5. Commissioning & Shutdown

5.1 Preparation of Commissioning

There are three ways to download and install the latest APP:

  1. Visit www.soliscloud.com to download the latest version APP.
  2. Search "Soliscloud" in Google Play or App Store.
  3. Scan the QR code to download "Soliscloud".

5.2 Commissioning Procedure

Step 1: Measure DC voltage of PV strings and battery and ensure the polarity is correct.

Step 2: Measure AC voltage and frequency and ensure they are within local standard.

Step 3: Switch on the external AC breaker to power on the inverter control board. (Bluetooth signal available)

Step 4: Turn on Bluetooth switch on your mobile phone and then open the Soliscloud APP. Click "More Tools" -> "Local Operation" -> "Connect with Bluetooth".

Step 5: Select the Bluetooth signal from the inverter. (Bluetooth Name: Solis-Inverter SN)

Step 6: If you are the installer, please select the account type as Installer. If you are the plant owner, please select the account type as Owner. Then set your own initial password for control verification. (The first log-in must be finished by installer in order to do the initial set up)

Step 7: After the log in for the first time, initial settings are required.

Step 8: Now the initial settings on the inverter have been set and you can switch on the inverter DC switch and switch on the battery breaker to start up the system. You can also explore in the APP to check the operating data, alarm message, or other advanced settings.

Step 9: If the Owner forgot the password, please contact the installer. Installer logs in and goes to "Setting" -> "More" -> "Change Password" to reset the password for the owner's account. If the Installer forgot the password, please contact the Solis service team.

5.3 Shutdown Procedure

  1. Turn off the AC breaker at the grid connection point.
  2. Turn off the DC switch of the inverter.
  3. Turn off the battery breaker.
  4. Wait for the device to be powered off and the system shutdown is completed.

6. Troubleshooting

Solis S6 Series inverter does not require any regular maintenance. However, cleaning the heatsink will help the inverter dissipate heat and increase the lifetime of inverter. The dirt on the inverter can be cleaned with a soft brush.

CAUTION: Do not touch the surface when the inverter is operating. Some parts may be hot and could cause burns. Turn OFF the inverter (refer to Section 6.2) and let it cool down before you do any maintenance or cleaning of the inverter.

The screen and the LED status indicator lights can be cleaned with a cloth if they are too dirty to be read.

Note: Never use any solvents, abrasives, or corrosive materials to clean the inverter.

The inverter has been designed in accordance with international grid-tied standards for safety and electromagnetic compatibility requirements. Before being delivered to the customer, the inverter is subjected to several tests to ensure reliability of operation and reliability.

In case of a failure, the app will display an alarm message. In this case, the inverter may stop feeding energy into the grid. The alarm descriptions and their corresponding alarm messages are listed in Table 6.1:

