Bell Lighting Emergency Bulkhead 09040V2

Installation Instructions

Specifications

Important Information

Important User Advice

Installation Instructions: Emergency Bulkhead (09040V2)

Read these instructions before installation and retain for future reference. This equipment should be installed by a competent electrician.

Installation:

  1. Connect mains supply wiring as follows: L (Live), N (Neutral).

Diagram showing wiring connections for Non-maintained and Maintained operation.

  1. Power line & battery wires should be connected securely, and all screws fixed.
  2. Switch on 220-240V AC supply and check if the green LED indicator illuminates to confirm charging of batteries.
  3. Allow a short period for part charging of the batteries and then isolate the mains supply to the fitting in order to check the correct operation of the fitting in emergency mode. In the first use, after a continuous charge for 24 hours, a mains failure should be simulated to ensure that the fitting works for its specified time (only at a safe & appropriate time). The fitting will be fully charged with 24 hours continuous charging.

Diagram illustrating the battery and wiring connections within the luminaire.

The instruction of the switch on PCB: 'ON' indicates standard mode, '1' indicates self-test mode. Please ensure that the switch position is set before installation.

Recommended Routine Test Procedure

The following tests are designed to ensure the continued protection of your premises and occupants. Because of the possibility of a failure of the normal lighting supply occurring shortly after a period of testing, all tests should, whenever possible, be undertaken at times of least risk, e.g. during daylight hours.

This product may contain substances that can be hazardous to the environment if not disposed of properly. Electrical and electronic equipment should never be disposed of with general household waste but must be separated for its correct treatment and recovery. Where possible, recycle your packaging.

Self-Test Functionality

Self-Test fittings perform a self-commissioning test at first power on. After charging for 24 hours, a full duration test (3 hours) is performed. Initial function and duration tests are randomly generated. They are then performed in accordance with standard requirements (every 30 days for function tests and every 52 weeks for duration tests).

A single bi-colour indicator LED is fitted in all Self-Test products. This LED is clearly visible for manual inspection. It indicates the module status. The LED shows permanent green or flashing green when conditions are normal and flashing red if a fault condition is present.

Function Test

A function test is a 2 minutes test that simulates a mains failure and checks the operation of the emergency light source from the battery supply. The local indicator LED slow flashes green whilst the 2 minutes function test is in progress. If there is a failure during a function test, the local indicator LED changes to a flashing red.

Duration Test

A duration test simulates a mains failure. It also checks the operation of the emergency light source from the battery supply for the rated duration of the module. The local indicator LED fast flashes green whilst the duration test is in progress. If there is a failure during a duration test, the local indicator LED either changes to flashing red. The battery is required to be fully charged before a duration test can be started.

Test Button Functions

The test button of the unit has the following functions:

Test Button Green LED Status
Press for approx 1 Second Off Emergency mode for 1 second
Press for approx 5 Seconds Slow flash Function for 30 seconds
Press for approx 7 Seconds Fast Flash 3 Hour duration test
Press for approx 10 Seconds End the duration test

Please refer to the following chart below for more complete description/fault indication:

Test Button Green LED Status
Mains on / No fault
Slow flash Function for 2 minutes
Fast flash 3 hour duration test
1 Flash cycle Battery fault
2 Flash cycle Lamp fault
3 Flash cycle Duration test fault

Conducting additional manual tests of self-test fittings may significantly reduce battery life.

Diagram illustrating the self-test function and LED indications.

Testing & Commissioning for Emergency Luminaire

Luminaire Ref/Location

In Case of difficulty, contact the Installation Engineers:-

Full Recharge Time: 24 Hours

Duration: 3 Hours

Lamp Type: LED

Routine Test Record

Monthly Test Year 1 Year 2 Year 3 Year 4 Year 5
Signed Date Signed Date Signed Date Signed Date Signed Date
Functional
Functional
Functional
Functional
Functional
Functional
Functional
Functional
Functional
Functional
Functional
Three Hour

Technical Helpline +44 (0)1924 893380

www.belllighting.co.uk

British Electric Lamps Ltd
BELL House, Foxbridge Way, Normanton Industrial Estate
Normanton, West Yorkshire. WF6 1TN
UK T: +44 (0)1924 893380 F: +44 (0)1924 894320 E: sales@belllighting.co.uk

www.belllighting.co.uk

Models: 09040V2 3.3W Spectrum LED Emergency Bulkhead, 09040V2, 3.3W Spectrum LED Emergency Bulkhead, LED Emergency Bulkhead, Emergency Bulkhead, Bulkhead

PDF preview unavailable. Download the PDF instead.

INSTALLATIONINSTRUCTIONS90 Adobe PDF library 17.00

Related Documents

Preview Bell Lighting Emergency Pack Installation Instructions (10281V2)
Comprehensive installation, testing, and maintenance guide for the Bell Lighting 10281V2 Emergency Pack, including features, specifications, and troubleshooting.
Preview Bell Lighting Spectrum LED Emergency High Power IP65 Twin Spot (09159) - Technical Data
Detailed technical specifications and features for the Bell Lighting Spectrum LED Emergency High Power IP65 Twin Spot (Model 09159), including IP65 rating, LiFePO4 battery, Osram LED chip, and 5-year warranty.
Preview BELL Lighting Emergency Pack (11478) Installation Guide
Comprehensive installation instructions for the BELL Lighting Emergency Pack (11478), covering important safety information, user advice, auto-test functions, and emergency indications. Includes technical specifications and contact details.
Preview Aquaconnect LED Wattage Switchable CCT Bulkhead | BELL Lighting
BELL Lighting's Aquaconnect LED bulkhead offers switchable CCT and wattage, energy efficiency, and durable construction. Features include hinged gear tray, twist-lock diffuser, and optional emergency pack and sensor. Ideal for various applications.
Preview BELL Lighting Lumo LED CCT Asymmetric Wallpack - Specifications & Features
Discover the BELL Lighting Lumo LED CCT Asymmetric Wallpack. Features include asymmetric light distribution, 3/4/6000K CCT, 50W Metal Halide replacement, 50% energy saving, 50,000 hours lifespan, IP66 rating, and IK8 impact resistance. Available with photocell and emergency options.
Preview BELLlighting Sports Lighting Guide 2025: Solutions for Sports Venues
This comprehensive guide from BELLlighting details advanced LED lighting solutions for sports venues, covering football, rugby, tennis, hockey, and more. Discover benefits like energy efficiency, cost savings, and enhanced performance.
Preview Bell Lighting Arial Multi Backlit LED Panel - Technical Specifications and Features
Detailed information on the Bell Lighting Arial Multi Backlit LED Panel, including specifications, features, and available options for uniform light distribution and energy efficiency.
Preview BELL Lighting 08187V2 Firestay CCT LED Downlights Installation Guide
Comprehensive installation instructions for BELL Lighting's 08187V2 Firestay CCT LED Downlights, covering wiring, fitting, and features. Suitable for professional electricians.