss LOtdn. line at:

Valuetesters.com

info@valuetesters.com2

LevelPro® -- ShoPro® SP100
Level Display | Controller

Pipe | Pole Mount Brackets

NEMA 4X Enclosure
Bright LED Display

The ShoPro® Series Level Display | Controller is engineered to be the most durable and dependable wall or pipe-mount remote display in the industry. This all-in-one unit is ready to use straight out of the box, featuring a bright LED display, NEMA 4X enclosure, polycarbonate cover, cord grips, and plastic captive screws.
Designed for industrial applications, it withstands even the harshest corrosive environments and is available with multiple output options.
Features
? All-in-one | Out of the Box Ready to Use ? Visual Alarm -- High | Low Level ? NEMA 4X Enclosure ? Corrosion Resistant Thermoplastic ? Cord Grips Included ­ No Tools Required

Push Buttons

Polycarbonate Cover

Model Selection

ShoPro® SP100 -- Liquid Level LED Display

Part Number SP100
SP100-A SP100-V SP100-A-V

Input 4-20mA 4-20mA 4-20mA 4-20mA

Output 4-20mA 2 Relay + 4-20mA + Audible 2 Relay + 4-20mA + Visual 2 Relay + 4-20mA + Audible & Visual

Technical Specifications

General

Display Displayed Values Transmission Parameters Stability

LED | 5 x 13mm High | Red -19999 ~ 19999 1200...115200 bit/s, 8N1 / 8N2 50 ppm | °C

Housing Material

Polycarbonate

Protection Class

NEMA 4X | IP67

Input Signal | Supply

Standard Voltage

Current: 4-20mA 85 - 260V AC/DC | 16 - 35V AC, 19 - 50V DC*

Output Signal | Supply

Standard Voltage Passive Current Output *

4-20mA | 2 x Relays (5A) + 4-20mA 24VDC 4-20mA | (Operating Range Max. 2.8 - 24mA)

Performance

Accuracy

0.1% @ 25°C One Digit

Accuracy According to IEC 60770 - Limit Point Adjustment | Non-Linearity | Hysteresis | Repeatability

Temperatures

Operating Temperatures

-20 to 158°F | -29 to 70°C

*Optional

2F4i-n05d47Q©uaIcolintPyroPcersos Cdounctrtolss LOtdn. line at:

Valuetesters.com

info@valuetesters.com3

LevelPro® -- ShoPro® SP100
Level Display | Controller

Installation Instructions
The unit has been designed and manufactured in a way assuring a high level of user safety and resistance to interference occurring in a typical industrial environment. In order to take full advantage of these characteristics installation of the unit must be conducted correctly and according to the local regulations. ? Read the basic safety requirements on page 2 prior to starting the installation. ? Ensure that the power supply network voltage corresponds to the nominal voltage stated on the unit's identification label.
The load must correspond to the requirements listed in the technical data. ? All installation works must be conducted with a disconnected power supply. ? Protecting the power supply connections against unauthorized persons must be taken into consideration.
Package Contents
Please verify that all listed parts are consistent, undamaged and included in the delivery / your specified order. After removing the unit from the protective packaging, please verify that all listed parts are consistent, undamaged and included in the delivery/your specified order.
Any transportation damage must be immediately reported to the carrier. Also, write down the unit serial number located on the housing and report the damage to the manufacturer.
Wall Mounting

1

2

3

111.75 mm

62.5mm

Ø4.4

R

dSP

SET

F

AL R1 SP100 R2
Sht

To install device on the wall, pinholes should be made. The distances between holes are mentioned above. This part of the case should be mounted to a wall by screws.

