APC Installation and Operation

Back-UPS™ Pro BR1000G

This document provides detailed instructions for the installation and operation of the APC Back-UPS Pro BR1000G. It covers initial setup, equipment connection, operational features, troubleshooting, and technical specifications.

Inventory

Inspect the package contents upon receipt. Notify the carrier and dealer if there is any damage.

Safety and General Information

  • Read the Safety Guide supplied with this unit before installing the UPS.
  • This UPS is intended for indoor use only.
  • Do not operate this UPS in direct sunlight, in contact with fluids, or where there is excessive dust or humidity.
  • Be sure the air vents on the UPS are not blocked. Allow adequate space for proper ventilation.
  • The battery typically lasts for three to five years. Environmental factors impact battery life. Elevated ambient temperatures, poor quality AC power, and frequent short duration discharges will shorten battery life.
  • Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or extension cords.

Connect the Battery

Follow these steps to connect the battery:

  1. Locate the battery compartment.
  2. Remove the battery.
  3. Connect the battery cable.
  4. Insert the battery back into the unit.
  5. Secure the battery compartment cover.

Install PowerChute™ Personal Edition Software

PowerChute Personal Edition software provides automatic file saving and shutdown of your computer in the event of a power failure. Use the cable supplied with the Back-UPS to connect the data port on the Back-UPS to the USB port on your computer. Place the CD into your computer, and follow the on-screen instructions.

Connect the Equipment

Battery Backup and Surge Protected Outlets

When the Back-UPS is receiving input power, the Battery Backup with Surge Protection outlets will supply power to connected equipment. During a power outage or other AC problems, the Battery Backup outlets receive power for a limited time from the Back-UPS. Connect equipment such as printers, fax machines, scanners, or other peripherals that do not need battery backup power to the Surge Protection Only outlets. These outlets provide full-time protection from surges even if the Back-UPS is switched OFF.

Master and Controlled Outlets

To conserve electricity, when the device connected to the Master Outlet goes into Sleep or Standby mode, or turns Off, the Controlled device(s) will shut down as well, saving electricity. Connect a master device, such as a desktop computer or audio/visual receiver to the Master outlet. Connect peripheral devices such as a printer, speakers, or a scanner to the Controlled outlets.

#Port/FeatureDescription
1USB and Serial Data portTo use PowerChute Personal Edition, connect the supplied USB software cable or an optional serial cable (not supplied).
2Ground screwConnect the ground lead of additional surge suppression devices such as network and data line surge protectors.
3Building Wiring Fault indicatorIf this indicator is illuminated, there is a problem with the wiring in the building. Contact an electrician immediately and do not use the Back-UPS.
4Surge Protected outlets, controlled by the Master outletThese outlets are protected from electrical surges, and will disconnect from AC power during a power outage, or if the Master device goes into Sleep or Standby mode.
5Surge Protected outletsThese outlets provide full-time protection from surges, even if the Back-UPS is off. Connect equipment such as printers and scanners that do not require battery backup protection.
6Battery Backup outlets with Surge ProtectionDuring a power outage or other AC problems, the Battery Backup outlets receive power for a limited time from the Back-UPS. Connect critical equipment such as desktop computer, computer monitor, modem or other data sensitive devices into these outlets.
7Battery Backup outlets with Surge Protection, controlled by the Master outletThese outlets will supply battery power to the connected equipment during a power outage. Power will be disconnected to these outlets if the Master device goes into Sleep or Standby mode. Connect equipment such as a computer monitor to these outlets.
8Master outletConnect the master device to this outlet, in most scenarios, this will be the main computer.
9In/Out Ethernet surge-protected portsUse an Ethernet cable to connect a cable modem to the IN port, and connect a computer to the OUT port.
10Coaxial ports with surge protectionConnect a cable modem or other equipment with coaxial jacks.

Operation

Power Saving Function

To conserve electricity, configure the Back-UPS to recognize a Master device, such as a desktop computer or an A/V receiver, and Controlled peripheral devices, such as a printer, speakers, or a scanner. When the Master device goes into Sleep or Standby mode, or is switched OFF, the Controlled device(s) will be switched off as well, saving electricity.

Note: Devices that provide network services such as routers, modems or wireless printers should not be plugged into the Controlled outlets. This product ships with the Power Saving feature Disabled. To enable this feature follow the instructions below.

