Solis S6 EO Series Off-grid Inverter User Manual
For S6 EO Series Off-grid Inverter
Company Information
Ginlong Technologies Co., Ltd.
No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo, Zhejiang, 315712, P.R.China.
Tel: +86 (0)574 6578 1806
Email: info@ginlong.com
Web: www.solisinverters.com
Please adhere to the actual products in case of any discrepancies in this user manual. If you encounter any problem on the inverter, please find out the inverter S/N and contact us, we will try to respond to your question ASAP.
Smart O&M
In order to improve our products and provide you with higher quality services, this device has a built-in data logging module for collecting relevant information during operation (such as power generation data, fault data).
Commitment:
- We will only collect, use and process your device information for the purpose of improving our products and services.
- We will take all reasonable and feasible measures to ensure that no irrelevant information is collected and we will protect your device information.
- We will not share, transfer or disclose the collected device information with any company, organization or individual.
- When we stop operating products or services, we will stop collecting your device information in a timely manner.
- If you do not want to provide such information, you can notify our company to turn off this function, which will not affect your normal use of other functions of the product.
1. Introduction
1.1 Product Description
Solis EO series inverter is designed for off-grid systems. This series of inverters is highly flexible and can work with or without the grid to provide power to the load. It has battery connections for low voltage batteries and up to 2 PV string inputs. It is able to charge the batteries through the PV, grid or onsite generator.
This manual covers the EO series inverter model list listed below:
S6-EO1P4K-48-EU, S6-EO1P5K-48-EU
Figure 1.1 Product Description
NO. | Description | NO. | Description |
---|---|---|---|
1 | LCD Display | 9 | AC Input |
2 | Status Indicator | 10 | Generator output/input signal |
3 | Battery Indicator | 11 | RS-485 Communication Port |
4 | Fault Indicator | 12 | BMS/NTC Port |
5 | Function Buttons | 13 | Parallel Communication Ports |
6 | PV Input | 14 | Battery Connections |
7 | GEN Port | 15 | COM Port |
8 | AC Output | 16 | Circuit Breaker |
Table 1.1 Product Description
NOTE: Please refer to the specification of the battery before configuration.
1.2 System Description
Figure 1.2 System Connection Diagram
1.3 Packaging
Please ensure that the following items are included in the packaging with your machine:
Inverter x1, Sheet Copper Terminal x10 (For PV/AC Wiring Connection), Fixing Screws x1 (For Grounding Connection), Expansion Bolt x3 (For Mounting), BMS Communication Line x1, Battery power line x2, Temperature Sensor x1 (Optional), Monitor Stick x1 (Optional), Quick Installation Manual x1.
If anything is missing, please contact your local Solis distributor.
2. Safety & Warning
2.1 Safety
The following types of safety instructions and general information appear in this document as described below:
DANGER: "Danger" indicates a hazardous situation which if not avoided, will result in death or serious injury.
WARNING: "Warning" indicates a hazardous situation which if not avoided, could result in death or serious injury.
CAUTION: "Caution" indicates a hazardous situation which if not avoided, could result in minor or moderate injury.
NOTE: "Note" provides tips that are valuable for the optimal operation of your product.
2.2 General Safety Instructions
WARNING: Only devices in compliance with SELV (EN 69050) may be connected to the RS485 and USB interfaces.
WARNING: Please don't connect PV array positive (+) or negative (-) to ground, it could cause serious damage to the inverter.
WARNING: Electrical installations must be done in accordance with the local and national electrical safety standards.
WARNING: Do not touch any inner live parts until 5 minutes after disconnection from the utility grid and the PV input.
WARNING: To reduce the risk of fire, over-current protective devices (OCPD) are required for circuits connected to the inverter. The DC OCPD shall be installed per local requirements. All photovoltaic source and output circuit conductors shall have isolators that comply with the NEC Article 690, Part II.
CAUTION: Risk of electric shock, do not remove the upper cover (lower cover can be removed for connection). There is no user serviceable parts inside, refer servicing to qualified and accredited service technicians.
CAUTION: The PV array supplies a DC voltage when they are exposed to sunlight.
CAUTION: Risk of electric shock from energy stored in capacitors of the Inverter, do not remove cover for 5 minutes after disconnecting all power sources (service technician only). Warranty may be voided if the cover is removed without authorization.
CAUTION: The surface temperature of the inverter can reach up to 60°C (140 °F). To avoid risk of burns, do not touch the surface of the inverter while it's operating. Inverter must be installed out of the reach of children.
NOTE: PV module used with inverter must have an IEC 61730 Class A rating.
WARNING: Operations below must be accomplished by licensed technician or Solis authorized person.
WARNING: Operator must put on the technicians' gloves during the whole process in case of any electrical hazards.
WARNING: For PV system, between the PV string and PV input of the inverter, it is required to install a DC isolator to meet local installation regulations.
3. Installation
3.1 Select a Location for the Inverter
To select a location for the inverter, the following criteria should be considered:
- Exposure to direct sunlight may cause the output power to decrease. It must install the inverter indoors and avoid direct sunlight and rain.
- This inverter is IP21 rated and it can be used indoors with environmental pollution level II. Please install it indoors to avoid rain, spraying water or splashing water.
- It is recommended that the inverter is installed in a cooler ambient which doesn't exceed 131°F/55°C.
WARNING: Risk of fire Despite careful construction, electrical devices can cause fires.
- Do not install the inverter in areas containing highly flammable materials or gases.
- Do not install the inverter in potentially explosive atmospheres.
- Install on a wall or strong structure capable of bearing the weight of the machine (14kg).
- Install vertically with a maximum incline of +/- 5 degrees, exceeding this may cause output power derating.
- To avoid overheating, always make sure the flow of air around the inverter is not blocked. A minimum clearance of 400mm should be kept between inverters or objects and 800mm clearance between the bottom of the machine and the ground.
Figure 3.1 Inverter Mounting Clearance
- Visibility of the LEDs and LCD should be considered.
- Adequate ventilation must be provided.
NOTE: Nothing should be stored on or placed against the inverter.
3.2 Mounting the Inverter
WARNING: The inverter must be mounted vertically.
Select the mounting height of the inverter and mark the mounting holes. It's recommended to install the inverter tighten by using two M5 screws.
Figure 3.2 Wall Mount Inverter
Fix the two holes on the top of the machine and one hole in the box with screws.
Figure 3.3 Fix inverter on the wall
3.3 PV Cable Installation
Before connecting inverter, please make sure the PV array open circuit voltage is within the limit of the inverter.
Please use approved DC cable for PV system.
Before connection, please make sure the polarity of the output voltage of PV array matches the "DC+"and"DC-"symbols.
- Select a suitable DC cable and strip the wires out by 7±0.5mm. Please refer to the table below for specific specifications.
