SpaceLogic KNX Energy Meter REG-K/3x230 V/16 A
Operating Instructions
Article No.: MTN6600-0603
For Your Safety
⚠️ DANGER
Risk of serious damage to property and personal injury, e.g. from fire or electric shock, due to incorrect electrical installation. Safe electrical installation can only be ensured if the person in question can prove basic knowledge in the following areas:
- Connection to installation networks
- Connecting several electrical devices
- Laying electric cables
- Connecting and establishing KNX networks
These skills and experience are normally only possessed by skilled professionals trained in electrical installation technology. Failure to meet or disregard these minimum requirements makes you solely liable for any damage to property or personal injury.
Getting to Know the Energy Meter
The KNX Energy Meter, REG-K/3x230 V/16 A (referred to below as Energy Meter) enables monitoring and measurement of energy on connected channels, thereby increasing building energy efficiency.
Device Properties
- Measurement of: energy consumption, power, and current, providing results via the bus.
- Determination of active energy consumption per channel and total consumption.
- Accuracy of active energy measurement per channel: max. 1.5%
- Accuracy of power measurement: 10%
- For installation on TH35 DIN rails as per DIN EN 60715.
- Bus connection is carried out via a bus connecting terminal.
Important: Never use the device in combination with current transformers.
Connections, Displays, and Operating Elements
The device features the following:
- A: Bus connection
- B: Protective cap for A
- C: Push-button and LED: programming
- D: LED: RUN
- E: LED: channel 1-3
- F: Connecting terminals
Diagram Description: A visual representation of the device showing the location of the bus connection (A), protective cap (B), programming button/LED (C), RUN LED (D), channel LEDs (E), and connecting terminals (F).
Mounting the Energy Meter
❗ WARNING
Risk of death from electric shock. The device can be damaged. Safety clearance must be guaranteed in accordance with IEC 60664-1. There must be at least 4 mm between the individual cores of the 230 V supply cable and the KNX line A.
- Place the device onto the DIN rail.
- Wire the device according to the desired application.
Diagram Description: Illustrates the device being mounted on a DIN rail and shows the required 4mm clearance between the 230V supply cable and the KNX line.
Note: Any number of loads can be connected to an input as long as the maximum input current of 16 A per channel is not exceeded. Any phases can be assigned to channels 1-3.
Putting the Energy Meter into Operation
- Press the programming button: the programming LED lights up.
- Load the physical address and application into the device from the ETS: The programming LED goes out.
The RUN LED lights up, indicating the application has been loaded successfully and the device is ready for operation.
Status LED Indicators
Status LED (red/green) | Programming LED (red) | RUN LED (green) | Indication |
---|---|---|---|
ON | - | The physical address can be loaded | |
OFF | ON | Application loaded and bus voltage connected | |
Flashes green | ON | Measurement being performed | |
OFF | OFF | No bus voltage | |
OFF | ON | Mains voltage absent | |
Flashes red | ON | Overload |
Behaviour in the Event of Problems
Mains Voltage Failure
No measurement can be performed on any input channels, and the status signal is unavailable. Communication via the bus is still possible.
Bus Failure (with Voltage Connected)
If a bus failure occurs, measurement stops immediately, and no further information is recorded. The RUN LED switches off.
Bus Connection Restored (with Voltage Connected)
The consumption value saved in the internal memory prior to the bus failure will be used as the starting point for power measurement once the bus connection is restored.
Technical Data
- Supply voltage: via KNX bus, DC 24 V, max. 12.5 mA
- Operating elements: 1x programming button
- Display elements: 1x LED (red): Programming, 1x LED (green): RUN, 1x LED (red/green) per channel: Status
- Inputs:
- Voltage: AC 220/230 V, 50/60 Hz
- Max. load per channel: 16 A
- Current: 20 mA (power factor 1)
- External protection per channel: 16 A
- Accuracy class (according to IEC 61557-12):
- Active energy measurement: Class 1
- Power measurement: 10%
- Ambient temperature:
- Operation: -5 °C to +45 °C
- Environment: Can be used at elevations up to 2000 m above sea level (MSL)
- Max. humidity: 93%, no condensation
- Connections:
- KNX: Bus connecting terminal
- Inputs: Screw terminal for cross sections up to max. 2.5 mm²
- Type of protection: IP 20
- Device width (HxWxD): 90x72x65 mm, 4 modules
Manufacturer: Schneider Electric Industries SAS
For technical questions, please contact the Customer Care Centre in your country. Visit se.com/contact