Lumination® Montage
Rough-In Kit

Installation Guide IND377

BEFORE YOU BEGIN
Read these instructions completely and carefully.

WARNING/AVERTISSEMENT

RISK OF ELECTRIC SHOCK · Turn power off before inspection, installation or removal. · Properly ground electrical enclosure.
RISK OF FIRE · Follow all NEC and local codes. · Use only UL approved wire for input/output connections.
Minimum size 18 AWG or 14 AWG for continuous runs.

RISQUES DE DÉCHARGES ÉLECTRIQUES · Coupez l'alimentation avant d'inspecter, installer ou déplacer le luminaire. · Assurez-vous de correctement mettre à la terre le boîtier d'alimentation
électrique.
RISK OF FIRE · Respectez tous les codes NEC et codes locaux. · N'utilisez que des fils approuvés par UL pour les entrées/sorties de
connexion. Taille minimum 18 AWG ou 14 AWG pour les rangées continues.

Save These Instructions
Use only in the manner intended by the manufacturer. If you have any questions, contact the manufacturer.
Prepare Electrical Wiring
Electrical Requirements · The LED driver must be supplied with 120 or 277V, 50/60 Hz and connected to
an individual properly grounded branch circuit, protected by a 20 ampere circuit breaker. Use min. 75°C supply conductor.
Grounding Instructions · The grounding and bonding of the overall system shall be done in accordance with
National Electric Code (NEC) Article 600 and local codes.

Lumination® Montage

Installation Guide

Unit Installation
Tile Ceiling (above ceiling access after installation)

1 Cut the appropriately sized hole (see table at the right) in the desired ceiling tile. Place the ceiling tile in the ceiling grid.

Fixture MM1 MM2 MM3 MM4 MM2X2

Hole Size 5.56 in. x 5.56 in. (141.29 mm x 141.29 mm) 10.31 in. x 5.56 in. (261.94 mm x 141.29 mm) 14.81 in. x 5.56 in. (376.24 mm x 141.29 mm) 19.31 in. x 5.56 in. (490.54 mm x 141.29 mm) 11.25 in x 11.25 in. (285.75 mm x 285.75 mm)

Tile Ceiling (above ceiling access after installation)

2 Slide hanger bars through the adjustable mounting brackets on the rough in kit.
2

Lumination® Montage

Installation Guide

3 Mount Rough-in-Kit by attaching the hanger bars to the T-Grid ceiling.

4 If necessary, the height of the adjustable mounting brackets can be adjusted by loosening the nut so that the bottom of the rough in kit is flush with the top of the ceiling tile.

Spacing Requirements
Minimum Spacing Requirements for Fixtures Center to center of adjacent luminaire Top of Luminaire to overhead building member Luminaire center to side building member

MM 1 and 2 24" 0.5" 12"

MM 3, 4, and 2x2 36" 0.5" 18"

3

Lumination® Montage

Wiring Instructions

TPC BLACK LEAD
BLACK AC INPUT LEAD PROVIDED BY INSTALLER

TPC
TPC WHITE LEAD

Installation Guide

WHITE AC INPUT LEAD PROVIDED BY INSTALLER

GREEN GROUND LEAD CONNECTED TO JUNCTION BOX

GREEN GROUND LEAD TO FIXTURE

TPC - BLUE LEAD (1-20V) TPC - RED LEAD (277V)
BLACK (+) AC LEAD TO DRIVER

WHITE (-) AC LEAD TO DRIVER

CONDUIT WHIP

1 Bring supply leads and ground to the junction box supplied on the Rough in Kit. Be sure to connect leads to existing wire connectors to ensure proper function of thermal protector and fixture.

Must use UL approved conduit fittings for all enclosure box connections to prevent wire cuts by sharp edges and excessive strain on wiring.
2 Install listed electrical fittings in the knockou holes for wire protection. Connect the AC line to the luminaire internal wires according to the wiring diagrams using 18-14AWG twist-on wire connectors.

Fixture intended for commercial use only. Use only in non-insulated applications.

www.gecurrent.com