5. Commissioning & Shutdown
5.1 Preparation of Commissioning
- Ensure all devices are accessible for operation, maintenance, and service.
- Check and confirm that the inverter is firmly installed.
- Space for ventilation is sufficient for one inverter or multiple inverters.
- Nothing is left on the top of the inverter or battery module.
- Inverter and accessories are correctly connected.
- Cables are routed in a safe place or protected against mechanical damage.
- Warning signs and labels are suitably affixed and durable.
- Bluetooth Antenna has been connected to the Antenna port of the inverter.
- An Android or iOS mobile phone with Bluetooth function is available.
- Soliscloud APP is installed on the mobile phone.
There are three ways to download and install the latest APP:
- Visit www.soliscloud.com to download the latest version APP.
- Search "Soliscloud" in Google Play or App Store.
- Scan the QR code to download "Soliscloud".
5.2 Commissioning Procedure
Step 1: Measure DC voltage of PV strings and battery and ensure the polarity is correct.
Step 2: Measure AC voltage and frequency and ensure they are within local standard.
Step 3: Switch on the external AC breaker to power on the inverter control board. (Bluetooth signal available)
Step 4: Turn on Bluetooth switch on your mobile phone and then open the Soliscloud APP. Click "More Tools" -> "Local Operation" -> "Connect with Bluetooth".
Step 5: Select the Bluetooth signal from the inverter. (Bluetooth Name: Solis-Inverter SN)
Step 6: If you are the installer, please select the account type as Installer. If you are the plant owner, please select the account type as Owner. Then set your own initial password for control verification. (The first log-in must be finished by installer in order to do the initial set up)
Step 7: After the log in for the first time, initial settings are required.
- Step 7.1: Set the inverter Date and Time. You can set to follow the time on your mobile phone.
- Step 7.2: Set the battery model. It must be based on the battery model that is actually connected to the inverter. If there is no battery connected for the moment, please select "No Battery" to avoid alarms. The default setting for battery over discharge SOC is 20%, force charge SOC is 10%.
- Step 7.3: Set the meter setting. It must be based on the meter type that is actually connected to the inverter. If there is no meter connected for the moment, please select "No Meter" to avoid alarms. It is suggested to install the meter at the system grid connection point and select "Meter in Grid".
- Step 7.4: Set the grid code setting. Please select the grid code based on the local grid network requirements.
- Step 7.5: Set the work mode setting. Recommended setting is Self-Use Mode. This mode can maximize the use of PV power generation for household electricity, or store it in batteries and use it for household electricity. If manual control of the battery charging and discharging with respect to time is needed, please use the Time of Use switch and the following set points. The “Allow Grid Charging" is recommended to be turned on (If turned off, the inverter will not force charge the battery and battery could potentially go to sleep).
Step 8: Now the initial settings on the inverter have been set and you can switch on the inverter DC switch and switch on the battery breaker to start up the system. You can also explore in the APP to check the operating data, alarm message, or other advanced settings.
Step 9: If the Owner forgot the password, please contact the installer. Installer logs in and goes to "Setting" -> "More" -> "Change Password" to reset the password for the owner's account. If the Installer forgot the password, please contact the Solis service team.
5.3 Shutdown Procedure
- Turn off the AC breaker at the grid connection point.
- Turn off the DC switch of the inverter.
- Turn off the battery breaker.
- Wait for the device to be powered off and the system shutdown is completed.
6. Troubleshooting
Solis S6 Series inverter does not require any regular maintenance. However, cleaning the heatsink will help the inverter dissipate heat and increase the lifetime of inverter. The dirt on the inverter can be cleaned with a soft brush.
CAUTION: Do not touch the surface when the inverter is operating. Some parts may be hot and could cause burns. Turn OFF the inverter (refer to Section 6.2) and let it cool down before you do any maintenance or cleaning of the inverter.
The screen and the LED status indicator lights can be cleaned with a cloth if they are too dirty to be read.
Note: Never use any solvents, abrasives, or corrosive materials to clean the inverter.