Loosen Box Screws & Open Display Cover

4

5

6

R
dSP SET F

AL R1 SP100 R2
Sht

Remove Display Cover

R
dSP SET F

AL R1 SP100 R2
Sht

Mount on Wall using Screws

2F4i-n05d47Q©uaIcolintPyroPcersos Cdounctrtolss LOtdn. line at:

R
dSP SET F

AL R1 SP100 R2
Sht

R
dSP SET F

AL R1 SP100 R2
Sht

Tighten Srews

Place Display Cover and Tighten Box Screws

Valuetesters.com

info@valuetesters.com4

LevelPro® -- ShoPro® SP100
Level Display | Controller

Pipe | Pole Clamp Installation

1

2

3

Do Not Use Tools

Do Not Use Tools

Open Clamp

Wiring

1

R
SP100 ddSSPP SSEETT F

AL

AL

R R1

1

SP100

RR2 2

SShhtt

2

R
SP100

dSP dSP

SET SET

F

F

Sht Sht

AL AL
R1 SP100 R2 R 1
R2

Lock Clamp on Pipe

3

R

SP100

dSP dSP

SET SET

F

F

Sht Sht

AL R1 SAPL100 R2 R 1
R2

Wire Clamp Open

Turn Cord Grip Counter-Clockwise

4

R SP100

dSP

SET

F

dSP SET

F

Sht Sht

w w w ww.wi.cicoonpnropcorn.ococm o n . c o m

AL AL
R1 SP100 R2 R 1
R2

Power Red Tab : 120VAC wire Blue Terminals : 0VAC wire
4-20mA Output
Sensor Red Tab : +mA Blue Tab : -mA

Remove Cord Grip
5

R
SP100

dSP dSP

SET SET

F

F

Sht Sht

w w www.wi .cicoonpnropcorn.ococmo n . c o m

AL R1 SAPL100 R2 R 1
R2

Insert Wire into Cord Grip
6

R

SP100

dSP

SET

F

dSP SET

F

Sht Sht

w w w ww.wi.cicoonpnropconr.coom c o n . c o m

AL R1 SP A1L 00 R2 R 1
R2

Insert Wire in theTerminals & Close Tabs

Turn Cable Grip Clockwise to Tighten

2F4i-n05d47Q©uaIcolintPyroPcersos Cdounctrtolss LOtdn. line at:

Valuetesters.com

info@valuetesters.com5

LevelPro® -- ShoPro® SP100
Level Display | Controller

Dimensions

130.00

85.25

80.00

127.00

85.25

Wiring Diagram

130.00

62.50

111.75

Power
Yellow

Output
Yellow

Input
Yellow

Red

Blue

Red

Blue

Red

Blue

2F4i-n05d47Q©uaIcolintPyroPcersos Cdounctrtolss LOtdn. line at:

Valuetesters.com

info@valuetesters.com6

LevelPro® -- ShoPro® SP100
Level Display | Controller

Wiring - ShoPro + 100 Series Submersible Level Sensor

SP-100
ShoPro Tank Level Display

Tab 2 : -mA from Sensor (Black) Tab 3 : +mA from Sensor (Red)
34 12

LP100
Junction Box

Power Supply 120VAC

Red Tab : +ve from Junction Box (Green) Blue Tab : -ve from Junction Box (Blue)

Red Black

+mA

-mA

100 Series
Submersible Liquid Level Sensor
Wiring - ShoPro + ProScan®3 Radar Level Sensor
SP-100
ShoPro Tank Level Display

Power Supply 120VAC

Red Tab : +ve from Junction Box (Red) Blue Tab : -ve from Junction Box (Black)

Red Wire : +ve Terminal Black Wire : -ve Terminal

2F4i-n05d47Q©uaIcolintPyroPcersos Cdounctrtolss LOtdn. line at:

Rotate display anti-clockwise to access wiring terminals
ProScan®3
Radar Liquid Level Sensor

Valuetesters.com

info@valuetesters.com7

LevelPro® -- ShoPro® SP100
Level Display | Controller

Display Description & Button Functions

Bright Large Display

Programming Push Buttons

SP100

dSP SET F

Alarm LED Indicator (AL)

AL R1 R2
Sht

Relay 1 & 2 LED Indicators (R)

dSP = Display Programming Menu (Press + Hold for 3 sec.)