  • Enable: Press and hold MUTE ? and DISPLAY ?️ simultaneously for two seconds. The Back-UPS will beep to indicate that the feature is enabled. The leaf icon ? on the display will illuminate.
  • Disable: Press and hold MUTE ? and DISPLAY ?️ simultaneously for two seconds. The Back-UPS will beep to indicate that the feature is disabled. The leaf icon ? on the display will darken.

Setting the threshold: The amount of power used by a device in Sleep or Standby mode varies between devices. It may be necessary to adjust the threshold at which the Master outlet signals the Controlled outlets to shut down.

  1. Ensure a master device is connected to the Master outlet. Put that device into Sleep or Standby mode, or turn it OFF.
  2. Press DISPLAY ?️ and MUTE ? simultaneously and hold for six seconds, until the leaf icon ? flashes three times and the Back-UPS beeps three times.
  3. The Back-UPS will now recognize the threshold level of the Master device and save it as the new threshold setting.

Power Saving Display

The display interface can be configured to be continuously illuminated, or to save energy, it can be configured to darken after a period of inactivity.

  • Full Time Mode: Press and hold DISPLAY ?️ for two seconds. The display will illuminate and the Back-UPS will beep to confirm the Full Time mode.
  • Power Saving Mode: Press and hold DISPLAY ?️ for two seconds. The display will darken and the Back-UPS will beep to confirm the Power Saving mode. While in Power Saving Mode, the display will illuminate if a button is pressed, it then darkens after 60 seconds of no activity.

Unit Sensitivity

Adjust the sensitivity of the Back-UPS to control when it will switch to battery power; the higher the sensitivity, the more often the Back-UPS will switch to battery power.

  1. Ensure the Back-UPS is connected to AC power, but is OFF.
  2. Press and hold the POWER ? button for six seconds. The LOAD CAPACITY bar will flash on and off, indicating that the Back-UPS is in programming mode.
  3. Press POWER ? again to rotate through the menu options. Stop at selected sensitivity. The Back-UPS will beep to confirm the selection.

Sensitivity Levels:

LevelVoltage RangeDescription
Low sensitivity78-142 Vac
Input voltage is extremely low or high. (Not recommended for computer loads.)
Medium sensitivity (Default)88-139 Vac
The Back-UPS frequently switches to battery power.
High sensitivity88-136 Vac
The connected equipment is sensitive to voltage fluctuations.

Front Panel Buttons and Display Interface

Use the three buttons on the front panel of the Back-UPS and the display interface to configure the Back-UPS.

Front panel buttons

  • 1 Mute button ?
  • 2 Power On/Off button ?
  • 3 Display button ?️
  • 4 Display interface

Display Interface Indicators

  • On Line: The Back-UPS is supplying conditioned AC power to connected equipment.
  • Power-Saving ?: Master and Controlled outlets are enabled, saving power when the master device goes into sleep or standby mode.
  • Load Capacity: The load is indicated by the number of sections illuminated, one to five. Each bar represents 20% of the load.
  • Battery Charge ?: The battery charge level is indicated by the number of sections illuminated. When all five blocks are illuminated, the Back-UPS is at full charge. When one block is filled, the Back-UPS is near the end of its battery capacity, the indicator will flash and the Back-UPS will beep continuously.
  • Overload ⚠️: The power demand from the load has exceeded the capacity of the Back-UPS.
  • Event: The event counter shows the number of events that occurred that caused the Back-UPS to switch to on-battery operation.
  • Automatic Voltage Regulation (AVR) ⚡: The Back-UPS can compensate for high or low input voltage.
    • When illuminated, the Back-UPS is compensating for low input voltage.
    • When illuminated, the Back-UPS is compensating for high input voltage.
  • In/Out: Input voltage / Output voltage.
  • System Faults ❗: The system has a fault. The fault number will illuminate on the display interface. See "System Faults" on page 5.
  • Mute ?: If the line through the speaker icon is illuminated, the audible alarm has been turned off.
  • Replace Battery ?: The battery is nearing the end of its useful life. Replace the battery.
  • On Battery ?: The Back-UPS is supplying battery backup power to the connected equipment, it will beep four times every 30 seconds.