The inverter has been designed in accordance with international grid-tied standards for safety and electromagnetic compatibility requirements. Before being delivered to the customer, the inverter is subjected to several tests to ensure reliability of operation and reliability.
In case of a failure, the app will display an alarm message. In this case, the inverter may stop feeding energy into the grid. The alarm descriptions and their corresponding alarm messages are listed in Table 6.1:
Alarm Message | Failure description | Solution |
---|---|---|
ARC-FAULT | ARC detected in DC circuit | 1. Check if there is an arc in the PV connection and restart inverter. |
AFC Check FAULT | AFC module self check fault | 1. Restart inverter or contact installer. |
DCinj-FAULT | High DC injection current | 1. Restart inverter or contact installer. |
DSP-B-FAULT | Comm. failure between main and slave DSP | 1. Restart inverter or contact installer. |
DC-INTF | DC input overcurrent | 1. Restart inverter. 2. Identify and remove the string related to the faulty MPPT. 3. Change power board. |
G-IMP | High grid impedance | 1. User design function allows the protection limit to be adjusted if it is allowed by electrical company. |
GRID-INTF01/02 | Grid interference | 1. Restart inverter. 2. Change power board. |
IGBT-OV-I | Over IGBT current | 1. Restart inverter or contact installer. |
IGFOL-F | Grid current tracking fail | 1. Restart inverter or contact installer. |
IG-AD | Grid current sampling fail | 1. Check AC and DC connection. 2. Check inverter inside cable connection. |
ILeak-PRO 01/02/03/04 | leakage current protection | 1. Restart inverter or contact installer. |
INI-FAULT | Initialization system fault | 1. Ensure the battery is connected properly. 2. Verify the output battery voltage is correct. |
NO-Battery | Unconnected battery | 1. Check connections and grid switch. 2. Verify the grid voltage is correct on the AC terminals inside the inverter wiring box. |
NO-GRID | No grid voltage | 1. Check inverter inductor connection. 2. Check driver connection. |
OV-BUS | Over DC bus voltage | 1. Check inverter inductor connection. 2. Check driver connection. |
OV-DC01/02/03/04 | Over DC voltage | 1. Reduce the module number in series. |
OV-DCA-I | DC input overcurrent | 1. Restart inverter. 2. Identify and remove the string of the faulty MPPT. 3. Change power board. |
OV-G-V01/02/03/04/05 | Over grid voltage | 1. Resistance of AC Cable is too high. Increase the gauge of grid cables. 2. Adjust the protection limit if it is permitted by electrical company. |
OV-G-I | Over grid current | 1. Restart inverter. 2. Change power board. |
OV-G-F01/02 | Over grid frequency | 1. User design function allows the protection limit to be adjusted if it is permitted by electrical company. |
OV-IgTr | AC side transient overcurrent | |
OV-ILLC | LLC hardware overcurrent | 1. Restart inverter. 2. Return-factory repair. |
OV-VBackup | Backup overvoltage fault | |
OV-TEM | Over Temperature | 1. Check inverter surrounding ventilation. 2. Determine if there is direct sunlight on the inverter during hot weather. |
OV-Vbatt1 | The detection of battery overvoltage | 1. Verify the protection point for over voltage is set correctly. 2. Restart inverter. |
OV-Vbatt-H | Battery overvoltage hardware fault | 1. Check if any part of the battery input circuit is tripped, ie. battery fuses, battery circuit breaker. 2. Restart inverter. |
Over-Load | Backup overload fault | 1. Check the load of Backup port is over rating output power or not. 2. Reduce the load of Backup port, then restart inverter. |
PV ISO-PRO01/02 | PV isolation protection | 1. Remove all DC input, reconnect and restart inverter one by one. 2. Identify which string causes the fault and check the isolation of the string. |
RelayChk-FAIL | Relay check fail | 1. Restart inverter or contact installer. |
UN-BUS01/02 | Under DC bus voltage | 1. Check inverter inductor connection. 2. Check driver connection. |
UN-G-F01/02 | Under grid frequency | 1. Use user define function to adjust the protection limit if it's allowed by electrical company. |
UN-G-V01/02 | Under grid voltage | 1. Use user define function to adjust the protection limit if it's allowed by electrical company. |
12Power-FAULT | 12V power supply fault | 1. Restart inverter or contact installer. |
NOTE: If the inverter displays any alarm message listed in Table 6.1, please turn off the inverter and wait for 5 minutes before restarting it. If the failure persists, please contact your local distributor or the service center.
