About This Guide
This document provides instructions to install the TC Series thermostat configuration wizard. To fully utilize the information within this guide, users should possess training or experience with the Niagara N4 software.
Prerequisites
Before proceeding with the installation, ensure the following prerequisites are met:
- Niagara workbench (refer to the latest software release notes for compatibility information).
- Google Chrome web browser.
- Required modules:
- honeywellTCThermostatWizard-rt
- honeywellTCThermostatWizard-ux
- honeywellTCThermostatWizard-wb
- honeywellBacnetDeviceManager-rt
- honeywellBacnetDeviceManager-wb
- honeywellDeviceManager-rt.jar
- honeywellDeviceManager-wb.jar
The TC Series wizard does not require additional licensing beyond the controllers or supervisor license.
Installing TC Thermostat Configuration Wizard Modules on the Controller
The installation procedure for the TC500A and TC300 thermostats is identical. This document uses the TC500A for configuration examples.
- Connect to the Platform and open the Software Manager.
- Select and install the 'honeywellTCThermostatWizard' module. The status should update from "Not Installed" to "Up to Date."
- Launch the station.
Adding the TC Series Device to the Station
Install the modules on the controller as previously described and connect to the station. The TC Series Thermostat Configuration Wizard functions as a BACnet device; therefore, a BACnet network must be added and configured before integrating the device into the station.
- Navigate to Window > Side Bars > Palette to open the palette pane, typically located in the lower-left corner.
- Click the (Open Palette) option within the palette window.
- In the filter field, type 'honeywellTCThermostatWizard', select the module, and click OK.
- Using the palette, navigate to the 'honeywellTCThermostatWizard' module in the workbench.
- Drag and drop the TC500 or TC300 device under the Station > Config > Drivers > BacnetNetwork path in the Nav tree.
- Double-click the TC500 or TC300 device to access the configuration wizard.
To resolve potential [web.reporting.csp] errors in the application director output, navigate to Services > WebService > HttpHeaderProviders > Content-Security Policy. Configure the font-src property with 'self' workbench data.
Applicable Technical Literature
Refer to the following documents for additional information:
Document Name | Document Number |
---|---|
TC Thermostat Configuration Wizard User Guide | 31-00490 |
TC500 Thermostat BACnet Integration Guide | 31-00478 |