Table 6.1 Fault message and description
Alarm Message Failure description Solution
ARC-FAULT ARC detected in DC circuit 1. Check if there is an arc in the PV connection and restart inverter.
AFC Check FAULT AFC module self check fault 1. Restart inverter or contact installer.
DCinj-FAULT High DC injection current 1. Restart inverter or contact installer.
DSP-B-FAULT Comm. failure between main and slave DSP 1. Restart inverter or contact installer.
DC-INTF DC input overcurrent 1. Restart inverter.
2. Identify and remove the string related to the faulty MPPT.
3. Change power board.
G-IMP High grid impedance 1. User design function allows the protection limit to be adjusted if it is allowed by electrical company.
GRID-INTF01/02 Grid interference 1. Restart inverter.
2. Change power board.
IGBT-OV-I Over IGBT current 1. Restart inverter or contact installer.
IGFOL-F Grid current tracking fail 1. Restart inverter or contact installer.
IG-AD Grid current sampling fail 1. Check AC and DC connection.
2. Check inverter inside cable connection.
ILeak-PRO 01/02/03/04 leakage current protection 1. Restart inverter or contact installer.
INI-FAULT Initialization system fault 1. Ensure the battery is connected properly.
2. Verify the output battery voltage is correct.
NO-Battery Unconnected battery 1. Check connections and grid switch.
2. Verify the grid voltage is correct on the AC terminals inside the inverter wiring box.
NO-GRID No grid voltage 1. Check inverter inductor connection.
2. Check driver connection.
OV-BUS Over DC bus voltage 1. Check inverter inductor connection.
2. Check driver connection.
OV-DC01/02/03/04 Over DC voltage 1. Reduce the module number in series.
OV-DCA-I DC input overcurrent 1. Restart inverter.
2. Identify and remove the string of the faulty MPPT.
3. Change power board.
OV-G-V01/02/03/04/05 Over grid voltage 1. Resistance of AC Cable is too high. Increase the gauge of grid cables.
2. Adjust the protection limit if it is permitted by electrical company.
OV-G-I Over grid current 1. Restart inverter.
2. Change power board.
OV-G-F01/02 Over grid frequency 1. User design function allows the protection limit to be adjusted if it is permitted by electrical company.
OV-IgTr AC side transient overcurrent
OV-ILLC LLC hardware overcurrent 1. Restart inverter.
2. Return-factory repair.
OV-VBackup Backup overvoltage fault
OV-TEM Over Temperature 1. Check inverter surrounding ventilation.
2. Determine if there is direct sunlight on the inverter during hot weather.
OV-Vbatt1 The detection of battery overvoltage 1. Verify the protection point for over voltage is set correctly.
2. Restart inverter.
OV-Vbatt-H Battery overvoltage hardware fault 1. Check if any part of the battery input circuit is tripped, ie. battery fuses, battery circuit breaker.
2. Restart inverter.
Over-Load Backup overload fault 1. Check the load of Backup port is over rating output power or not.
2. Reduce the load of Backup port, then restart inverter.
PV ISO-PRO01/02 PV isolation protection 1. Remove all DC input, reconnect and restart inverter one by one.
2. Identify which string causes the fault and check the isolation of the string.
RelayChk-FAIL Relay check fail 1. Restart inverter or contact installer.
UN-BUS01/02 Under DC bus voltage 1. Check inverter inductor connection.
2. Check driver connection.
UN-G-F01/02 Under grid frequency 1. Use user define function to adjust the protection limit if it's allowed by electrical company.
UN-G-V01/02 Under grid voltage 1. Use user define function to adjust the protection limit if it's allowed by electrical company.
12Power-FAULT 12V power supply fault 1. Restart inverter or contact installer.

NOTE: If the inverter displays any alarm message listed in Table 6.1, please turn off the inverter and wait for 5 minutes before restarting it. If the failure persists, please contact your local distributor or the service center.

If you have any technical problems with the hybrid system, please contact the Solis after-sale service. We recommend gathering the following information before making contact in order to get timely support.

Item Details Supplemental Info
Inverter SN SN from nameplate
Inverter Firmware Version 6 digits of number or letter (Check the inverter user manual for the path)
DC connections Solar modules, numbers, configuration
Detailed description of the problem Battery SN, Firmware version Check battery user manual for the path
Is it connected to Solis Monitoring Portal? Yes/No
Take pictures showing all the cable connections in the system (Videos preferred) If available

