ALTV244UL Series CCTV Power Supplies
Models Include:
- ALTV244UL: 24VAC @ 3.5A (85VA) or 28VAC @ 3A (85VA). Four (4) Fuse Protected Outputs.
- ALTV244ULX: 24VAC @ 3.5A (85VA) or 28VAC @ 3A (85VA). Four (4) Fuse Protected Outputs.
- ALTV244175UL: 24VAC @ 7A (175VA) or 28VAC @ 10A (300VA). Four (4) Fuse Protected Outputs.
- ALTV244ULCB: 24VAC @ 3.5A (85VA) or 28VAC @ 3A (85VA). Four (4) PTC Protected Outputs.
- ALTV244175ULCB: 24VAC @ 7A (175VA) or 28VAC @ 10A (300VA). Four (4) PTC Protected Outputs.
Installation Guide
Rev. 040506
Installing Company: ________________ Service Rep. Name: ___________________________________
Address: ______________________________________________ Phone #: ___________________
Overview
Altronix ALTV244UL Series CCTV Power Supplies provide 24VAC or 28VAC distributed via four (4) fuse or PTC protected outputs for powering CCTV cameras, heaters and other video accessories.
Four (4) Output ALTV244UL Reference Chart
Altronix Model Number | Output Voltage | Total Output Current (Power) | Number of Outputs | PTC Protected Outputs (Class 2 power-limited for Dry locations / Class 3 for Wet locations) (auto-resettable) | Fuse Protected | Class 1 Outputs | Individual Output Current (max per output, not to exceed total output current) | Fuse Ratings | Main Fuse Ratings | Primary In-line Fuse Ratings | 115VAC 60Hz Input Current | Agency Listings |
---|---|---|---|---|---|---|---|---|---|---|---|---|
ALTV244UL | 24VAC 28VAC | 3.5A 3A | 4 | ❌ | ✔️ | ✔️ | 3.5A | 3.5A | 5A/ 250V | 3.5A/ 250V | 0.9A | CULUS CE |
ALTV244ULX | 24VAC 28VAC | 3.5A 3A | 4 | ❌ | ✔️ | ✔️ | 3.5A | 3.5A | 5A/ 250V | 3.5A/ 250V | 0.9A | CULUS CE |
ALTV244ULCB | 24VAC 28VAC | 3.5A 3A | 4 | ✔️ | ❌ | ✔️ | 2.5A | - | 5A/ 250V | 3.5A/ 250V | 0.9A | CE |
ALTV244175UL | 24VAC 28VAC | 7A 6.25A | 4 | ❌ | ✔️ | ✔️ | 3.5A | 3.5A | 10A/ 250V | - | 1.76A | |
ALTV244175ULCB | 24VAC 28VAC | 7A 6.25A | 4 | ✔️ | ❌ | ✔️ | 2.5A | - | 10A/ 250V | - | 1.76A |
Specifications
Agency Listings:
- UL Listed for Commercial CCTV Equipment (UL 2044).
- CUL Listed - CSA Standard C22.2 No.1-98, Audio, Video and Similar Equipment.
- CE European Conformity.
Input:
- 115VAC, 50/60Hz.
Output:
- Four (4) fuse or PTC protected outputs.
- 24VAC or 28VAC output.
- Outputs are rated @ 3.5A (fused) or 2.5A (PTC).
- Surge suppression.
Features:
- Power ON/OFF switch (ALTV244UL, ALTV244ULX, and ALTV244ULCB).
- Illuminated power disconnect circuit breaker with manual reset (ALTV244175UL and ALTV244175ULCB).
- Unit maintains camera synchronization.
- Ease of installation saves time & eliminates costly labor.
- Spare fuses included (on fuse protected models).
Enclosure Dimensions (H x W x D)
ALTV244UL, ALTV244ULCB: 8.5" x 7.5" x 3.5" (215.9mm x 190.5mm x 88.9mm).