If you have any technical problems with the hybrid system, please contact the Solis after-sale service. We recommend gathering the following information before making contact in order to get timely support.
Item | Details | Supplemental Info |
---|---|---|
Inverter SN | SN from nameplate | |
Inverter Firmware Version | 6 digits of number or letter (Check the inverter user manual for the path) | |
DC connections | Solar modules, numbers, configuration | |
Detailed description of the problem | Battery SN, Firmware version | Check battery user manual for the path |
Is it connected to Solis Monitoring Portal? | Yes/No | |
Take pictures showing all the cable connections in the system (Videos preferred) | If available |
7. Specifications
Technical Data | S6-EH1P3.8K-H-US | S6-EH1P5K-H-US |
---|---|---|
Input DC (PV side) | ||
Recommended max. PV power | 6080W | 8000W |
Max. input voltage | 600V | 600V |
Rated voltage | 380V | 380V |
Start-up voltage | 80V | 80V |
MPPT voltage range | 80-550V | 80-550V |
Full load MPPT voltage range | 140-450V | 140-450V |
Max. input current per string | 16A | 16A |
Max. short circuit current per string | 25.6A | 25.6A |
Number of MPPTs/Number of strings per MPPT | 2/1 | 3/1 |
Energy Storage | ||
Battery type | Lithium-ion | Lithium-ion |
Battery voltage range | 120-500V | 120-500V |
Maximum charge/discharge current | 25A | 25A |
Battery Communication | CAN/RS485 | CAN/RS485 |
Number of batteries per inverter | See Battery Compatibility Sheet | See Battery Compatibility Sheet |
AC Output (Grid) | ||
Rated output power | 3.8kW | 5kW |
Max. apparent output power | 3.8kW | 5kW |
Rated output voltage | 240 V/120 V | 240 V/120 V |
Rated frequency | 60 Hz | 60 Hz |
Rated output current | 15.8A | 20.8A |
Max. output current | 15.8A | 20.8A |
THDI | <3% | <3% |
AC Input (Grid) | ||
Input voltage range | 211-264V | 211-264V |
Max. input current | 23.8A | 31.2A |
Frequency range | 59-61 Hz | 59-61 Hz |
AC Output (Backup and Off-grid) | ||
Rated output power | 3.8kW | 5kW |
Max. apparent output power | 6.1 kVA, 10 sec | 8 kVA, 10 sec |
Back-up switch time | < 10 ms | < 10 ms |
Phase Power | 240V Split-Phase | 240V Split-Phase |
Rated output voltage(L1-L2)/(L1/L2-N) | 240 V/120 V | 240 V/120 V |
AC output voltage range | 211-264 V/105-132 V | 211-264 V/105-132 V |
Rated grid frequency | 60 Hz | 60 Hz |
Frequency range | 55-65Hz | 55-65Hz |
Rated AC output current | 15.8A | 20.8A |
Max. output overcurrent protection, 10sec | 25.4A | 33.3A |
Max. allowable phase imbalance | 100% | 100% |
Backup support configurations | Dedicated loads and whole-home (with a Solis Power Hub) | Dedicated loads and whole-home (with a Solis Power Hub) |
Power Factor | >0.99 (0.8 leading - 0.8 lagging) | >0.99 (0.8 leading - 0.8 lagging) |
THDv(@linear load) | <3% | <3% |
Efficiency | ||
PV Max. efficiency | 97.6% | 97.6% |
PV CEC efficiency | 97.2% | 97.2% |
BAT charged by PV Max. efficiency | 98.5% | 98.5% |
BAT charged/discharged to AC Max. efficiency | 97.0% | 97.0% |
Protection | ||
Ground fault detection | Yes | Yes |