7. Specifications

Technical Data S6-EH1P3.8K-H-US S6-EH1P5K-H-US
Input DC (PV side)
Recommended max. PV power 6080W 8000W
Max. input voltage 600V 600V
Rated voltage 380V 380V
Start-up voltage 80V 80V
MPPT voltage range 80-550V 80-550V
Full load MPPT voltage range 140-450V 140-450V
Max. input current per string 16A 16A
Max. short circuit current per string 25.6A 25.6A
Number of MPPTs/Number of strings per MPPT 2/1 3/1
Energy Storage
Battery type Lithium-ion Lithium-ion
Battery voltage range 120-500V 120-500V
Maximum charge/discharge current 25A 25A
Battery Communication CAN/RS485 CAN/RS485
Number of batteries per inverter See Battery Compatibility Sheet See Battery Compatibility Sheet
AC Output (Grid)
Rated output power 3.8kW 5kW
Max. apparent output power 3.8kW 5kW
Rated output voltage 240 V/120 V 240 V/120 V
Rated frequency 60 Hz 60 Hz
Rated output current 15.8A 20.8A
Max. output current 15.8A 20.8A
THDI <3% <3%
AC Input (Grid)
Input voltage range 211-264V 211-264V
Max. input current 23.8A 31.2A
Frequency range 59-61 Hz 59-61 Hz
AC Output (Backup and Off-grid)
Rated output power 3.8kW 5kW
Max. apparent output power 6.1 kVA, 10 sec 8 kVA, 10 sec
Back-up switch time < 10 ms < 10 ms
Phase Power 240V Split-Phase 240V Split-Phase
Rated output voltage(L1-L2)/(L1/L2-N) 240 V/120 V 240 V/120 V
AC output voltage range 211-264 V/105-132 V 211-264 V/105-132 V
Rated grid frequency 60 Hz 60 Hz
Frequency range 55-65Hz 55-65Hz
Rated AC output current 15.8A 20.8A
Max. output overcurrent protection, 10sec 25.4A 33.3A
Max. allowable phase imbalance 100% 100%
Backup support configurations Dedicated loads and whole-home (with a Solis Power Hub) Dedicated loads and whole-home (with a Solis Power Hub)
Power Factor >0.99 (0.8 leading - 0.8 lagging) >0.99 (0.8 leading - 0.8 lagging)
THDv(@linear load) <3% <3%
Efficiency
PV Max. efficiency 97.6% 97.6%
PV CEC efficiency 97.2% 97.2%
BAT charged by PV Max. efficiency 98.5% 98.5%
BAT charged/discharged to AC Max. efficiency 97.0% 97.0%
Protection
Ground fault detection Yes Yes
Residual (leakage) current detection Yes Yes
Integrated AFCI (DC arc-fault circuit protection) Yes Yes
DC reverse-polarity protection Yes (PV only) Yes (PV only)
Rapid Shutdown NEC 2017 Integrated SunSpec-certified Transmitter Integrated SunSpec-certified Transmitter
Compatible RSD Receivers See MLRSD compatibility sheet See MLRSD compatibility sheet
Protection class/Over voltage category I/II I/II
Technical Data S6-EH1P6K-H-US S6-EH1P7.6K-H-S-US
Input DC (PV side)
Recommended max. PV power 9600W 12160W
Max. input voltage 600V 600V
Rated voltage 380V 380V
Start-up voltage 80V 80V
MPPT voltage range 80-550V 80-550V
Full load MPPT voltage range 155-450V 175-450V
Max. input current per string 16A 16A
Max. short circuit current per string 25.6A 25.6A
Number of MPPTs/Number of strings per MPPT 3/1 3/1
Energy Storage
Battery type Lithium-ion Lithium-ion
Battery voltage range 120-500V 120-500V
Maximum charge/discharge current 25A 25A
Battery Communication CAN/RS485 CAN/RS485
Number of batteries per inverter See Battery Compatibility Sheet See Battery Compatibility Sheet
AC Output (Grid)
Rated output power 6kW 7.6kW
Max. apparent output power 6kW 7.6kW
Rated output voltage 240 V/120 V 240 V/120 V
Rated frequency 60 Hz 60 Hz
Rated output current 25.0A 31.7A
Max. output current 25.0A 31.7A
THDI <3% <3%
AC Input (Grid)
Input voltage range 211-264V 211-264V
Max. input current 37.5A 47.6A
Frequency range 59-61 Hz 59-61 Hz
AC Output (Backup and Off-grid)
Rated output power 6kW 7.6kW
Max. apparent output power 9.6 kVA, 10 sec 12.2 kVA, 10 sec
Back-up switch time < 10 ms < 10 ms
Phase Power 240V Split-Phase 240V Split-Phase
Rated output voltage(L1-L2)/(L1/L2-N) 240 V/120 V 240 V/120 V
AC output voltage range 211-264 V/105-132 V 211-264 V/105-132 V
Rated grid frequency 60 Hz 60 Hz
Frequency range 55-65Hz 55-65Hz
Rated AC output current 25.0A 31.7A