Figure 3.4
Cable type | Range | Cross section (mm²) Recommended value |
---|---|---|
Industry generic PV cable | 4.0~6.0 (12~10AWG) | 4.0 (12AWG) |
- Take the DC terminal out of the accessory bag, turn the screw cap to disassemble it, and take out the waterproof rubber ring.
Figure 3.5
Figure 3.6
Figure 3.7
Figure 3.8
Figure 3.9
Figure 3.10
CAUTION: If DC inputs are accidently reversely connected or inverter is faulty or not working properly, it is NOT allowed to turn off the DC switch. Otherwise it may cause DC arc and damage the inverter or even lead to a fire disaster. The correct actions are: Use a clip-on ammeter to measure the DC string current. If it is above 0.5A, please wait for the solar irradiance reduces until the current decreases to below 0.5A. Only after the current is below 0.5A, you are allowed to turn off the DC switches and disconnect the PV strings. In order to completely eliminate the possibility of failure, please disconnect the PV strings after turning off the DC switch to avoid secondary failures due to continuous PV energy on the next day. Please note that any damages due to wrong operations are not covered in the device warranty.
3.4 AC Cable Installations
There are three AC terminals and the connection steps are showing in following sections. The AC Input and Gen ports are sharing the same type of connector, the connection steps are also the same.
AC Input | AC Output | Gen | |
---|---|---|---|
Cable Diameter | 14-17mm | 12-14mm | 14-17mm |
Cross Sectional Area | 10mm² | 6mm² | 10mm² |
Exposure Length | 9mm | 7mm | 9mm |
3.4.1 AC Input Connection and Gen Connection
Step 1: Strip the AC wires for about 9mm.
Figure 3.11
Step 2: Set the parts on the cable.
Figure 3.12
Figure 3.13
Step 4: Push wire connector housing into shell and insert claw and seal part into shell and then tighten the nut with torque 4±0.5N.m.
Figure 3.14
Figure 3.15
Step 5: Mating device and wire connector with a click sound.
Figure 3.16
Step 6: If need to disconnect the connector, please use the special disassembly tool to unmate device and wire connector, then turn the nut in the opposite direction and press the unlocking position with the disassembly tool, hold the cable and pull it out in the direction of the arrow.
Figure 3.17
3.4.2 AC Output Connection
The steps to assemble the AC grid terminal connectors are listed as follows:
a) Disassemble the AC connector. Strip the AC wires about 7mm.
Figure 3.18
b) Push pins into housing and use a slotted screwdriver in this step. Please try to pull out the wire to make sure the it's well connected.
Figure 3.19
c) Insert seal and clamp finger into body, then tighten the nut, torque 2.5+/-0.5N·m.
Figure 3.20
d) Mating plug and socket: Push the locker onto the socket housing completely, then rotate the locker according to the direction instructed by the marks on the locker. (Warning: hold the body)
Figure 3.21
3.5 Grounding
To effectively protect the inverter, a grounding methods must be performed. Connect the external grounding terminal. To connect the grounding terminal on the heat sink, please follow the steps below:
- Remove insulation sleeve 10 mm for positive and negative conductors.
- Insert the wire into the sleeve and use a suitable crimping tool for crimping.
- Connect the grounding cable to the grounding point on the heat sink and tighten the grounding screw. The torque rating is 1.0-1.2Nm.
Item | Cable Size (AWG) | Cable Size (Cross Section) | Torque |
---|---|---|---|
PE | 12 | 3.3mm² | 1.0-1.2Nm |
Figure 3.22 Grounding connection
3.6 Battery Terminal Components
Step 1: Take out the 1m battery cable from the package.
Figure 3.23
Step 2: Insert the connector end to the inverter battery port with a click sound.
Figure 3.24
Step 3: If need disassemble the connector, please press the button on the connector and pull out from the inverter battery port.
Figure 3.25
3.7 Battery Communication
The EO Series inverter uses RS485 cable to communicate with BMS/NTC port to communicate with the BMS of Lithium and NTC of Lead-acid battery.
Figure 3.26
NOTE: NTC temperature sensor should be attached to the surface of the lead-acid battery for detecting the temperature in real time.
Procedure for Connecting the BMS Cable or NTC Cable: If it is connected to a lithium battery, please take out the BMS communication cable from the accessory package. Connect one side of the cable to the battery and the other side to the BMS/NTC port; If it is connected to a lead-acid battery, please take out the NTC communication cable from the accessory package. Connect the RJ45 side of the cable to the BMS/NTC port, and put the other side with the ring near the negative pole of the battery.
NOTE: Lead-Acid and other older-technology battery types require experienced and precise design, installation and maintenance to work effectively. For lead-acid battery, battery SOC calculation may not be accurate according to battery inconformity between cells, battery aging or other specifications of lead-acid battery etc.
BMS/NTC PIN Definition Communication interface bewteen inverter and battery is RS485 with a RJ45 connector.
Figure 3.27
3.8 External Communication
RS-485 is one standard communication interface which can transmit the real data from inverter to PC or other monitoring equipments.
Figure 3.28
Procedure for Connecting the RS485 Cable: User can use the RS-485 port for external communication. User should prepare the Comm-cable by themselves according to the pin-definition sheet shown as below. The insert terminal need to use the RJ45 plug. Insert one side of the cable into the RS-485 port of the inverter, and insert another side into PC or other monitioring device.
RS485 PIN Definition Communication interface bewteen inverter and external device is RS485 with a RJ45 connector.
Figure 3.29
3.9 Generator Connection
S6 off-grid storage inverter is designed to operate in pure off grid condition or where the grid is unstable. AC Generator can be connected in the system to work with S6 off-grid storage inverter as an alternative backup source. The AC Generator can be connected in two positions, either on the AC Input port or the GEN port of the inverter.
Option 1: Generator on the AC Input Port AC Generator can be connected on the AC input port of the S6 off-grid storage inverter. There is no need to install extra communication wires, the S6 off-grid storage inverter by design will not export power to the AC input port. In a place where the grid is unstable, external auto transfer switch can be installed to switch between grid connection and generator connection when necessary.
Option 2: Generator on the GEN port S6 off-grid storage inverter is designed with a dedicated generator input port which can actively control the generator operation together with the generator input/output communication signals.
Figure 3.30
Figure 3.31
3.10 AC Coupling Connection
The AC Output port of the S6 off-grid storage inverter is capable of connecting loads as well as connecting PV grid tied inverter. The S6 off-grid storage inverter can dynamically increase the AC frequency in linearly relationship on the AC Output Port when battery is close to full. PV grid tied inverters, which support frequency-power response, can passively respond to the frequency change and adjust their generating power. In this way, S6 off-grid storage inverter can control the PV grid tied inverter's power without a physical communication cable in between. The PV inverter should correctly set the overfrequency derating point to match the S6 off-grid storage inverter's AC coupling setting, otherwise the S6 off-grid storage inverter may not be able to correctly control the power of the PV inverter.