Residual (leakage) current detection | Yes | Yes |
Integrated AFCI (DC arc-fault circuit protection) | Yes | Yes |
DC reverse-polarity protection | Yes (PV only) | Yes (PV only) |
Rapid Shutdown NEC 2017 | Integrated SunSpec-certified Transmitter | Integrated SunSpec-certified Transmitter |
Compatible RSD Receivers | See MLRSD compatibility sheet | See MLRSD compatibility sheet |
Protection class/Over voltage category | I/II | I/II |
Technical Data | S6-EH1P6K-H-US | S6-EH1P7.6K-H-S-US |
---|---|---|
Input DC (PV side) | ||
Recommended max. PV power | 9600W | 12160W |
Max. input voltage | 600V | 600V |
Rated voltage | 380V | 380V |
Start-up voltage | 80V | 80V |
MPPT voltage range | 80-550V | 80-550V |
Full load MPPT voltage range | 155-450V | 175-450V |
Max. input current per string | 16A | 16A |
Max. short circuit current per string | 25.6A | 25.6A |
Number of MPPTs/Number of strings per MPPT | 3/1 | 3/1 |
Energy Storage | ||
Battery type | Lithium-ion | Lithium-ion |
Battery voltage range | 120-500V | 120-500V |
Maximum charge/discharge current | 25A | 25A |
Battery Communication | CAN/RS485 | CAN/RS485 |
Number of batteries per inverter | See Battery Compatibility Sheet | See Battery Compatibility Sheet |
AC Output (Grid) | ||
Rated output power | 6kW | 7.6kW |
Max. apparent output power | 6kW | 7.6kW |
Rated output voltage | 240 V/120 V | 240 V/120 V |
Rated frequency | 60 Hz | 60 Hz |
Rated output current | 25.0A | 31.7A |
Max. output current | 25.0A | 31.7A |
THDI | <3% | <3% |
AC Input (Grid) | ||
Input voltage range | 211-264V | 211-264V |
Max. input current | 37.5A | 47.6A |
Frequency range | 59-61 Hz | 59-61 Hz |
AC Output (Backup and Off-grid) | ||
Rated output power | 6kW | 7.6kW |
Max. apparent output power | 9.6 kVA, 10 sec | 12.2 kVA, 10 sec |
Back-up switch time | < 10 ms | < 10 ms |
Phase Power | 240V Split-Phase | 240V Split-Phase |
Rated output voltage(L1-L2)/(L1/L2-N) | 240 V/120 V | 240 V/120 V |
AC output voltage range | 211-264 V/105-132 V | 211-264 V/105-132 V |
Rated grid frequency | 60 Hz | 60 Hz |
Frequency range | 55-65Hz | 55-65Hz |
Rated AC output current | 25.0A | 31.7A |
Max. output overcurrent protection, 10sec | 40.0A | 50.7A |
Max. allowable phase imbalance | 100% | 100% |
Backup support configurations | Dedicated loads and whole-home (with a Solis Power Hub) | Dedicated loads and whole-home (with a Solis Power Hub) |
Power Factor | >0.99 (0.8 leading - 0.8 lagging) | >0.99 (0.8 leading - 0.8 lagging) |
THDv(@linear load) | <3% | <3% |
Efficiency | ||
PV Max. efficiency | 97.6% | 97.6% |
PV CEC efficiency | 97.2% | 97.2% |
BAT charged by PV Max. efficiency | 98.5% | 98.5% |
BAT charged/discharged to AC Max. efficiency | 97.0% | 97.0% |
Protection | ||
Ground fault detection | Yes | Yes |
Residual (leakage) current detection | Yes | Yes |
Integrated AFCI (DC arc-fault circuit protection) | Yes | Yes |
DC reverse-polarity protection | Yes (PV only) | Yes (PV only) |
Rapid Shutdown NEC 2017 | Integrated SunSpec-certified Transmitter | Integrated SunSpec-certified Transmitter |
Compatible RSD Receivers | See MLRSD compatibility sheet | See MLRSD compatibility sheet |