Max. output overcurrent protection, 10sec 40.0A 50.7A
Max. allowable phase imbalance 100% 100%
Backup support configurations Dedicated loads and whole-home (with a Solis Power Hub) Dedicated loads and whole-home (with a Solis Power Hub)
Power Factor >0.99 (0.8 leading - 0.8 lagging) >0.99 (0.8 leading - 0.8 lagging)
THDv(@linear load) <3% <3%
Efficiency
PV Max. efficiency 97.6% 97.6%
PV CEC efficiency 97.2% 97.2%
BAT charged by PV Max. efficiency 98.5% 98.5%
BAT charged/discharged to AC Max. efficiency 97.0% 97.0%
Protection
Ground fault detection Yes Yes
Residual (leakage) current detection Yes Yes
Integrated AFCI (DC arc-fault circuit protection) Yes Yes
DC reverse-polarity protection Yes (PV only) Yes (PV only)
Rapid Shutdown NEC 2017 Integrated SunSpec-certified Transmitter Integrated SunSpec-certified Transmitter
Compatible RSD Receivers See MLRSD compatibility sheet See MLRSD compatibility sheet
Protection class/Over voltage category I/II I/II
Technical Data S6-EH1P7.6K-H-L-US S6-EH1P8K-H-US
Input DC (PV side)
Recommended max. PV power 12160W 12800W
Max. input voltage 600V 600V
Rated voltage 380V 380V
Start-up voltage 80V 80V
MPPT voltage range 80-550V 80-550V
Full load MPPT voltage range 175-450V 185-450V
Max. input current per string 16A 16A
Max. short circuit current per string 25.6A 25.6A
Number of MPPTs/Number of strings per MPPT 4/1 4/1
Energy Storage
Battery type Lithium-ion Lithium-ion
Battery voltage range 120-500V 120-500V
Maximum charge/discharge current 50A 50A
Battery Communication CAN/RS485 CAN/RS485
Number of batteries per inverter See Battery Compatibility Sheet See Battery Compatibility Sheet
AC Output (Grid)
Rated output power 7.6kW 8kW
Max. apparent output power 7.6kW 8kW
Rated output voltage 240 V/120 V 240 V/120 V
Rated frequency 60 Hz 60 Hz
Rated output current 31.7A 33.3A
Max. output current 31.7A 33.3A
THDI <3% <3%
AC Input (Grid)
Input voltage range 211-264V 211-264V
Max. input current 47.6A 49.9A
Frequency range 59-61 Hz 59-61 Hz
AC Output (Backup and Off-grid)
Rated output power 7.6kW 8kW
Max. apparent output power 12.2 kVA, 10 sec 12.8 kVA, 10 sec
Back-up switch time < 10 ms < 10 ms
Phase Power 240V Split-Phase 240V Split-Phase
Rated output voltage(L1-L2)/(L1/L2-N) 240 V/120 V 240 V/120 V
AC output voltage range 211-264 V/105-132 V 211-264 V/105-132 V
Rated grid frequency 60 Hz 60 Hz
Frequency range 55-65Hz 55-65Hz
Rated AC output current 31.7A 33.3A
Max. output overcurrent protection, 10sec 50.7A 53.3A
Max. allowable phase imbalance 100% 100%
Backup support configurations Dedicated loads and whole-home (with a Solis Power Hub) Dedicated loads and whole-home (with a Solis Power Hub)
Power Factor >0.99 (0.8 leading - 0.8 lagging) >0.99 (0.8 leading - 0.8 lagging)
THDv(@linear load) <3% <3%
Efficiency
PV Max. efficiency 97.6% 97.6%
PV CEC efficiency 97.2% 97.2%
BAT charged by PV Max. efficiency 98.5% 98.5%
BAT charged/discharged to AC Max. efficiency 97.0% 97.0%
Protection
Ground fault detection Yes Yes
Residual (leakage) current detection Yes Yes
Integrated AFCI (DC arc-fault circuit protection) Yes Yes
DC reverse-polarity protection Yes (PV only) Yes (PV only)
Rapid Shutdown NEC 2017 Integrated SunSpec-certified Transmitter Integrated SunSpec-certified Transmitter
Compatible RSD Receivers See MLRSD compatibility sheet See MLRSD compatibility sheet
Protection class/Over voltage category I/II I/II
Technical Data S6-EH1P10K-H-US S6-EH1P11.4K-H-US
Input DC (PV side)
Recommended max. PV power 16000W 18240W
Max. input voltage 600V 600V
Rated voltage 380V 380V
Start-up voltage 80V 80V
MPPT voltage range 80-550V 80-550V
Full load MPPT voltage range 230-450V 245-450V
Max. input current per string 16A 16A
Max. short circuit current per string 25.6A 25.6A
Number of MPPTs/Number of strings per MPPT 4/1 4/1
Energy Storage
Battery type Lithium-ion Lithium-ion
Battery voltage range 120-500V 120-500V