SET = Save the Value

F

=

[F] []

Press & Hold Back Menu

for

3

SEC

for

Alarm

Set

= Changing the Values

Sht = [F] Back to Main Display [ ] Changing Menu

Programming 4-20mA

STEPS

1

Main Menu

 dSP
3 Sec.

2

4mA Settings

SET

3

Enter 4mA Value

SET

F DISPLAY

Move Selection Left

Sht
Change Digit Value

OPERATION

Main Display

R

SP100

ddSSPP SSEETT FF

FSht

www.iconprocon.com www.iconprocon.com

AL
AL R1 R1 SP100 RR22

4mA Settings 4mA = Low Level
Enter 4mA Value Factory Default = 0

4mA Empty

4

20mA Settings

SET

5

Enter 20mA Value

SET

20mA Settings 20mA = High Level
Enter 20mA Value

20mA

R

SP100

ddSSPP SSEETT FF

SFht

www.iwcwow.incopnprroococn.oconm .com

AL AL RR1 1SP100 RR2 2

6

Main Display

Main Display

 dSPL = Low Level Value | Empty or Lowest Liquid Level | Factory Default = 0.  dSPH = High Level Value | Enter Maximum Level.

2F4i-n05d47Q©uaIcolintPyroPcersos Cdounctrtolss LOtdn. line at:

Valuetesters.com

info@valuetesters.com8

LevelPro® -- ShoPro® SP100
Level Display | Controller

Alarm Programming

STEPS

1

Main Display

F
3 Sec.

2

Alarm 1 Settings

SET

3

Alarm 1 Value

SET

4

Alarm 2 Settings

SET

5

Alarm 2 Value

SET

6

Hysteresis

SET

7

Hysteresis Value

SET

8

Main Display

DISPLAY

Main Display

F Move Selection Left OPERATION

Sht Change Digit Value

Alarm 1 Settings
Alarm 1 Value Enter Alarm 1 Value
Alarm 2 Settings
Alarm 2 Value Enter Alarm 2 Value
Hysteresis
Hysteresis Value Enter Hysterisis Value
Main Display

Alarm Mode Selection

ALt No.
ALt = 1 ALt = 2 ALt = 3

· CV  AL1  AL1 Relay ON · CV < (AL1-HYS)  AL1 Relay OFF

Description
· CV  AL2  AL2 Relay ON · CV < (AL2-HYS)  AL2 Relay OFF

· CV  AL1  AL1 Relay ON · CV < (AL1-HYS)  AL1 Relay OFF

· CV  AL2  AL2 Relay ON · CV > (AL2+HYS) AL2 Relay OFF

· CV  AL1  AL1 Relay ON · CV > (AL1+HYS)  AL1 Relay OFF

· CV  AL2  AL2 Relay ON · CV > (AL2+HYS)  AL2 Relay OFF

CV = Current Value

Note:

To access the Alarm Mode Selection Menu, press

SET + F



3 Sec.

And then press

SET X 6

2F4i-n05d47Q©uaIcolintPyroPcersos Cdounctrtolss LOtdn. line at:

Valuetesters.com

info@valuetesters.com9

LevelPro® -- ShoPro® SP100
Level Display | Controller

Reset Programming

STEPS

1

Main Display

SET + F


3 Sec.

2

Lock Settings

SET X 2

3

Input Settings

SET X 7

4

Home Screen

SET + F


3 Sec.

5

Lock Settings

SET X 2

6

Input Settings

SET X 7

DISPLAY

Main Display

F Move Selection Left OPERATION

Sht Change Digit Value

Lock Settings
Factory Default : Lk.10 Otherwise meter will enter Lockout Mode*

Input Settings
Int.2 will be displayed. Change Int.2 to Int.4 using

or Sht button.