Protection class/Over voltage category | I/II | I/II |
Technical Data | S6-EH1P7.6K-H-L-US | S6-EH1P8K-H-US |
---|---|---|
Input DC (PV side) | ||
Recommended max. PV power | 12160W | 12800W |
Max. input voltage | 600V | 600V |
Rated voltage | 380V | 380V |
Start-up voltage | 80V | 80V |
MPPT voltage range | 80-550V | 80-550V |
Full load MPPT voltage range | 175-450V | 185-450V |
Max. input current per string | 16A | 16A |
Max. short circuit current per string | 25.6A | 25.6A |
Number of MPPTs/Number of strings per MPPT | 4/1 | 4/1 |
Energy Storage | ||
Battery type | Lithium-ion | Lithium-ion |
Battery voltage range | 120-500V | 120-500V |
Maximum charge/discharge current | 50A | 50A |
Battery Communication | CAN/RS485 | CAN/RS485 |
Number of batteries per inverter | See Battery Compatibility Sheet | See Battery Compatibility Sheet |
AC Output (Grid) | ||
Rated output power | 7.6kW | 8kW |
Max. apparent output power | 7.6kW | 8kW |
Rated output voltage | 240 V/120 V | 240 V/120 V |
Rated frequency | 60 Hz | 60 Hz |
Rated output current | 31.7A | 33.3A |
Max. output current | 31.7A | 33.3A |
THDI | <3% | <3% |
AC Input (Grid) | ||
Input voltage range | 211-264V | 211-264V |
Max. input current | 47.6A | 49.9A |
Frequency range | 59-61 Hz | 59-61 Hz |
AC Output (Backup and Off-grid) | ||
Rated output power | 7.6kW | 8kW |
Max. apparent output power | 12.2 kVA, 10 sec | 12.8 kVA, 10 sec |
Back-up switch time | < 10 ms | < 10 ms |
Phase Power | 240V Split-Phase | 240V Split-Phase |
Rated output voltage(L1-L2)/(L1/L2-N) | 240 V/120 V | 240 V/120 V |
AC output voltage range | 211-264 V/105-132 V | 211-264 V/105-132 V |
Rated grid frequency | 60 Hz | 60 Hz |
Frequency range | 55-65Hz | 55-65Hz |
Rated AC output current | 31.7A | 33.3A |
Max. output overcurrent protection, 10sec | 50.7A | 53.3A |
Max. allowable phase imbalance | 100% | 100% |
Backup support configurations | Dedicated loads and whole-home (with a Solis Power Hub) | Dedicated loads and whole-home (with a Solis Power Hub) |
Power Factor | >0.99 (0.8 leading - 0.8 lagging) | >0.99 (0.8 leading - 0.8 lagging) |
THDv(@linear load) | <3% | <3% |
Efficiency | ||
PV Max. efficiency | 97.6% | 97.6% |
PV CEC efficiency | 97.2% | 97.2% |
BAT charged by PV Max. efficiency | 98.5% | 98.5% |
BAT charged/discharged to AC Max. efficiency | 97.0% | 97.0% |
Protection | ||
Ground fault detection | Yes | Yes |
Residual (leakage) current detection | Yes | Yes |
Integrated AFCI (DC arc-fault circuit protection) | Yes | Yes |
DC reverse-polarity protection | Yes (PV only) | Yes (PV only) |
Rapid Shutdown NEC 2017 | Integrated SunSpec-certified Transmitter | Integrated SunSpec-certified Transmitter |
Compatible RSD Receivers | See MLRSD compatibility sheet | See MLRSD compatibility sheet |
Protection class/Over voltage category | I/II | I/II |
Technical Data | S6-EH1P10K-H-US | S6-EH1P11.4K-H-US |
---|---|---|
Input DC (PV side) | ||
Recommended max. PV power | 16000W | 18240W |
Max. input voltage | 600V | 600V |
Rated voltage | 380V | 380V |
Start-up voltage | 80V | 80V |