Maximum charge/discharge current 50A 50A
Battery Communication CAN/RS485 CAN/RS485
Number of batteries per inverter See Battery Compatibility Sheet See Battery Compatibility Sheet
AC Output (Grid)
Rated output power 10kW 11.4kW
Max. apparent output power 10kW 11.4kW
Rated output voltage 240 V/120 V 240 V/120 V
Rated frequency 60 Hz 60 Hz
Rated output current 41.7A 47.5A
Max. output current 41.7A 47.5A
THDI <3% <3%
AC Input (Grid)
Input voltage range 211-264V 211-264V
Max. input current 62.6A 71.3A
Frequency range 59-61 Hz 59-61 Hz
AC Output (Backup and Off-grid)
Rated output power 10kW 11.4kW
Max. apparent output power 16 kVA, 10 sec 18.2 kVA, 10 sec
Back-up switch time < 10 ms < 10 ms
Phase Power 240V Split-Phase 240V Split-Phase
Rated output voltage(L1-L2)/(L1/L2-N) 240 V/120 V 240 V/120 V
AC output voltage range 211-264 V/105-132 V 211-264 V/105-132 V
Rated grid frequency 60 Hz 60 Hz
Frequency range 55-65Hz 55-65Hz
Rated AC output current 41.7A 47.5A
Max. output overcurrent protection, 10sec 66.7A 76.0A
Max. allowable phase imbalance 100% 100%
Backup support configurations Dedicated loads and whole-home (with a Solis Power Hub) Dedicated loads and whole-home (with a Solis Power Hub)
Power Factor >0.99 (0.8 leading - 0.8 lagging) >0.99 (0.8 leading - 0.8 lagging)
THDv(@linear load) <3% <3%
Efficiency
PV Max. efficiency 97.6% 97.6%
PV CEC efficiency 97.2% 97.2%
BAT charged by PV Max. efficiency 98.5% 98.5%
BAT charged/discharged to AC Max. efficiency 97.0% 97.0%
Protection
Ground fault detection Yes Yes
Residual (leakage) current detection Yes Yes
Integrated AFCI (DC arc-fault circuit protection) Yes Yes
DC reverse-polarity protection Yes (PV only) Yes (PV only)
Rapid Shutdown NEC 2017 Integrated SunSpec-certified Transmitter Integrated SunSpec-certified Transmitter
Compatible RSD Receivers See MLRSD compatibility sheet See MLRSD compatibility sheet
Protection class/Over voltage category I/II I/II
Technical Data S6-EH1P7.6K-H-L-US S6-EH1P8K-H-US
General data
Dimensions (H/W/D) 26.61*21.85*9.39 in (676*555*238.5 mm) 26.61*21.85*9.39 in (676*555*238.5 mm)
Weight 81.04 lbs (36.76 kg) 81.04 lbs (36.76 kg)
Topology Transformerless Transformerless
Operation temperature range -25 ~ +60 °C / -31 ~ +140 °F -25 ~ +60 °C / -31 ~ +140 °F
Ingress protection NEMA 4X(IP66) NEMA 4X(IP66)
Noise emission (Typical) <30 dB (A) <30 dB (A)
Cooling method Natural convection Natural convection
Max.operation altitude 13120 ft (4000 m) 13120 ft (4000 m)
Compliance UL1741SB, UL1741SA, IEEE1547-2018, UL1699B, UL1998, FCC Part15 ClassB, California Rule21, Heco Rule 14H, NEC 690.12-2020, CAN/CSA C22.2 No.107.1-1 UL1741SB, UL1741SA, IEEE1547-2018, UL1699B, UL1998, FCC Part15 ClassB, California Rule21, Heco Rule 14H, NEC 690.12-2020, CAN/CSA C22.2 No.107.1-1
Generator support Yes; up to 25 kW (with a Solis Power Hub) Yes; up to 25 kW (with a Solis Power Hub)
Features
DC connection 1 in. knockouts for conduit (x2) on the side and bottom; Spring clamp terminals 1 in. knockouts for conduit (x2) on the side and bottom; Spring clamp terminals
AC connection 2 in. knockouts for conduit (x3) on the side and bottom; Spring clamp terminals 2 in. knockouts for conduit (x3) on the side and bottom; Spring clamp terminals
Interface LED indicator lights, Bluetooth/Phone app LED indicator lights, Bluetooth/Phone app
Monitoring Platform Solis Cloud (modbus map and API sharing available upon request) Solis Cloud (modbus map and API sharing available upon request)
Communication RS485, Optional: Cellular, Wi-Fi, LAN RS485, Optional: Cellular, Wi-Fi, LAN
Warranty 10 years standard (Extend to 20 years) 10 years standard (Extend to 20 years)
Technical Data S6-EH1P10K-H-US S6-EH1P11.4K-H-US
Input DC (PV side)
Recommended max. PV power 16000W 18240W
Max. input voltage 600V 600V
Rated voltage 380V 380V
Start-up voltage 80V 80V
MPPT voltage range 80-550V 80-550V
Full load MPPT voltage range 230-450V 245-450V