Warnings and System Faults

Audible Warnings

Audible WarningDescription
Four Beeps Every 30 SecondsBack-UPS is running on battery. You should consider saving any work in progress.
Continuous BeepingLow battery condition and battery run-time is very low. Promptly save any work in progress, exit all open applications, and shut down the operating system.
Continuous toneBattery Backup outputs are overloaded.
Chirps every 2 Seconds with the Load Capacity Bar flashingBattery is disconnected.
Chirps for 1 Minute every 5 hoursBattery fails the automatic diagnostic test and should be replaced.

Warning Icons

If these icons are illuminated...

  • Overload Icon (on AC power): This may be the problem. The Back-UPS is operating on AC power, but is overloaded. Disconnect one of the items connected to the Back-UPS. If the Overload icon stops flashing, the Back-UPS is no longer overloaded and will continue to operate normally.
  • Overload Icon (on battery power): The Back-UPS is operating on battery power, but is overloaded. Disconnect one of the items connected to the Back-UPS. If the Overload icon stops flashing, the Back-UPS is no longer overloaded and will continue to operate normally.
  • Battery Fault Icon: The Back-UPS is operating on AC power, but the battery is not functioning properly. Contact Schneider Electric IT (SEIT) Customer Service to order a replacement battery. See "Replacement Battery" on page 8.
  • Low Battery Icon: The Back-UPS is operating on battery power and the battery power is getting low. Shut down all connected equipment to avoid losing an unsaved data. When possible, connect the Back-UPS to AC power to recharge the battery.

System Faults

The Back-UPS will display these fault messages. For faults F01 and F02, contact SEIT Technical Support.

Fault CodeDescriptionCorrective Action
F01On-Battery OverloadTurn the Back-UPS off. Disconnect non-essential equipment from the Battery Backup outlets and then turn Back-UPS on.
F02On-Battery Output ShortTurn the Back-UPS off. Disconnect non-essential equipment from the Battery Backup outlets and then turn Back-UPS on.
F03On-Battery Xcap OverloadFaults F03-F09 cannot be corrected by the user, contact SEIT Technical Support for assistance.
F04Clamp Short
F05Charge Fault
F06Relay Welding
F07Temperature
F08Fan Fault
F09Internal Fault

Function Button Quick Reference

FunctionButtonTiming (seconds)UPS StatusDescription
Power On?0.2OffPress POWER to start receiving input AC power. If AC input power is not available, the Back-UPS will run on battery power.
Power Off?2OnThe Back-UPS is not receiving input AC power, but is providing surge protection.
Status Inquiry?️0.2OnVerify the status or condition of the Back-UPS. The LCD will illuminate for 60 seconds.
Full-Time/Power-Saving mode?️2OnThe LCD will illuminate and the Back-UPS will beep to confirm the Full-Time mode. The LCD will darken and the Back-UPS will beep to confirm the Power-Saving mode. While in Power-Saving Mode, the LCD will illuminate if a button is pressed, then darkens after 60 seconds of no activity.
Event Specific Mute?0.2OnDisable any audible alarms caused by an event.
General Status Enable/Disable Mute?2OnEnable or disable the audible alarms. The Mute icon will illuminate and the Back-UPS will beep one time. The Mute function will not activate unless the Back-UPS is operating on battery power.
Sensitivity Programming?6OffThe Load Capacity icon will blink, indicating that the Back-UPS is in programming mode. Use the POWER button to scroll through Low, Medium, and High, stop at selected sensitivity. The Back-UPS will beep to confirm selection. See Configuration for details.
Master/Controlled outlet Enable/Disable?2OnThe leaf icon will darken indicating that the Master Outlet feature is disabled or illuminate to indicate the Master Outlet feature is enabled. The Back-UPS will beep once.
Master/Enable Threshold Calibration?6OnWhile calibrating the threshold setting, the device connected to the Master Outlet should be turned off or placed in Standby or Sleep mode. Upon completion, Power-Saving icon will flash 3 and beep 3 times.
Self-Test (manual)?6OnThe Back-UPS will perform a test of the internal battery. Note: This will happen automatically when the Back-UPS is turned ON.
Event Reset?️ + ?0.2OnWhen the Event screen is visible, press and hold DISPLAY, then press POWER, to clear the failure event counter.
Fault Reset?2FaultAfter a fault has been identified, press POWER to remove the visual indication and return to standby status.