MPPT voltage range | 80-550V | 80-550V |
Full load MPPT voltage range | 230-450V | 245-450V |
Max. input current per string | 16A | 16A |
Max. short circuit current per string | 25.6A | 25.6A |
Number of MPPTs/Number of strings per MPPT | 4/1 | 4/1 |
Energy Storage | ||
Battery type | Lithium-ion | Lithium-ion |
Battery voltage range | 120-500V | 120-500V |
Maximum charge/discharge current | 50A | 50A |
Battery Communication | CAN/RS485 | CAN/RS485 |
Number of batteries per inverter | See Battery Compatibility Sheet | See Battery Compatibility Sheet |
AC Output (Grid) | ||
Rated output power | 10kW | 11.4kW |
Max. apparent output power | 10kW | 11.4kW |
Rated output voltage | 240 V/120 V | 240 V/120 V |
Rated frequency | 60 Hz | 60 Hz |
Rated output current | 41.7A | 47.5A |
Max. output current | 41.7A | 47.5A |
THDI | <3% | <3% |
AC Input (Grid) | ||
Input voltage range | 211-264V | 211-264V |
Max. input current | 62.6A | 71.3A |
Frequency range | 59-61 Hz | 59-61 Hz |
AC Output (Backup and Off-grid) | ||
Rated output power | 10kW | 11.4kW |
Max. apparent output power | 16 kVA, 10 sec | 18.2 kVA, 10 sec |
Back-up switch time | < 10 ms | < 10 ms |
Phase Power | 240V Split-Phase | 240V Split-Phase |
Rated output voltage(L1-L2)/(L1/L2-N) | 240 V/120 V | 240 V/120 V |
AC output voltage range | 211-264 V/105-132 V | 211-264 V/105-132 V |
Rated grid frequency | 60 Hz | 60 Hz |
Frequency range | 55-65Hz | 55-65Hz |
Rated AC output current | 41.7A | 47.5A |
Max. output overcurrent protection, 10sec | 66.7A | 76.0A |
Max. allowable phase imbalance | 100% | 100% |
Backup support configurations | Dedicated loads and whole-home (with a Solis Power Hub) | Dedicated loads and whole-home (with a Solis Power Hub) |
Power Factor | >0.99 (0.8 leading - 0.8 lagging) | >0.99 (0.8 leading - 0.8 lagging) |
THDv(@linear load) | <3% | <3% |
Efficiency | ||
PV Max. efficiency | 97.6% | 97.6% |
PV CEC efficiency | 97.2% | 97.2% |
BAT charged by PV Max. efficiency | 98.5% | 98.5% |
BAT charged/discharged to AC Max. efficiency | 97.0% | 97.0% |
Protection | ||
Ground fault detection | Yes | Yes |
Residual (leakage) current detection | Yes | Yes |
Integrated AFCI (DC arc-fault circuit protection) | Yes | Yes |
DC reverse-polarity protection | Yes (PV only) | Yes (PV only) |
Rapid Shutdown NEC 2017 | Integrated SunSpec-certified Transmitter | Integrated SunSpec-certified Transmitter |
Compatible RSD Receivers | See MLRSD compatibility sheet | See MLRSD compatibility sheet |
Protection class/Over voltage category | I/II | I/II |
Technical Data | S6-EH1P7.6K-H-L-US | S6-EH1P8K-H-US |
---|---|---|
General data | ||
Dimensions (H/W/D) | 26.61*21.85*9.39 in (676*555*238.5 mm) | 26.61*21.85*9.39 in (676*555*238.5 mm) |
Weight | 81.04 lbs (36.76 kg) | 81.04 lbs (36.76 kg) |
Topology | Transformerless | Transformerless |
Operation temperature range | -25 ~ +60 °C / -31 ~ +140 °F | -25 ~ +60 °C / -31 ~ +140 °F |
Ingress protection | NEMA 4X(IP66) | NEMA 4X(IP66) |
Noise emission (Typical) | <30 dB (A) | <30 dB (A) |
Cooling method | Natural convection | Natural convection |