Max. input current per string 16A 16A
Max. short circuit current per string 25.6A 25.6A
Number of MPPTs/Number of strings per MPPT 4/1 4/1
Energy Storage
Battery type Lithium-ion Lithium-ion
Battery voltage range 120-500V 120-500V
Maximum charge/discharge current 50A 50A
Battery Communication CAN/RS485 CAN/RS485
Number of batteries per inverter See Battery Compatibility Sheet See Battery Compatibility Sheet
AC Output (Grid)
Rated output power 10kW 11.4kW
Max. apparent output power 10kW 11.4kW
Rated output voltage 240 V/120 V 240 V/120 V
Rated frequency 60 Hz 60 Hz
Rated output current 41.7A 47.5A
Max. output current 41.7A 47.5A
THDI <3% <3%
AC Input (Grid)
Input voltage range 211-264V 211-264V
Max. input current 62.6A 71.3A
Frequency range 59-61 Hz 59-61 Hz
AC Output (Backup and Off-grid)
Rated output power 10kW 11.4kW
Max. apparent output power 16 kVA, 10 sec 18.2 kVA, 10 sec
Back-up switch time < 10 ms < 10 ms
Phase Power 240V Split-Phase 240V Split-Phase
Rated output voltage(L1-L2)/(L1/L2-N) 240 V/120 V 240 V/120 V
AC output voltage range 211-264 V/105-132 V 211-264 V/105-132 V
Rated grid frequency 60 Hz 60 Hz
Frequency range 55-65Hz 55-65Hz
Rated AC output current 41.7A 47.5A
Max. output overcurrent protection, 10sec 66.7A 76.0A
Max. allowable phase imbalance 100% 100%
Backup support configurations Dedicated loads and whole-home (with a Solis Power Hub) Dedicated loads and whole-home (with a Solis Power Hub)
Power Factor >0.99 (0.8 leading - 0.8 lagging) >0.99 (0.8 leading - 0.8 lagging)
THDv(@linear load) <3% <3%
Efficiency
PV Max. efficiency 97.6% 97.6%
PV CEC efficiency 97.2% 97.2%
BAT charged by PV Max. efficiency 98.5% 98.5%
BAT charged/discharged to AC Max. efficiency 97.0% 97.0%
Protection
Ground fault detection Yes Yes
Residual (leakage) current detection Yes Yes
Integrated AFCI (DC arc-fault circuit protection) Yes Yes
DC reverse-polarity protection Yes (PV only) Yes (PV only)
Rapid Shutdown NEC 2017 Integrated SunSpec-certified Transmitter Integrated SunSpec-certified Transmitter
Compatible RSD Receivers See MLRSD compatibility sheet See MLRSD compatibility sheet
Protection class/Over voltage category I/II I/II
Technical Data S6-EH1P10K-H-US S6-EH1P11.4K-H-US
General data
Dimensions (H/W/D) 26.61*21.85*9.39 in (676*555*238.5 mm) 26.61*21.85*9.39 in (676*555*238.5 mm)
Weight 81.04 lbs (36.76 kg) 81.04 lbs (36.76 kg)
Topology Transformerless Transformerless
Operation temperature range -25 ~ +60 °C / -31 ~ +140 °F -25 ~ +60 °C / -31 ~ +140 °F
Ingress protection NEMA 4X(IP66) NEMA 4X(IP66)
Noise emission (Typical) <30 dB (A) <30 dB (A)
Cooling method Natural convection Natural convection
Max.operation altitude 13120 ft (4000 m) 13120 ft (4000 m)
Compliance UL1741SB, UL1741SA, IEEE1547-2018, UL1699B, UL1998, FCC Part15 ClassB, California Rule21, Heco Rule 14H, NEC 690.12-2020, CAN/CSA C22.2 No.107.1-1 UL1741SB, UL1741SA, IEEE1547-2018, UL1699B, UL1998, FCC Part15 ClassB, California Rule21, Heco Rule 14H, NEC 690.12-2020, CAN/CSA C22.2 No.107.1-1
Generator support Yes; up to 25 kW (with a Solis Power Hub) Yes; up to 25 kW (with a Solis Power Hub)
Features
DC connection 1 in. knockouts for conduit (x2) on the side and bottom; Spring clamp terminals 1 in. knockouts for conduit (x2) on the side and bottom; Spring clamp terminals
AC connection 2 in. knockouts for conduit (x3) on the side and bottom; Spring clamp terminals 2 in. knockouts for conduit (x3) on the side and bottom; Spring clamp terminals
Interface LED indicator lights, Bluetooth/Phone app LED indicator lights, Bluetooth/Phone app
Monitoring Platform Solis Cloud (modbus map and API sharing available upon request) Solis Cloud (modbus map and API sharing available upon request)
Communication RS485, Optional: Cellular, Wi-Fi, LAN RS485, Optional: Cellular, Wi-Fi, LAN
Warranty 10 years standard (Extend to 20 years) 10 years standard (Extend to 20 years)