Troubleshooting

ProblemPossible CauseCorrective Action
Back-UPS will not switch on.The Back-UPS is not connected to AC power.Ensure that the Back-UPS is securely connected to an AC outlet.
The circuit breaker has been tripped.Disconnect non-essential equipment from the Back-UPS. Reset the circuit breaker. Re-connect equipment one item at a time. If the circuit breaker is tripped again, disconnect the device that caused the trip.
The internal battery is not connected.Connect the battery.
The AC input voltage is out of range.Adjust the transfer voltage and sensitivity range.
The Back-UPS does not provide power during a AC power outage.Ensure that essential equipment is not plugged into a SURGE ONLY outlet.Disconnect equipment from the SURGE ONLY outlet and re-connect to a Battery Backup outlet.
The Back-UPS is operating on battery power, while connected to AC power.The plug has partially pulled out of the wall outlet, the wall outlet is no longer receiving AC power, or the circuit breaker has been tripped.Ensure that the plug is fully inserted into the wall outlet. Ensure that the wall outlet is receiving AC power by checking it with another device.
The Back-UPS is performing an automatic self test.No action is necessary.
The Back-UPS does not provide the expected amount of backup time.The AC input voltage is out of range, the frequency is out of range, or the waveform is distorted.Adjust the transfer voltage and sensitivity range.
Battery Backup outlets may be fully or improperly loaded.Disconnect non-essential equipment from the Battery Backup outlets and connect the equipment to SURGE ONLY outlets.
The battery was recently discharged due to a power outage and has not fully recharged.Charge the battery cartridge for 16 hours.
The REPLACE BATTERY indicator ? is illuminated.The battery has reached the end of its useful life.Replace the battery.
The OVERLOAD indicator ⚠️ is illuminated.The equipment connected to the Back-UPS is drawing more power than the Back-UPS can provide.Disconnect non-essential equipment from the Battery Backup outlets and connect the equipment to SURGE ONLY outlets.
The SYSTEM FAULT indicator ❗ is illuminated, all the front panel indicators are flashing.There is an internal fault.Determine which internal fault message is displayed by matching the number displayed on the LCD with the corresponding Fault Message (see System Faults) and contact SEIT Technical Support.
Power is not supplied to some outlets.Power to the Controlled outlets has intentionally been turned off.Confirm that the correct peripherals are connected to Controlled outlets. If this feature is not desired, disable the Power-Saving Master and Controlled outlets.
The Controlled outlets are not supplying power, even though the Master device is not in sleep mode.The Master Outlet threshold may be incorrectly set.Adjust the threshold when the Master outlet signals the Controlled outlets to shut down.

Specifications

SpecificationValue
VA1000 VA
Maximum Load600 W
Nominal Input Voltage120 V
Online Input Voltage Range88 - 141 V
Automatic Voltage Regulation(94-107) +11.2%
(126-141) -11.2%
Frequency Range50/60 Hz ± 1 Hz
On-battery WaveshapeStep-approximated sine-wave
Typical Recharge Time8 hours
Transfer Time8 ms, maximum
Operating Temperature0° to 40°C (32° to 104°F)
Storage Temperature-5° to 45°C (23° to 113°F)
Unit Dimensions25 × 10 × 38.2 cm (9.84 × 3.93 × 15.0 in)
Unit Weight10.7 kg (23.6 lbs)
InterfaceUSB
On Battery RuntimeGo to: www.apc.com

Service, Warranty, and Support

Service

If the unit requires service, do not return it to the dealer. Follow these steps:

  1. Review the Troubleshooting section of the manual to eliminate common problems.
  2. If the problem persists, contact Schneider Electric IT (SEIT) Customer Support through the APC by Schneider Electric Web site, www.apc.com.
    • Note the model number and serial number and the date of purchase. The model and serial numbers are located on the rear panel of the unit and are available through the LCD display on select models.
    • Call SEIT Customer Support and a technician will attempt to solve the problem over the phone. If this is not possible, the technician will issue a Returned Material Authorization Number (RMA#).
    • If the unit is under warranty, the repairs are free.
    • Service procedures and returns may vary internationally. Refer to the APC by Schneider Electric Web site for country specific instructions.
  3. Pack the unit in the original packaging whenever possible to avoid damage in transit. Never use foam beads for packaging. Damage sustained in transit is not covered under warranty.
  4. Always DISCONNECT THE UPS BATTERIES ? before shipping. The United States Department of Transportation (DOT), and the International Air Transport Association (IATA) regulations require that UPS batteries be disconnected before shipping. The internal batteries may remain in the UPS.
  5. Write the RMA# provided by Customer Support on the outside of the package.
  6. Return the unit by insured, pre-paid carrier to the address provided by Customer Support.