Max.operation altitude | 13120 ft (4000 m) | 13120 ft (4000 m) |
Compliance | UL1741SB, UL1741SA, IEEE1547-2018, UL1699B, UL1998, FCC Part15 ClassB, California Rule21, Heco Rule 14H, NEC 690.12-2020, CAN/CSA C22.2 No.107.1-1 | UL1741SB, UL1741SA, IEEE1547-2018, UL1699B, UL1998, FCC Part15 ClassB, California Rule21, Heco Rule 14H, NEC 690.12-2020, CAN/CSA C22.2 No.107.1-1 |
Generator support | Yes; up to 25 kW (with a Solis Power Hub) | Yes; up to 25 kW (with a Solis Power Hub) |
Features | ||
DC connection | 1 in. knockouts for conduit (x2) on the side and bottom; Spring clamp terminals | 1 in. knockouts for conduit (x2) on the side and bottom; Spring clamp terminals |
AC connection | 2 in. knockouts for conduit (x3) on the side and bottom; Spring clamp terminals | 2 in. knockouts for conduit (x3) on the side and bottom; Spring clamp terminals |
Interface | LED indicator lights, Bluetooth/Phone app | LED indicator lights, Bluetooth/Phone app |
Monitoring Platform | Solis Cloud (modbus map and API sharing available upon request) | Solis Cloud (modbus map and API sharing available upon request) |
Communication | RS485, Optional: Cellular, Wi-Fi, LAN | RS485, Optional: Cellular, Wi-Fi, LAN |
Warranty | 10 years standard (Extend to 20 years) | 10 years standard (Extend to 20 years) |
Technical Data | S6-EH1P10K-H-US | S6-EH1P11.4K-H-US |
---|---|---|
Input DC (PV side) | ||
Recommended max. PV power | 16000W | 18240W |
Max. input voltage | 600V | 600V |
Rated voltage | 380V | 380V |
Start-up voltage | 80V | 80V |
MPPT voltage range | 80-550V | 80-550V |
Full load MPPT voltage range | 230-450V | 245-450V |
Max. input current per string | 16A | 16A |
Max. short circuit current per string | 25.6A | 25.6A |
Number of MPPTs/Number of strings per MPPT | 4/1 | 4/1 |
Energy Storage | ||
Battery type | Lithium-ion | Lithium-ion |
Battery voltage range | 120-500V | 120-500V |
Maximum charge/discharge current | 50A | 50A |
Battery Communication | CAN/RS485 | CAN/RS485 |
Number of batteries per inverter | See Battery Compatibility Sheet | See Battery Compatibility Sheet |
AC Output (Grid) | ||
Rated output power | 10kW | 11.4kW |
Max. apparent output power | 10kW | 11.4kW |
Rated output voltage | 240 V/120 V | 240 V/120 V |
Rated frequency | 60 Hz | 60 Hz |
Rated output current | 41.7A | 47.5A |
Max. output current | 41.7A | 47.5A |
THDI | <3% | <3% |
AC Input (Grid) | ||
Input voltage range | 211-264V | 211-264V |
Max. input current | 62.6A | 71.3A |
Frequency range | 59-61 Hz | 59-61 Hz |
AC Output (Backup and Off-grid) | ||
Rated output power | 10kW | 11.4kW |
Max. apparent output power | 16 kVA, 10 sec | 18.2 kVA, 10 sec |
Back-up switch time | < 10 ms | < 10 ms |
Phase Power | 240V Split-Phase | 240V Split-Phase |
Rated output voltage(L1-L2)/(L1/L2-N) | 240 V/120 V | 240 V/120 V |
AC output voltage range | 211-264 V/105-132 V | 211-264 V/105-132 V |
Rated grid frequency | 60 Hz | 60 Hz |
Frequency range | 55-65Hz | 55-65Hz |
Rated AC output current | 41.7A | 47.5A |
Max. output overcurrent protection, 10sec | 66.7A | 76.0A |