WARNING: To use this function, please contact the manufacturer of the PV grid tied inverter to confirm the capability and configuration steps of the frequency-power response. Then adjust the AC coupling settings of S6 off-grid storage inverter accordingly. Solis is not responsible for any damages due to wrong configuration when using this function.
NOTE: This application is only applicable when AC Input and Gen port are left empty.
Figure 3.32
3.11 Parallel Connection
S6 off-grid storage inverter supports multiple kinds of parallel connection. Customers can flexibly utilize the parallel functions to expand the system capacity.
System | Support Parallel Port | Limitations |
---|---|---|
Single Phase System Parallel | AC Input Port, AC Output Port, Battery Port, GEN Port | Max 6 Units of Inverter can be connected in parallel |
Three Phase System Parallel | AC Input Port, AC Output Port, Battery Port, GEN Port | Max 6 Units of Inverter can be connected in parallel (2 Unit per Phase) |
WARNING: All inverters in the parallel system MUST be with the same model/same power rating.
WARNING: When operating in parallel condition, if using the GEN port to connect the generator, all inverters' GEN port MUST be connected in parallel and then connect to a single generator. (The G-DRY/G-FB signal wire needs to be connected to the MASTER inverter of the system). It is not supported to connect multiple individual generators to each inverter's GEN port when the system is running in parallel.
WARNING: When operating in parallel condition, if using the Battery port to connect the battery, all inverters' Battery port MUST be connected in parallel and then connect to a single battery bank (The BMS communication or NTC wire needs to be connected to the MASTER inverter of the system). It is not supported to connect multiple individual battery units to each inverter's battery port when the system is running in parallel.
WARNING: Please carefully size the cable, DC breaker and AC breaker specification according to the actual capacity of the parallel system.
NOTE: The parallel communication cable needs to be connected in daisy chain among all inverters in the parallel system. Two RJ45 parallel ports are provided at the bottom of the inverter for parallel communication.
3.12 External Communication Stick Connection
Inverter provides a Monitoring port which can collect data from inverter and transmit it to monitoring-website via an external monitoring data collector. For details please refer to WiFi Stick Data logger Quick installation guide.
Figure 3.35
Figure 3.36
NOTE: When a single inverter is running, DIP switch 1 and 2 shall be both at the bottom position. When multiple inverters are paralleled, DIP switch: the master inverter need to have 2 DIP switches enabled (Both Pin 1 & Pin2).
3.13 LED Indicates
There are three LED indicators on the inverter which indicate the working status.
Light | Color | Status | Description |
---|---|---|---|
STATUS | Green | FLASHING | The inverter is in standby (Slow flashing for 3S). |
Green | ON | The inverter is normal operation. Or The inverter is operating normally. | |
Green/Yellow | OFF | The inverter is deenergized. | |
BATTERY | Yellow/Red | GREEN FLASHING | Battery is charging. |
Yellow/Red | GREEN CONSTANT | Battery is discharging. | |
Yellow/Red | OFF | Battery is not installed or in the off position. | |
ALARM | Yellow/Red | YELLOW CONSTANT | Battery failure. |
Yellow/Red | YELLOW CONSTANT | There is an alarm but system is operational. | |
Yellow/Red | RED CONSTANT | There is an alarm and the system has stopped. | |
OFF | No Alarm. |
Table 3.3 Status Indicator Lights
4. Commissioning
4.1 Preparation of Commissioning
- Ensure all the devices are accessible for operation, maintenance and service.
- Check and confirm that the inverter is firmly installed.
- Ensure space for ventilation is sufficient for one inverter or multiple inverters.
- Ensure Nothing is left on top of the inverter or battery module.
- Ensure inverter and accessories are correctly connected.
- Ensure cables are routed in a safe location or protected against mechanical damage.
- Ensure warning signs and labels are suitably affixed and durable.
4.2 Commissioning Procedure
If all the items mentioned above meet the requirements, proceed as follows to start up the inverter for the first time.
- Switch on the AC-Output and AC-Input.
- Refer to "Part 5" to configure the parameters. Ensure to run through the Startup Wizard.
- Switch on the DC circuit breaker between inverter and battery.
- If the battery equipped is Pylon Li-ion Battery, actuate the switch on the battery manually. The relay will make 'clicking' sounds and it will take a short-time to work automatically.
- Verify the system is working properly.
- Proceed to setup the systems communication and refer to the datalogger manual.
- All manuals can be found at www.solisinverters.com
5. Operation
5.1 Startup guide
Please follow the steps to complete the initial setup process.
Steps: Start-up Wizard > Language > Time > Connect battery? > Battery Type > Connect generator? > Back up setting > Setting successfully
Figure 5.1 Operation Overview
5.2 Main Menu
There are four submenu in the Main Menu (see Figure 5.1):
- Information
- Settings
- Advanced Info.
- Advanced Settings
5.3 Information
In the information section, operating data and information data can be viewed. Sub-sections include:
- General Information
- System Information
- Energy Records
- BMS information
5.3.1 General Information
The example displays are shown in the following figures. The user can view it by pressing the up and down keys. Values are for reference only.
Display | Description |
---|---|
Inverter SN: 000000000000000 | Shows the inverter serial number. |
Model: S6-E01P5K-48-EU | Shows the model of the device. |
SoftVer.: 040000 | Shows the DSP and ARM version of the inverter. |
HMI Software | ARM version of the inverter. |
Figure 5.2 General Information
5.3.2 System Information
The example displays are shown in the following figures. The user can view it by pressing the up and down keys. Values are for reference only.
Display | Description |
---|---|
V DC: 000.0V | Shows the voltage on DC side. |
I DC: 000.0A | Shows the current on DC side. |
V AC: 000.0V | Shows the voltage on AC side. |
I AC: 000.0A | Shows the current on AC side. |
Grid Frequency: 00.00Hz | Shows the grid frequency value. |
Battery V: 000.0V | Shows the battery voltage. |
Battery I: 000.0A | Shows the battery current. |
Backup V: 000.0V | Shows the voltage on backup. |
Backup P: 00.0kW | Shows the power on backup. |
Charge P: 00.0kW | Shows the charging power. |
DisCharge P: 00.0kW | Shows the discharging power. |
Gen P: | Show the power of generator |
Figure 5.3 System Information
5.3.3 Energy Records
Sub-sections of the Yield information section include:
- Battery Yield
- Grid Yield
- Load Yield
The example displays are shown in the following figures. Values are for reference only.