8. Appendix

8.1 FCC Certification

This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.

FCC WARNING: Any Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.

NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body.

Models: S6EH1P-H1, 2AWE8-S6EH1P-H1, 2AWE8S6EH1PH1, Energy Storage Inverter App, Energy Storage App, Storage App, Inverter App

PDF preview unavailable. Download the PDF instead.

GetApplicationAttachment.html?id=6789446 Microsoft: Print To PDF

Related Documents

Preview Solis S6 Hybrid Series User Manual: Residential Energy Storage Inverter
Comprehensive user manual for the Solis S6 Hybrid series of single-phase residential energy storage inverters. Covers installation, operation, safety, and troubleshooting for models S6-EH1P3.8K-H-US through S6-EH1P11.4K-H-US, designed for efficient solar energy management and backup power.
Preview Solis S6 Series Hybrid Inverter User Manual
User manual for the Solis S6 Series Hybrid Inverter, covering installation, operation, safety, and specifications for models like S6-EH3P5K2-H, S6-EH3P6K2-H, and others.
Preview Solis S6 Series Hybrid Inverter User Manual
User manual for the Solis S6 Series Hybrid Inverter, covering product description, safety warnings, installation, commissioning, maintenance, troubleshooting, and specifications for residential hybrid systems.
Preview Solis S6 Series Hybrid Inverter User Manual
Comprehensive user manual for the Solis S6 Series Hybrid Inverter, covering installation, operation, safety, and troubleshooting for commercial hybrid systems. Includes details on applicable models and system configurations.
Preview Solis S6 Series Hybrid Inverter User Manual
Comprehensive user manual for the Solis S6 Series Hybrid Inverter, covering installation, safety, operation, and troubleshooting for models S6-EH3P3K-H-EU through S6-EH3P10K-H-EU.
Preview Solis S6系列混合型逆变器用户手册
本用户手册提供了Solis S6系列混合型逆变器的全面指南,涵盖安装、操作、安全规程、维护和故障排除。该系列逆变器专为工商业混合光伏系统设计,旨在最大化效率并提供可靠的备用电源。
Preview Solis S6-EH1P(3-8)K-L-PLUS: Single Phase Low Voltage Energy Storage Inverter Datasheet
Detailed technical specifications for the Solis S6-EH1P(3-8)K-L-PLUS series of single-phase low voltage energy storage inverters, including features, models, and performance data.
Preview Solis S6 Series Hybrid Inverter User Manual
Comprehensive user manual for the Solis S6 Series Hybrid Inverter, covering installation, operation, maintenance, and troubleshooting for residential hybrid systems.