ALTV244175UL, ALTV24175ULCB: 12" x 7.5" x 4.5" (304.8mm x 190.5mm x 114.3mm).
ALTV244ULX: 13.5" x 13" x 3.25" (342.9mm x 330.2mm x 82.6mm).
Installation Instructions
- Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure's upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure's upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pgs. 10-12). Secure enclosure to earth ground.
- Set power switch on power distribution board marked [PD] to OFF position for models ALTV244UL, ALTV244ULX or ALTV244ULCB (Figs. 1-3, pgs. 4-6).
- All units are factory set for 24VAC operation. For 28VAC operation adjust unit prior to applying power as follows: Remove wires marked [24V] and [28V] from terminals marked [P] and [S]. Connect wire marked [28V] to terminal marked [P] and connect wire marked [24V] to terminal marked [S]. Note: ALTV244ULCB set for 28VAC operation is not Class 2 Rated, not power-limited.
- Connect AC power to the black and white flying leads of the transformer (Figs. 1-5, pgs. 4-8). Secure green lead to earth ground. Use 18 AWG or larger gauge for all power connections. Keep power-limited (PTC protected outputs only) wiring separate from non power-limited wiring. Minimum 0.25" spacing must be provided. Use separate knockouts.
- Set power switch on power distribution board marked [PD] to ON position for models ALTV244UL, ALTV244ULX or ALTV244ULCB (Figs. 1-3, pgs. 4-6).
- Measure output voltage before connecting devices. This helps avoiding potential damage. Terminals marked [1P - 4P] are of the same polarity. CAUTION: Determine the maximum operating voltage of the equipment being powered before adjusting the output voltage.
- Set power switch on power distribution board marked [PD] to OFF position for models ALTV244UL, ALTV244ULX or ALTV244ULCB (Figs. 1-3, pgs. 4-6).
- Connect devices to the terminals marked [1P] - [1N] through [4P] - [4N] on PD4 or PD4CB board (Figs. 1-5, pgs. 4-8), carefully observing polarity.
- Set power switch on power distribution board marked [PD] to ON position for models ALTV244UL, ALTV244ULX or ALTV244ULCB (Figs. 1-3, pgs. 4-6).
- Green LED will illuminate when power is present.
- Upon completion of the wiring, secure enclosure door with screws (supplied). Installation of a cam lock is optional.
Caution:
Equipment to be installed/serviced by authorized/trained personnel only. Shut branch circuit power before installing/servicing equipment.
WARNING:
To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture. This installation should be made by qualified service personnel and should conform to the National Electrical Code and all local codes. Use 75°C or higher rated UL insulated wiring for connecting the unit to the mains. Replace fuses with the same type and rating (refer to Four (4) Output ALTV244UL Reference Chart, pg. 2).
Terminal Identification
PD4/PD4CB - Distribution Module
Terminals | Description |
---|---|
1P - 4P | AC output. |
1N - 4N | AC output. |
⚡️ [High Voltage Warning]: The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE within the product's enclosure that may be of sufficient magnitude to constitute an electric shock.
⚠️ [Important Information]: The exclamation point within an equilateral triangle is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance.
CAUTION:
To reduce the risk of electric shock do not open enclosure. There are no user serviceable parts inside. Refer servicing to qualified service personnel.
Diagrams
Fig. 1 - ALTV244UL Internal Layout
This diagram shows the internal components of the ALTV244UL. It features a transformer (XFMR) with input connections for a black lead (non power-limited), white lead (non power-limited), and a green lead for ground. The input is rated for 115VAC, 50/60Hz. A primary in-line fuse is present, along with an ON/OFF switch. The unit has four Class 1 Outputs, labeled 1P/1N through 4P/4N. Each output terminal pair is designed for AC output. The diagram also shows a Voltage Selection Configuration section with terminals N, P, S, allowing selection between 24VAC and 28VAC outputs. The output terminals are protected by 3.5A, 250V fuses.