Display | Description |
---|---|
BattChgE Total: 0000000kWh | Shows the total battery charged energy. |
BattChgE Today: 000.0kWh | Shows today's battery charged energy. |
BattChgE Lastday: 000.0kWh | Shows yesterday's battery charged energy. |
BattDisChgE Total: 0000000kWh | Shows the total battery discharged energy. |
BattDisChgE Today: 0000000kWh | Shows today's battery discharged energy. |
BattDisChgE Lastday: 0000000kWh | Shows yesterday's battery discharged energy. |
Figure 5.4 Battery Yield
Display | Description |
---|---|
GridGetE Total: 0000000kWh | Shows the total energy received from the grid. |
GridGetE Today: 000.0kWh | Shows today's energy received from the grid. |
GridGetE Lastday: 000.0kWh | Shows yesterday's energy received from the grid. |
Figure 5.5 Grid Yield
5.3.4 BMS Information
The example displays are shown in the following figures. The user can view it by pressing the up and down keys. Values are for reference only.
Display | Description |
---|---|
Battery V: 00.00V Battery I: +00.00A | Battery V: Shows battery voltage (From BMS). Battery I: Shows battery current (From BMS). |
ChargeLmt: 000.0A DischargLmt: 000.0A ChargeVLmt: 000.0A DischargVLmt: 000.0A | ChargeLmt: Shows battery charge limit(Current). DischargelLmt: Shows battery discharge limit(Current). ChargeVLmt: Shows battery charge limit(Voltage). DischargVLmt: Shows battery discharge limit(Voltage). |
SOC Value: 000% SOH Value: 000% | SOC value: Shows battery state of charge. SOH value: Shows battery state of health.. |
BMS Status: CAN Fail | Shows that Battery BMS communication status. |
BMS Version: 0.0 | Shows that Battery BMS version. |
Figure 5.9 BMS Information
BMS ONLY support CAN communication not RS485, and all the data will display "0" when the battery has been selected as Lead-acid battery which is monitored by NTC in CAN/NTC port.
5.4 Settings
The following submenus are displayed when the Settings menu is selected:
- Set Time/Date
- Set Address
- Set Mute
- Mode Settings
5.4.1 Set Time/Date
This function allows time and date setting. When this function is selected, the LCD will display a screen as shown in Figure 5.10.
Figure 5.10 Set Time
5.4.2 Set Address
This function is used to set inverter address for data logger connection/modbus communication/parallel connection.
Figure 5.11 Set Address
5.4.3 Set Mute
This function allows you to turn on/off the keypad tone and buzzer sound. Select YES to disable the sound and select NO to enable the sound. Default is "YES".
Figure 5.12 Set Mute
5.4.4 Mode Settings
This section describes the working logic of each work mode of the inverter.
Display | Description |
---|---|
Work Mode: Self Use | Self-Use Mode stores the excess PV power into the battery. If the battery is charged, or there is no battery, the excess PV power will be exported (sold) back to the utility company. If the system is set to not export any power, then the inverter will curtail the PV power (derate the inverter output power). |
Self use Switch: Enable/Disable | The switch is to enable/disable the self-use mode. |
Time of Use Switch: Enable/Disable | The switch is to enable/disable the Time of use setting to allow user to set a customized charging/discharging pattern. |
Time of Use chg curr | To Set the Charge Current for battery in the state of time of use. |
Time of Use Disch Curr | To Set the Discharge Current for battery in the state of time of use. |
Chg Tim Slot 1-6: Start/stop | To Set the customized charging/discharging time period. Inverter will follow self-use logic during undefined time period. These settings are only effective when Time of Use Switch is enabled. |
Dischg Tim Slot 1-6: Start/stop | To Set the customized charging/discharging time period. Inverter will follow self-use logic during undefined time period. These settings are only effective when Time of Use Switch is enabled. |
AllowGridCharging: Enable/Disable | To Set if the system is allowed to use grid power to charge the battery. |
BatReserve Switch: Enable/Disable | To Set if the system needs to reserve a certain SOC of battery during normal operation and only to be used when grid is lost to support the load for a longer time. |
Reserved SOC Set | Reserved SOC. Only effective when Battery Reserve Switch is enabled. |
Grid Charge Power Limit | The max power limit from grid can be used to reserve the battery SOC level. Only effective when Battery Reserve Switch is enabled. |
Figure 5.13 Work Mode
Display | Description |
---|---|
Work Mode: Off-Grid | Off-Grid Mode is only to be used by systems that are not electrically connected to the grid at all. |
OffGrid Switch: Enable/Disable | The switch is to enable/disable the off grid mode. |
Offgrid overdischarge SOC | To set the overdischarge SOC of the battery under off grid condition. |
Figure 5.14 Work Mode
5.5 Advanced Information
NOTE: This area is for fully qualified and accredited technicians only.
Enter the password 0010 to access to the following sections.
- Alarm Message
- Warning Message
- Running Status
- Communication data
- Yield Profile
Figure 5.15 Enter Password
The screen can be scrolled by pressing the UP/DOWN keys. Pressing the ENTER key gives access to a submenu. Press the ESC key to return to the Main Menu.
5.5.1 Alarm Message
The display shows the 500 latest alarm messages. Screens can be scrolled by pressing the UP/DOWN keys.
Figure 5.16 Alarm Message
Press the ESC key to return to the previous menu. Press the ENTER key to return to the next menu. The example displays are shown in the following figures. Values are for reference only.
5.5.2 Warning Message
The display shows the warning messages appeared on screen, can store in total 500pcs. Press the ESC key to return to the previous menu.
Figure 5.17 Warning Message
5.5.3 Running Status
This section is for maintenance personnel to view the running information (Values are for reference only).
Figure 5.18 Running Status
Display | Description |
---|---|
DC Bus Voltage: 0.0V | Shows DC bus voltage. |
Power Factor: +0.000 | Shows power factor of the inverter. |
Power Limit%: 000% | Shows the power output percentage of the inverter. |
Inverter Temp: +0.0degC | Shows heat sink temperature of the inverter. |
Grid Standard: | Shows grid standard. |
Flash State: | Shows the data migration time. |
Figure 5.19 General Status
NOTE: The advanced status is reserved for Solis technicians.
Display | Description |
---|---|
Ground Voltage: 000.0V | Shows the voltage to the ground. |
Relay-Fault Func.: RUN | Shows the status of the relay. |
GRID-INTF.02 Func.: RUN | Shows the interference status from the grid. |
Figure 5.20 Advanced Status
5.5.4 Communication data
This section shows the communication data between HMI and DSP. For Solis engineers ONLY.
Figure 5.21 Communication Data
5.5.5 Yield Profile
5.5.5.1 Energy Battery
Shows the battery charge & discharge energy.
Display | Description |
---|---|
Battery Charge | Shows the battery charge energy. |
Battery Discharge | Shows the battery discharge energy. |
Figure 5.22 Battery Charge
5.5.5.2 Grid Energy
Energy received from the grid. or Energy from the grid.