Replacement Battery

The battery typically lasts for 3 to 5 years, a shorter period if subjected to frequent outages or elevated temperatures. Battery replacement part for Back-UPS BR1000G is APCRBC123. Recycle spent battery cartridges.

Warranty

The standard warranty is three (3) years from the date of purchase. Schneider Electric IT (SEIT) standard procedure is to replace the original unit with a factory reconditioned unit. Customers who must have the original unit back due to the assignment of asset tags and set depreciation schedules must declare such a need at first contact with an SEIT Technical Support representative. SEIT will ship the replacement unit once the defective unit has been received by the repair department, or cross ship upon the receipt of a valid credit card number. The customer pays for shipping the unit to SEIT. SEIT pays ground freight transportation costs to ship the replacement unit to the customer.

APC by Schneider Electric IT Customer Support Worldwide

For country specific customer support, go to the APC by Schneider Electric Web site, www.apc.com.

Select models are ⭐ ENERGY STAR qualified. For more information go to www.apc.com/site/recycle/index.cfm/energy-efficiency/energy-star/.

EMC Compliance

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

© 2014 APC by Schneider Electric. APC, the APC logo, Back-UPS, and PowerChute are owned by Schneider Electric Industries S.A.S., or their affiliated companies. All other trademarks are property of their respective owners.

EN 990-3804B 10/2014

Models: BR1000G, APC,APC,APC,Back-UPS,Pro,1000VA,UPS,Battery,Backup,&,Surge,Protector,(BR1000G),Stepped,Sinewave,1000VA,B07HHQBYMM,B0038ZTZ3W

PDF preview unavailable. Download the PDF instead.

810iRwyeBBL Acrobat Distiller 9.5.5 (Windows)

Related Documents

Preview APC Back-UPS BR1000G-IN / BR1500G-IN: Installation and Operation Manual
Comprehensive guide for installing and operating the APC Back-UPS BR1000G-IN and BR1500G-IN Uninterruptible Power Supply (UPS), covering specifications, connections, features, troubleshooting, and service.
Preview APC Back-UPS Pro 900: Premium Battery Backup & Surge Protector
Discover the APC Back-UPS Pro 900, offering reliable battery backup, surge protection, and automatic voltage regulation for your electronics. Features LCD display, green outlets, and auto-shutdown software.
Preview APC Back-UPS BX Series User Manual: Installation, Operation, and Troubleshooting
Comprehensive user manual for APC Back-UPS BX Series (500VA to 2200VA) from Schneider Electric, covering safety instructions, product description, operational features, installation, troubleshooting, service, and warranty information.
Preview APC Back-UPS BX Series User Manual: Power & Surge Protection for Computers
Comprehensive user manual for APC Back-UPS BX Series (500VA to 2200VA). Learn about safety, installation, features, specifications, status indicators, and troubleshooting for reliable power protection.
Preview APC Back-UPS BVN650M1, BVN650M1-CA, BVN900M1, BVN900M1-CA User Manual
User manual for APC Back-UPS models BVN650M1, BVN650M1-CA, BVN900M1, and BVN900M1-CA, covering safety, installation, specifications, operation, troubleshooting, and service.
Preview APC Back-UPS Pro 900 Installation and Operation Guide
This guide provides instructions for installing and operating the APC Back-UPS Pro 900, including setup, software installation, connection of equipment, operational features like power saving and display modes, troubleshooting, and specifications.
Preview APC Back-UPS Pro 1200/1500 230V Installation and Operation Guide
Comprehensive guide for installing and operating the APC Back-UPS Pro 1200/1500 230V. Covers safety, setup, software installation, operation, troubleshooting, specifications, and warranty.
Preview APC Back-UPS BE550G/BE700G User Manual: Installation, Operation, and Troubleshooting
Comprehensive user manual for APC Back-UPS BE550G and BE700G models, covering installation, setup, power-saving features, status indicators, troubleshooting, specifications, and support.