Generac Automatic Transfer Switches
Service and Non-Service Rated
Models
- RXSC100A3
- RXSW100A3
- RXSW150A3
- RXSC200A3
- RXSW200A3
Generac Power Systems, Inc.
generac.com
ETL Listed ?? Engineered & Built in the USA using domestic and foreign parts.
Description
This series of Generac Automatic Transfer Switches is designed for use with single-phase generators that utilize an Evolution™ or Nexus™ Controller. The 100 and 200 Amp open transition switches are available as single phase in both service equipment rated and non-service equipment rated configurations. Service rated equipment configuration ships with a dead front and non-service rated equipment configuration ships without a dead front. The 150 Amp open transition switch is only available in a service rated equipment configuration.
Standard Features
Service rated (RXSW) Generac Automatic Transfer Switches are housed in an aluminum NEMA Type 3R enclosure*, with electrostatically applied and baked powder paint. The Heavy Duty Generac Contactor is an ETL recognized device, designed for years of service. The controller at the generator handles all the timing, sensing, exercising functions, and transfer commands. All switches are covered by a five-year limited warranty.
*Non-service rated (RXSC) switches are housed in a steel enclosure.
Load Management Technology
Through the use of the integrated Smart A/C Module (SACM), these switches have the capability to manage up to four individual HVAC (24 VAC controlled) loads with no additional hardware. When used in tandem with external Smart Management Modules, a total of eight more loads can be managed, providing the most installation-efficient power management options available.
Functions
All timing and sensing functions originate in the generator controller.
Utility Voltage Drop-out | <65% |
Timer to Generator Start | 10 Second Factory Set, Adjustable Between 2 – 1,500 Seconds by a Qualified Dealer* |
Engine Warmup Delay | 5 Seconds |
Standby Voltage Sensor | 65% for 5 Seconds |
Utility Voltage Pickup | >80% |
Re-transfer Time Delay | 15 Seconds |
Engine Cooldown Timer | 60 Seconds |
Exerciser | Nexus™: 12 Minutes Weekly Evolution™: 5 to 12 Minutes Adjustable, Weekly/Bi-weekly/ Monthly |
* When used in conjunction with units utilizing Evolution™ controls.
The Transfer Switch can be Operated Manually Without Power Applied.
Specifications
Model | RXSC100A3 | RXSW100A3 | RXSW150A3 | RXSC200A3 | RXSW200A3 |
---|---|---|---|---|---|
Amps | 100 | 100 | 150 | 200 | 200 |
Voltage | 120/240, 1Ø | 120/240, 1Ø | 120/240, 1Ø | 120/240, 1Ø | 120/240, 1Ø |
Load Transition Type (Automatic) | Open Transition | Open Transition Service Rated | Open Transition Service Rated | Open Transition | Open Transition Service Rated |
Enclosure Type | NEMA 3R | NEMA 3R | NEMA 3R | NEMA 3R | NEMA 3R |
ETL Rating | cETLus | ETLus | ETLus | cETLus | ETLus |
Withstand Rating (Amps) | 10,000 | 10,000 | 22,000 | 10,000 | 22,000 |
Lug Range | 2/0 - #14 | 250 MCM - #6 | 250 MCM - #6 | 2/0 - #14 | 250 MCM - #6 |
Dimensions
Model | RXSC100A3 | RXSW100A3 | RXSW150A3 | RXSC200A3 | RXSW200A3 |
---|---|---|---|---|---|
Height - in (mm) | 17.2 (437.9) | 17.2 (437.9) | 26.8 (679.4) | 17.2 (437.9) | 26.8 (679.4) |
H2 | 20.0 (508.0) | 20.0 (508.0) | 30.0 (672.0) | 20.0 (508.0) | 30.0 (672.0) |
Width - in (mm) | 12.5 (317.5) | 12.5 (317.5) | 10.5 (266.7) | 12.5 (317.5) | 10.5 (266.7) |
W2 | 14.6 (370.8) | 14.6 (370.8) | 13.5 (342.9) | 14.6 (370.8) | 13.5 (342.9) |
Depth - in (mm) | 7.1 (180.1) | 7.1 (180.1) | 6.3 (160.1) | 7.1 (180.1) | 6.3 (160.1) |
Weight - lbs (kg) | 20.0 (9.1) | 22.5 (10.2) | 39.0 (17.7) | 20.0 (9.1) | 39.0 (17.7) |
Diagrams showing the dimensions H1, H2, W1, W2, and Depth for the transfer switch models are provided.
Generac Power Systems, Inc. | S45 W29290 HWY. 59 | Waukesha, WI 53189 | generac.com
©2024 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
Part No. 10000013459 Rev. E 2/12/2024
Related Documents
![]() |
Generac Automatic Transfer Switch Owner's Manual This manual provides comprehensive instructions for the Generac Automatic Transfer Switch, covering safety, general information, installation, operation, and diagrams. It details model numbers RXSW100A3, RXSC100A3, RXSW150A3, RXSW200A3, and RXSC200A3. |
![]() |
Owner's Manual: Automatic Transfer Switch Comprehensive guide for Generac Automatic Transfer Switch (ATS) covering installation, operation, safety, and system components for reliable power backup. |
![]() |
Generac Guardian Series Residential Standby Generators 10/14/18 kW - Features & Specifications Comprehensive overview of Generac Guardian Series residential standby generators (10/14/18 kW), detailing features, technical specifications, switch options, and available accessories for reliable home backup power. |
![]() |
Generac RTS Automatic Transfer Switch Technical Manual: Installation, Operation, and Safety Guide Comprehensive technical manual for Generac RTS Automatic Transfer Switches. Covers design, application, installation, operation, servicing, safety guidelines, voltage checks, generator testing, mounting dimensions, and warranty information. |
![]() |
R-200B Digital Controller Technical Manual This technical manual provides detailed information and operating instructions for the R-200B Digital Controller, a key component for generator sets. It covers safety rules, general information, generator operation modes (manual, auto, exercise), system diagnostics, DIP switch settings, and connection diagrams for both ATS and GTS modes. The manual is essential for proper installation, operation, and maintenance of the R-200B controller with compatible generator units. |
![]() |
Generac Automatic Transfer Switch Lineup for Residential Use Discover the next generation of Generac Automatic Transfer Switches for residential use, offering reduced installation time, improved reliability, and enhanced performance with integrated surge protection. |
![]() |
Generac PWRcell ATS Controller Installation Manual Installation guide for the Generac PWRcell ATS Controller, detailing safety precautions, fuse replacement, and wiring procedures for integrating with Generac Home Standby Generators and PWRcell ESS. |
![]() |
Generac Commercial Generators 22-150 kW: Reliable Standby Power Solutions Generac offers a comprehensive range of commercial standby generators from 22-150 kW, providing reliable backup power for businesses. This document details product features, applications, transfer switches, controllers, accessories, and ordering information, emphasizing business continuity and operational resilience. |