Display | Description |
---|---|
Energy Received | Shows the energy received from the grid. |
Figure 5.23 Energy Received from Grid
5.5.5.3 Energy Backup
Energy provided from backup port.
Display | Description |
---|---|
Daily Energy | Shows the daily energy. |
Monthly Energy | Shows the monthly energy. |
Yearly Energy | Shows the yearly energy. |
Figure 5.24 Energy Backup
5.6 Advanced Settings
NOTE: This area is for fully qualified and accredited technicians only.
Enter the password 0010 to access to the following sections.
- Backup Settings
- Feed Grid Setting
- Battery Settings
- Special Settings
- Parallel Settings
- Generator Settings
- AC Coupling Settings
- Password Settings
Figure 5.25 Enter Password
The screen can be scrolled by pressing the UP/DOWN keys. Pressing the ENTER key gives access to a submenu. Press the ESC key to return to the Main Menu.
5.6.1 Backup Settings
Display | Description |
---|---|
Backup ON/OFF | When you select ON, AC output port is enabled. When you select OFF, AC output port is disabled. |
Backup Voltage | Shows the backup voltage. |
Backup Frequency | Shows the backup frequency. |
Volt Droop | Voltage droop function when overload on backup port. |
Min. Droop V | Min allowed voltage for voltage droop function. |
Figure 5.26 Backup Settings
5.6.2 Feed Grid Setting
Display | Description |
---|---|
Allow Feed in Grid: Enable/Disable | When you turn on the enable switch, excess energy is fed into the grid. When you turn off the enable switch, no energy is fed into the grid. |
Figure 5.27 For Feed Grid Setting
NOTE: The Feed Grid Setting enable switch can be turned on only when the utility grid allows the inverter to export power to the grid.
5.6.3 Battery Settings
The section has 2 parts:
- Battery Select
- Advanced Battery Settings
5.6.3.1 Battery Select
The battery selection includes the following 5 options:
- Lithium battery
- 48V Lithium battery (without comm)
- 52.1V Lithium battery (without comm)
- Lead Acid
- No Battery
5.6.3.2 Advanced Battery Settings
The following is the setting of battery parameters. For different lithium batteries, the inverter has been set with the optimal battery configuration, and it is recommended that customers do not modify it without authorization. For lead-acid batteries, the installer should set it according to the battery type. For lithium batteries, these are the following settings:
Display | Description |
---|---|
Max Charge Curr | To set the max allowed charge current. |
Max Dischar Curr | To set the max allowed discharge current. |
Battery Wakeup | To set the the type of battery wake. |
Figure 5.29 For Lithium Batteries
There are two types of battery wake-up: Wake up Manually and Wack Up Automatic
Display | Description |
---|---|
Manual Wakeup funcion. Switch: ON/OFF | Inverter will charge the battery port at the wakeup voltage level and maintain for a certain time period in order to wakeup battery in sleep mode. |
Voltage Set | Wake up voltage setting. |
Time Set | Wake up time setting. |
Figure 5.30 Wake up Manually
Display | Description |
---|---|
Automatic battery wake up function. Inverter will initiate the battery wake up function when it is powered up. | Automatic battery wake up function. Inverter will initiate the battery wake up function when it is powered up. |
Wake up time setting. | Wake up time setting. |
Figure 5.31 Wack Up Automatic
Display | Description |
---|---|
Overdischar SOC | When battery reached overdischarge SOC, inverter will stop discharging the battery. |
Force SOC Set | Due to selfdischarging, battery SOC may drop to lower than overdischarge SOC. When reached forcecharge SOC, inverter will charge the battery automatically to avoid battery entering sleep mode. |
Figure 5.28 For Lithium Batteries
Display | Description |
---|---|
Battery Healing switch: ON/OFF | To enable/disable the battery healing function. During low PV period, battery SOC may be kept low SOC for a long time. Battery healing function will charge the battery until the target SOC. |
Battery Healing SOC | Target SOC for battery healing function, the value ranges from 80 to 100%. The default value is 100%. |
Figure 5.32 Battery Healing
Display | Description |
---|---|
Force Power Set | Max grid power allowed for battery forcecharging. |
ECO Function | To enable/disable the ECO function. When at night and battery SOC recahed overdischarge SOC, inverter will shutdown the battery circuit to avoid battery power consumption. |
Quick Charge | Enable the quick charge function, inverter will charge the battery at the max capability. |
Figure 5.33 For Lithium Batteries
For lead acid batteries, these are the following settings:
Display | Description |
---|---|
Battery Capacity | Battery capacity in Ah. |
Bulk Chg. Volt | Voltage setting for Constant voltage charging stage. Also called absorption voltage. |
Overdischar Volt | When battery reached overdischarge voltage, inverter will stop discharging the battery. |
Figure 5.34 For Lead Acid Batteries
Display | Description |
---|---|
Force Volt Set | Due to selfdischarging, battery voltage may drop to lower than overdischarge voltage. When reached forcecharge voltage, inverter will charge the battery automatically to avoid battery entering sleep mode. |
Float Volt | Voltage setting for floating charging stage. |
Batt equalization | This function is designed to realize the equalizing charging stage for the batteries. |
Equalized time. | Equalizing Charging Time Period. |
Equalized Volt | Equalizing Charging Voltage. |
Equalized interval | Interval between equalizing charging. |
Temp compem | Voltage-Temperature compensation coefficient. |
Figure 5.35 For Lead Acid Batteries
5.6.4 Special Settings
NOTE: These functions are for maintenance personnel only. Misuse of these functions could lead to equipment damage, inverter function or reduced inverter production.
The section has 8 parts:
- Power Switch
- Batt Line ZO
- MPPT Multi-peak Scan
- RisoLim
- Daily PV-ISO-dec
- Clear Energy
- Restore Settings
- AFCI Setting
5.6.4.1 Power Switch
When choose On. Inverter will generate power (default) When choose Off, inverter stops generating.
Display | Description |
---|---|
Power Switch: ON |
Figure 5.36 Power Switch Setting
5.6.4.2 Batt Line ZO
Batt Line ZO is the battery line impedance setting. The purpose is to compensate the resistance loss of the battery line. The default value is 10mΩ, 0-99mΩ can be set.
Display | Description |
---|---|
Batt Line ZO: 10mΩ |
Figure 5.37 Battery Line ZO Setting
5.6.4.3 MPPT Multi-peak Scan
Enable periodic MPPT scanning to track the global max power point of the system.
Display | Description |
---|---|
Scan Switch: Enable/Disable | Enable/Disable the scanning. |
Scan Interval: 1800S | Set the scan interval. |
Figure 5.38 MPPT Multi-peak Scan Setting
5.6.4.4 RisoLim
Set the PV insulation protection limit.