Max. allowable phase imbalance | 100% | 100% |
Backup support configurations | Dedicated loads and whole-home (with a Solis Power Hub) | Dedicated loads and whole-home (with a Solis Power Hub) |
Power Factor | >0.99 (0.8 leading - 0.8 lagging) | >0.99 (0.8 leading - 0.8 lagging) |
THDv(@linear load) | <3% | <3% |
Efficiency | ||
PV Max. efficiency | 97.6% | 97.6% |
PV CEC efficiency | 97.2% | 97.2% |
BAT charged by PV Max. efficiency | 98.5% | 98.5% |
BAT charged/discharged to AC Max. efficiency | 97.0% | 97.0% |
Protection | ||
Ground fault detection | Yes | Yes |
Residual (leakage) current detection | Yes | Yes |
Integrated AFCI (DC arc-fault circuit protection) | Yes | Yes |
DC reverse-polarity protection | Yes (PV only) | Yes (PV only) |
Rapid Shutdown NEC 2017 | Integrated SunSpec-certified Transmitter | Integrated SunSpec-certified Transmitter |
Compatible RSD Receivers | See MLRSD compatibility sheet | See MLRSD compatibility sheet |
Protection class/Over voltage category | I/II | I/II |
Technical Data | S6-EH1P10K-H-US | S6-EH1P11.4K-H-US |
---|---|---|
General data | ||
Dimensions (H/W/D) | 26.61*21.85*9.39 in (676*555*238.5 mm) | 26.61*21.85*9.39 in (676*555*238.5 mm) |
Weight | 81.04 lbs (36.76 kg) | 81.04 lbs (36.76 kg) |
Topology | Transformerless | Transformerless |
Operation temperature range | -25 ~ +60 °C / -31 ~ +140 °F | -25 ~ +60 °C / -31 ~ +140 °F |
Ingress protection | NEMA 4X(IP66) | NEMA 4X(IP66) |
Noise emission (Typical) | <30 dB (A) | <30 dB (A) |
Cooling method | Natural convection | Natural convection |
Max.operation altitude | 13120 ft (4000 m) | 13120 ft (4000 m) |
Compliance | UL1741SB, UL1741SA, IEEE1547-2018, UL1699B, UL1998, FCC Part15 ClassB, California Rule21, Heco Rule 14H, NEC 690.12-2020, CAN/CSA C22.2 No.107.1-1 | UL1741SB, UL1741SA, IEEE1547-2018, UL1699B, UL1998, FCC Part15 ClassB, California Rule21, Heco Rule 14H, NEC 690.12-2020, CAN/CSA C22.2 No.107.1-1 |
Generator support | Yes; up to 25 kW (with a Solis Power Hub) | Yes; up to 25 kW (with a Solis Power Hub) |
Features | ||
DC connection | 1 in. knockouts for conduit (x2) on the side and bottom; Spring clamp terminals | 1 in. knockouts for conduit (x2) on the side and bottom; Spring clamp terminals |
AC connection | 2 in. knockouts for conduit (x3) on the side and bottom; Spring clamp terminals | 2 in. knockouts for conduit (x3) on the side and bottom; Spring clamp terminals |
Interface | LED indicator lights, Bluetooth/Phone app | LED indicator lights, Bluetooth/Phone app |
Monitoring Platform | Solis Cloud (modbus map and API sharing available upon request) | Solis Cloud (modbus map and API sharing available upon request) |
Communication | RS485, Optional: Cellular, Wi-Fi, LAN | RS485, Optional: Cellular, Wi-Fi, LAN |
Warranty | 10 years standard (Extend to 20 years) | 10 years standard (Extend to 20 years) |
8. Appendix
8.1 FCC Certification
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
FCC WARNING: Any Changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate the equipment.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator & your body.