Main Display
The Value displayed will be 0.00. This value is equal to 4mA output from the sensor

Lock Settings

Input Settings
Int.4 will be displayed. Change Int.4 to Int.2 using

or Sht button.

7

Main Display

SET + F


3 Sec.

8

Lock Settings

SET X 3

Main Display The value displayed is equal to 20mA output from the sensor.
Lock Settings

9

Decimal Point

SET X 6

Decimal Point Change decimal point to 0. (dP.0)

10

Main Display

Main Display Reset Completed

After reset, the dSPL (4mA) and dSPH (20mA) values must be reconfigured. See "Programming 4-20mA" (Page 8) for details.

2F4i-n05d47Q©uaIcolintPyroPcersos Cdounctrtolss LOtdn. line at:

Valuetesters.com

info@valuetesters.com10

LevelPro® -- ShoPro® SP100
Level Display | Controller
Warranty, Returns and Limitations
Warranty
Icon Process Controls Ltd warrants to the original purchaser of its products that such products will be free from defects in material and workmanship under normal use and service in accordance with instructions furnished by Icon Process Controls Ltd for a period of one year from the date of sale of such products. Icon Process Controls Ltd obligation under this warranty is solely and exclusively limited to the repair or replacement, at Icon Process Controls Ltd option, of the products or components, which Icon Process Controls Ltd examination determines to its satisfaction to be defective in material or workmanship within the warranty period. Icon Process Controls Ltd must be notified pursuant to the instructions below of any claim under this warranty within thirty (30) days of any claimed lack of conformity of the product. Any product repaired under this warranty will be warranted only for the remainder of the original warranty period. Any product provided as a replacement under this warranty will be warranted for the one year from the date of replacement.
Returns
Products cannot be returned to Icon Process Controls Ltd without prior authorization. To return a product that is thought to be defective submit a customer return (MRA) request form and follow the instructions therein. All warranty and non-warranty product returns to Icon Process Controls Ltd must be shipped prepaid and insured. Icon Process Controls Ltd will not be responsible for any products lost or damaged in shipment.
Limitations
This warranty does not apply to products which: 1) are beyond the warranty period or are products for which the original purchaser does not follow the warranty procedures outlined above; 2) have been subjected to electrical, mechanical or chemical damage due to improper, accidental or negligent use; 3) have been modified or altered; 4) anyone other than service personnel authorized by Icon Process Controls Ltd have attempted to repair; 5) have been involved in accidents or natural disasters; or 6) are damaged during return shipment to Icon Process Controls Ltd reserves the right to unilaterally waive this warranty and dispose of any product returned to Icon Process Controls Ltd where: 1) there is evidence of a potentially hazardous material present with the product; or 2) the product has remained unclaimed at Icon Process Controls Ltd for more than 30 days after Icon Process Controls Ltd has dutifully requested disposition. This warranty contains the sole express warranty made by Icon Process Controls Ltd in connection with its products. ALL IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE EXPRESSLY DISCLAIMED. The remedies of repair or replacement as stated above are the exclusive remedies for the breach of this warranty. IN NO EVENT SHALL Icon Process Controls Ltd BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING PERSONAL OR REAL PROPERTY OR FOR INJURY TO ANY PERSON. THIS WARRANTY CONSTITUTES THE FINAL, COMPLETE AND EXCLUSIVE STATEMENT OF WARRANTY TERMS AND NO PERSON IS AUTHORIZED TO MAKE ANY OTHER WARRANTIES OR REPRESENTATIONS ON BEHALF OF Icon Process Controls Ltd. This warranty will be interpreted pursuant to the laws of the province of Ontario, Canada.
If any portion of this warranty is held to be invalid or unenforceable for any reason, such finding will not invalidate any other provision of this warranty.

by

2F4i-n05d47Q©uaIcolintPyroPcersos Cdounctrtolss LOtdn. line at:

Valuetesters.com

info@valuetesters.com11



References

Adobe PDF library 17.00