Display | Description |
---|---|
RisoLim | Set the PV insulation protection limit. |
Figure 5.39 RisoLim Setting
5.6.4.5 Daily PV-ISO-dec
Enable/Disable the Daily PV-ISO Detection.
Display | Description |
---|---|
Daily PV-ISO-dec: Enable/Disable | Enable/Disable the Daily PV-ISO Detection. |
Figure 5.40 Daily PV-ISO-dec Setting
5.6.4.6 Clear Energy
Clear Energy will reset the historical yield of the inverter.
NOTE: This function is only for maintenance personnel.
5.6.4.7 Restore Settings
This section allows you to reset all the settings and bring the settings back to default values.
Figure 5.41 Restore Settings
5.6.4.8 AFCI Protect
Display | Description |
---|---|
AFCI Protect: | Enable/Disable the Arc fault detection function. |
Clear AFCI Fault: | UL1699B Arc Fault Alarm Clear. |
Figure 5.42 AFCI Protect Setting
5.6.5 Parallel Settings
Display | Description |
---|---|
Parallel Mode: Single/Parallel | To set if the inverter is running in single unit condition or parallel condition. |
Physical Address ID | To set the physical address ID for parallel operation. |
Set Master/Slave: Slave/Master | To set if the inverter is a master unit or slave unit in parallel operation. |
Connected Phase: None/Single Phase/ Phase A(Three phase)/ Phase B(Three phase)/ Phase C(Three phase) | To set which phase the inverter is connected to. |
Figure 5.43 Parallel Settings
5.6.6 Generator Settings
Display | Description |
---|---|
With Gen: Enable/Disable | To set if the system is connected with generator or not. |
Gen Power Set: Gen Rated P/ Gen Max. Charge P | To set the generator rated output power. |
Gen Position: Gen port/Grid port | To set position where the generator is connected. |
Start-Stop SOC/V | To set the battery SOC/voltage at which the generator will step in or stop operation. |
Gen signal: Enable/Disable | To set if the generator signal is available. |
Gen Force: 0/1 | To force start up the generator. |
Gen Stop: 0/1 | To force stop the generator. |
Figure 5.44 Generator Settings
5.6.7 AC Coupling Settings
Display | Description |
---|---|
Switch: Enable/Disable | To enable/disable the AC coupling function to use frequency adjustment to control the PV inverter generation. |
Position: Gen/Back Up | To set the position where the PV inverter is connected. |
ON_SOC | When the battery SOC drops to this setting, the PV inverter starts to work. |
ON_Bat_Volt | When the battery Volt drops to this setting, the PV inverter starts to work. |
Start Frequency | When the battery SOC reaches ON-SOC, the inverter will first control the frequency to the start frequency, corresponding to the starting point of the inverter's overfrequency load reduction. |
OFF_SOC | To set the AC coupling stop SOC at which the frequency will reach AC coupling Max. Fre. |
OFF_Bat_Volt | To set the AC coupling stop Voltage at which the frequency will reach AC coupling Max.Fre. |
Max.fre | The max frequency allowed in the system for controlling PV Inverter generation. |
Figure 5.45 AC Coupling Settings
5.6.8 Password Settings
Figure 5.46 Password Settings
6. Maintenance
Solis EO series inverter do not require any regular maintenance. However, cleaning the heatsink will help the inverter dissipate heat and increase the lifespan. The dirt on the inverter can be cleaned with a soft brush.
CAUTION: Do not touch the surface when the inverter is operating. Some parts may be hot and cause burns.
The LCD and the LED status indicator lights can be cleaned with cloth.
NOTE: Never use any solvents, abrasives or corrosive materials to clean the inverter.
7. Troubleshooting
The inverter has been designed in accordance with international interconnection standards for safety and electromagnetic compatibility requirements. Before delivering to the customer the inverter has been subjected to several test to ensure optimal operation and reliability.
In case of a failure the LCD screen will display an alarm message. The alarm descriptions and their corresponding alarm messages are listed in Table 7.1: When a fault occurs, the "Fault" state will be shown on the main screen. Follow the steps below to check the fault status.
Steps: Enter → Down → Advanced Information→ Enter Password → Enter → Down →Warning Message.
Figure 7.1 Advanced Information
Figure 7.2 Enter Password
Press DOWN to select Warning Message, the press ENTER.
Figure 7.3 Warning Messages
Alarm Message | Failure description | Solution |
---|---|---|
GAB Over Volt GBC Over Volt G CA Over Volt GAB Over Volt2 GBC Over Volt2 GCA Over Volt2 GAB Trans Ov V G BC Trans Ov V G AB 10min Ov V G BC 10min Ov V G CA 10min Ov V Grid Trans Ov V | Gird Overvoltage | 1. Resistant of AC cable is too high, Change AC cable for larger size. 2. Adjust the protection limit if it's allowed by electrical company. |
GAB Under Volt G BC Under Volt G CA Under Volt GAB Under Volt2 G BC Under Volt2 G CA Under Volt2 | Grid Undervoltage | 1. Adjust the protection limit In user define setting if it's allowed by electrical company. |
Grid Over Freq. Grid Over Freq.2 | Grid Overfrequency | 1. Adjust the protection limit In user define setting if it's allowed by electrical company. |
Grid Under Freq. Grid Under Fre.2 | Grid Underfrequency | 1. Adjust the protection limit In user define setting if it's allowed by electrical company. |
Grid Over Imp. | Grid Impedance is too large | 1. Adjust the protection limit In user define setting if it's allowed by electrical company. |
No Grid | NO Grid Voltage | 1. Check connection and grid switch. 2. Check grid voltage on the inverter terminals. |
Grid Unbalance | Grid voltage is unbalanced | 1. Restart inverter or contact installers. |
Grid Freq. Spark | Grid frequency is sparking | 1. Check connection of AC cable is normal. 2. Confirm connnection of AC cable is normal. 3. Restart System and ensure whether the fault is existing. |
Grid A Over Curr Grid B Over Curr Grid C Over Curr Phase Over Curr | Grid overcurrent | 1. Restart inverter. 2. Change power board. |
Ig Tracking Err | Grid current tracking fail | 1. Restart inverter or contact installers. |
Pv1 Over Volt Pv2 Over Volt Pv3 Over Volt Pv4 Over Volt | DC Overvoltage | 1. Reduce the module number in series. |
Bus Under Volt | DC Bus is undervolgage | 1. Check inductor connection of inverter. 2. Check driver connection. |
Vbus Unbalance2 | DC Bus is unbalanced voltage | 1. Restart System and ensure whether the fault is existing. |
Pv1 Over Curr Pv2 Over Curr | Pv1 overcurrent Pv2 overcurrent | 1. Restart inverter. 2. Identify the fault and remove the strings from fault MPPT. 3. Change power board. |
PV Input Disturb | DC input disturbs | 1. Restart inverter. 2. Change power board. |
PV Connect Err | DC polarity reverse fault | 1. Check whether the polarity of PV cable has reversed connection. |
PV Mid Iso | PV midpoint grounding fault | 1. Check whether PV strings have trouble in insulation. |
Pv1 Under Volt Pv2 Under Volt | Pv1 undervoltage Pv2 undercurrent | 1. Check whether the DC cable is damaged. 2. Restart system and ensure whether the fault is existing. |