Fig. 2 - ALTV244ULCB Internal Layout
This diagram illustrates the ALTV244ULCB. Similar to Fig. 1, it includes a transformer (XFMR), input wiring (black, white, green leads) for 115VAC, 50/60Hz, a primary in-line fuse, and an ON/OFF switch. It features four Class 1 Outputs (1P/1N to 4P/4N). The voltage selection configuration allows for 24VAC or 28VAC output. A note indicates that the 24VAC configuration is Class 2 Not Wet/Class 3 Wet, while the 28VAC configuration is Class 1. The output terminals are protected by 3.5A, 250V fuses.
Fig. 3 - ALTV244ULX Internal Layout
This diagram depicts the internal layout of the ALTV244ULX. It shows the transformer (XFMR), input connections (black, white, green leads) for 115VAC, 50/60Hz, a primary in-line fuse, and an ON/OFF switch. The unit provides four Class 1 Outputs (labeled 1P/1N through 4P/4N). The voltage selection configuration allows for 24VAC or 28VAC output. The output terminals are protected by 3.5A, 250V fuses.
Fig. 4 - ALTV244175UL Internal Layout
This diagram shows the internal components of the ALTV244175UL. It features a transformer (XFMR) with input connections for black, white, and green leads (115VAC, 50/60Hz). A primary in-line fuse is present. Instead of a simple ON/OFF switch, this model has an Illuminated Power Disconnect Circuit Breaker with a manual reset. It provides four Class 1 Outputs (1P/1N to 4P/4N). The voltage selection configuration allows for 24VAC or 28VAC output. The output terminals are protected by 3.5A, 250V fuses.
Fig. 5 - ALTV244175ULCB Internal Layout
This diagram illustrates the ALTV244175ULCB. It includes a transformer (XFMR) with 115VAC, 50/60Hz input (black, white, green leads) and a primary in-line fuse. This model also features an Illuminated Power Disconnect Circuit Breaker with manual reset. It offers four Class 1 Outputs (1P/1N to 4P/4N). The voltage selection configuration supports 24VAC or 28VAC output. A note specifies that the 24VAC configuration is Class 2 Not Wet/Class 3 Wet, and the 28VAC configuration is Class 1. The output terminals are protected by 3.5A, 250V fuses.
Notes
Enclosure Dimensions (H x W x D)
ALTV244UL, ALTV244ULCB
Dimensions: 8.5" x 7.5" x 3.5" (215.9mm x 190.5mm x 88.9mm).
Diagram Description: This drawing shows the front, side, and top views of the enclosure. It details mounting hole positions and dimensions, including offsets and diameters, for the ALTV244UL and ALTV244ULCB models. Key dimensions include height (8.125" / 206.4mm), width (7.25" / 184.2mm), and depth (3.5" / 88.9mm). Mounting hole centers are indicated with precise measurements.
ALTV244ULX
Dimensions: 13.5" x 13" x 3.25" (342.9mm x 330.2mm x 82.6mm).
Diagram Description: This drawing presents the enclosure dimensions for the ALTV244ULX. It includes front, side, and top views, highlighting mounting hole locations and dimensions. Key dimensions are height (13.0" / 330.2mm), width (12.5" / 317.5mm), and depth (3.25" / 82.6mm). The diagram shows precise measurements for hole placement and spacing.
ALTV244175UL, ALTV244175ULCB
Dimensions: 12" x 7.5" x 4.5" (304.8mm x 190.5mm x 114.3mm).
Diagram Description: This drawing provides the enclosure dimensions for the ALTV244175UL and ALTV244175ULCB models. It includes front, side, and top views, detailing mounting hole positions and dimensions. Key dimensions are height (12" / 304.8mm), width (7.5" / 190.5mm), and depth (4.5" / 114.3mm). The diagram specifies precise measurements for mounting hole placement and spacing.