Vbus Sample Err | Bus voltage sampling fault | 1. Check whether the DC cable is damaged. 2. restart system and ensure whether the fault is existing. |
Boost Over Curr | Boost overcurrent | 1. Restart System and ensure whether the fault is existing. |
Grid Disturb | Gird disturbing | 1. Restart inverter. 2. Change power board. |
Dsp Init Err | DSP initializing protection | 1. Restart inverter or contact installers. |
Module Over Temp System Over Temp | Over temperature protection | 1. Check whether the environment around inverter is poor heat dissipation. 2. Confirm whether inverter installation is satisfied with requirements. |
PV Iso Pro | PV isolation protection | 1. Remove all DC inputs then restart and reconnect to inverter one by one. 2. Identify the faulty string and check the string isolation. |
Ig Leak Pro1 Ig Leak Pro2 Ig Leak Pro3 Ig Leak Pro4 | Leakage current protection | 1. Check AC and DC connection. 2. Check the connections inside the inverter. |
Input Relay Err | Relay fault | 1. Restart inverter or contact installers. |
Dsp B Fault | Communication fault betweent main DSP and slave DSP | 1. Restart inverter or contact installers. |
Ig DC Err | DC component fault | 1. Restart inverter or contact installers. |
Alarm Message | Failure description | Solution |
---|---|---|
12V Power Err | 12V power undervoltage | 1. Restart System and ensure whether the fault is existing. |
Leak Sensor Err | Leakage self-detection fault | 1. Restart System and ensure whether the fault is existing. |
Dsp SelfCk Err | Abnormal self-detection of DSP | 1. Check the environment temperature around inverter. 2. Restart System and ensure whether the fault is existing. |
Under Temp | Undertemperature protection | 1. Check the environment temperature around inverter. 2. Restart System and ensure whether the fault is existing. |
AFCI Check Err | Arc self-detection fault | 1. Check whether there is arc in PV connection and restart inverter. |
AFCI Err | Arc protection | 1. Restart inverter or contact installers. |
Dsp Ram Err | Abnormal SRAM of DSP board | 1. Restart inverter or contact installers. |
Dsp Flash Err | Abnormal FLASH of DSP board | 1. Restart inverter or contact installers. |
Dsp PC Err | Abnormal PC pointer of DSP board | 1. Restart inverter or contact installers. |
Dsp Reg Err | Abnormal key register of DSP | 1. Restart inverter or contact installers. |
Grid Disturb2 | Grid disturbing 02 | 1. Restart inverter. 2. Change power board. |
Output Short Circuit | Output Short Circuit | 1. Restart inverter or contact installers. |
Grid Resonance | Grid resonance | 1. Restart inverter. 2. Change power board. |
Trans Ov-lg | Transient overcurrent of AC side | 1. Restart inverter or contact installers. |
Hw Ov-Vbatt | Battery overvoltage and firmware fault | 1. Restart inverter. 2. Return to factory for repairing. |
LLC Over Curr | LLC firmware overcurrent | 1. Restart inverter. 2. Return to factory for repairing. |
Batt Over Volt | Battery overvoltage detection | 1. Check whether battery breaker has tripped. 2. Check whether battery is damaged. 3. Check whether battery parameter settings are reasonable. |
Batt Under Volt | Battery undervoltage detection | 1. Check whether battery breaker has tripped. 2. Check whether battery is damaged. 3. Check whether battery parameter settings are reasonable. |
No Battery | Battery module is not connected | 1. Check whether the power line of battery is connected correctly. 2. Check whether the output voltage of battery is correct. |
Bypass Over Volt | Bypass overvoltage fault | 1. Check whether Backup port wire is normal. 2. Restart system and confirm whether the fault is existing. |
Bypass Over Curr | Bypass overcurrent fault | 1. Restart inverter or contact installers. |
Soft Start Err | Soft start failure | 1. Restart inverter. 2. Return to factory for repairing. |
Nbus Earthing Err | Impedance of N-Ground fault | 1. Check whether the Grounding line is connected correctly. |
Pbus Earthing Err | Impedance of L-Ground fault | 1. Check whether the Grounding line is connected correctly. |
Eeprom Init Err | Eeprom initializing fault | 1. Restart inverter or contact installers. |
BMS Over Volt | Battery overvoltage of BMS | 1. Restart inverter or contact installers. |
BMS Under Volt | Battery undervoltage of BMS | 1. Restart inverter or contact installers. |
BMS Over Temp | Battery overtemperature of BMS | 1. Restart inverter or contact installers. |
BMS Under Temp | Battery undertemperature of BMS | 1. Restart inverter or contact installers. |
BMS Dischg. Ov_C | Discharge overcurrent of BMS | 1. Start the battery and contact battery manufacture for handling if the fault still exists. |
BMS Chg. Ov_C | Charge overcurrent of BMS | 1. Start the battery and contact battery manufacture for handling if the fault still exists. |
BMS Internal | External fault of BMS | 1. Start the battery and contact battery manufacture for handling if the fault still exists. |
BMS Imbalance | Battery unbalance of BMS | 1. Confirm whether connection of meter or CT is correct. |
Fail safe | CT or Meter failure | 1. Confirm whether connection of meter or CT is correct. |
Meter Comm Fail | Meter communication fault | 1. Check whether the communication cable of meter is damaged. 2. Confirm whether DRM cable connection is reliable. 3. Check whether meter is damaged. |
Can Comm Fail | Battery communication fault | 1. Check whether the communication cable of meter is damaged. |
Alarm Message | Failure description | Solution |
---|---|---|
Dsp Comm Fail | DSP communication fault | 1. Restart DSP to ensure whether the fault is existing. |
BMS Alarm | Alarm fault of BMS | 1. Restart the Battery to ensure whether the fault is existing. |
Batt Name Err | Uncorrespondence of battery select | 1. Confirm whether the selected battery brand in inverter is consistent with the actual battery. |
Heatsink Ntc Err | External temperature sensor failure | 1. Check whether temperature sensor has been installed in the Lead-acid battery. 2. Check whether the NTC cable is connected to the inverter correctly. 3. Restart system and confirm whether the fault still exists. |
Buck Boost Ov_C | Buckboost overcurrent | 1. Restart system and confirm whether the fault still exists. |
AC Reverse | AC connected reversely | 1. Check the cable polarity of AC side. |
Lead-acid batt UTP | Undertemperature of lead-acid battery | 1. Check whether the environment temperature of Lead-acid is in the normal range. |
Lead-acid batt OTP | Overtemperature of lead-acid battery | 1. Check whether the environment temperature of Lead-acid is in the normal range. |
Table 7.1 Fault Message and Description
NOTE: If the inverter displays any alarm message as listed in Table 7.1; please turn off the inverter and wait for 5 minutes before restarting it. If the failure persists, please contact your local distributor or the service center.
Please keep ready with you the following information before contacting us.
- Serial number of Solis Inverter;
- The distributor/dealer of Solis Inverter (if available);
- Installation date.
- The description of problem (i.e. the alarm message displayed on the LCD and the status of the LED status indicator lights. Other readings obtained from the Information submenu (refer to Section 3.10) will also be helpful.);
- The PV array configuration (e.g. number of panels, capacity of panels, number of strings, etc.);
- Your contact details.
8. Specifications
Solar Charger
Model | S6-EO1P4K-48-EU |
---|---|
Recommended max. PV power | 5.5kW |
Max. input voltage | 500V |
Start-up voltage | 90V |
MPPT voltage range | 90-430V |
Full load MPPT voltage range | 171-430V |
Max. input current | 16A/16A |
Max. short circuit current | 40A |
Max. Solar Charge Current | 100A |
MPPT number / Max. input strings number | 1/2 |
Battery
Battery Type | Li-ion/Lead-acid |
---|---|
Rated battery voltage | 48V |
Max. charge / discharge power | 5000W/5000W |
Max. charge / discharge current | 100A |
Communication | CAN/RS485 |
Inverter Output
Rated output power | 4kVA/4kW |
---|---|
Operation phase | 1/N/PE |
Rated output voltage | 230V±1% |
Rated grid frequency | 50Hz/60Hz±0.1% |
Surge Capacity | 8kVA |
Max. Output Current | 20A |
Output Voltage Waveform | Pure sine wave |
Transfer Time | 10ms typical, 20ms Max |
THDv (@linear load) | <3% |
Peak Efficiency(PV-AC) | 96.6% |
AC Charger
Model | S6-EO1P4K-48-EU |
---|---|
Rated Input Voltage | 230V |
Selectable Voltage Range | 90-280V |
AC Frequnence Range | 50Hz/60Hz(Auto sensing) |
Max. AC Charge Current | 60A |
Generator
Rated input power | 5kW |
---|---|
Rated input current | 80A |
Protection
Output Over Voltage Protection | Yes |
---|---|
Outout Over Current Protection | Yes |
Short Circuit Protection | Yes |
Surge Protection | Yes |
Temperature Compensation Protection | Yes |
Integrated AFCI (DC arc-fault circuit protection) | Yes |
Gerneral Data
Dimension (W*H*D) | 335*450*160mm |
---|---|
Net Weight | 14kg |
Relative Humidity | 5% to 95% (Non-condensing) |
Operation Temperature Range | -10°C-60°C |
Storage Temperature Range | -25°C-60°C |
Ingress Protection | IP21 |
Max. Operation Altitude | 2000m |
Parallel capability | 6 units |
Safety/EMC standard | IEC 62109, IEC 61000, 55011 |
Features
DC Connection | Terminal Connectors |
---|---|
AC Connection | Terminal Connectors |
Display | LCD |
Communication Interface | CAN, BMS, RS485, Dry-contact, Bluetooth, Optional: Wifi |
Solar Charger
Model | S6-EO1P5K-48-EU |
---|---|
Recommended max. PV power | 6.5kW |
Max. input voltage | 500V |
Start-up voltage | 90V |
MPPT voltage range | 90-430V |
Full load MPPT voltage range | 215-430V |
Max. input current | 16A/16A |
Max. short circuit current | 40A |
Max. Solar Charge Current | 100A |
MPPT number / Max. input strings number | 1/2 |
Battery
Battery Type | Li-ion/Lead-acid |
---|---|
Rated battery voltage | 48V |
Max. charge / discharge power | 5000W/5000W |
Max. charge / discharge current | 100A |
Communication | CAN/RS485 |
Inverter Output
Rated output power | 5kVA/5kW |
---|---|
Operation phase | 1/N/PE |
Rated output voltage | 230V±1% |
Rated grid frequency | 50Hz/60Hz±0.1% |
Surge Capacity | 10kVA |
Max. Output Current | 25A |
Output Voltage Waveform | Pure sine wave |
Transfer Time | 10ms typical, 20ms Max |
THDv (@linear load) | <3% |
Peak Efficiency (PV-AC) | 96.6% |
File Info : application/pdf, 32 Pages, 3.16MB
DocumentDocumentReferences
Corel PDF Engine Version 24.3.0.571Related Documents
![]() |
Solis S6 Series Hybrid Inverter User Manual User manual for the Solis S6 Series Hybrid Inverter, covering installation, operation, safety, and specifications for models like S6-EH3P5K2-H, S6-EH3P6K2-H, and others. |
![]() |
Solis S6 Series Hybrid Inverter User Manual User manual for the Solis S6 Series Hybrid Inverter, covering product description, safety warnings, installation, commissioning, maintenance, troubleshooting, and specifications for residential hybrid systems. |
![]() |
Solis S6 Series Hybrid Inverter User Manual Comprehensive user manual for the Solis S6 Series Hybrid Inverter, covering installation, safety, operation, and troubleshooting for models S6-EH3P3K-H-EU through S6-EH3P10K-H-EU. |
![]() |
Solis S6-GR1P(2.5-6)K Single-Phase Inverters Datasheet Technical specifications and features of the Solis S6-GR1P(2.5-6)K series of single-phase inverters, including efficiency, input/output parameters, protection features, and general data. |
![]() |
Solis S6 Series Inverter User Manual: Commissioning, Shutdown, and Troubleshooting Comprehensive user manual for the Solis S6 Series inverter, covering commissioning procedures, shutdown steps, troubleshooting common alarms, and detailed technical specifications. Includes guidance on app usage, settings, and safety precautions. |
![]() |
Solis S6 Mini Series Inverters: Datasheet and Features Detailed datasheet and features for Solis S6 Mini Series Solar Inverters (0.7kW to 3.6kW), including technical specifications, protection features, and general data. |
![]() |
Solis S6 Series Hybrid Inverter User Manual Comprehensive user manual for the Solis S6 Series Hybrid Inverter, covering installation, operation, safety, and troubleshooting for commercial hybrid systems. Includes details on applicable models and system configurations. |
![]() |
Solis S6 Mini Single Phase Inverter Installation and Operation Manual This manual provides detailed instructions for the installation, operation, and maintenance of the Solis S6 Mini Single Phase Inverter. It covers product description, safety instructions, overview, installation procedures, start and stop operations, maintenance, troubleshooting, and specifications. |