Bell Lighting Emergency Bulkhead 09040V2
Installation Instructions
Specifications
- Operating environmental temp: 0 to +35°C
- Operating relative humidity: less than 90%
- Rated voltage: 220-240V 50/60Hz
- Wattage: 3.3W
- Conversion time: 1 second
- LED: SMT 2835 LED*8pcs
- Emergency duration: more than 180 minutes
- Battery installed or replaced: LiFePO4 3.2V 1500mah
- Recharge time: 24 hours
Important Information
- Bell recommends that luminaires are installed by a qualified electrician ensuring the installation complies with current IEE wiring regulations BS7671:2018 & local building control.
- All tests should be carried out in accordance to EN 50172:2004.
- BELL will not accept responsibility for any claims arising from a poor installation.
- The light source of this luminaire is not replaceable: when the light source reaches end of life, the whole luminaire must be replaced.
Important User Advice
- Ensure that there is adequate free air ventilation around the fitting.
- Always switch off mains supply before installing.
Installation Instructions: Emergency Bulkhead (09040V2)
Read these instructions before installation and retain for future reference. This equipment should be installed by a competent electrician.
Installation:
- Connect mains supply wiring as follows: L (Live), N (Neutral).
Diagram showing wiring connections for Non-maintained and Maintained operation.
- Power line & battery wires should be connected securely, and all screws fixed.
- Switch on 220-240V AC supply and check if the green LED indicator illuminates to confirm charging of batteries.
- Allow a short period for part charging of the batteries and then isolate the mains supply to the fitting in order to check the correct operation of the fitting in emergency mode. In the first use, after a continuous charge for 24 hours, a mains failure should be simulated to ensure that the fitting works for its specified time (only at a safe & appropriate time). The fitting will be fully charged with 24 hours continuous charging.
Diagram illustrating the battery and wiring connections within the luminaire.
The instruction of the switch on PCB: 'ON' indicates standard mode, '1' indicates self-test mode. Please ensure that the switch position is set before installation.
Recommended Routine Test Procedure
The following tests are designed to ensure the continued protection of your premises and occupants. Because of the possibility of a failure of the normal lighting supply occurring shortly after a period of testing, all tests should, whenever possible, be undertaken at times of least risk, e.g. during daylight hours.
- ONCE A DAY
Visual inspection of battery charge LED. - ONCE A MONTH
Each unit should be energized from its battery for an adequate time to ensure, by simulation of a failure of the normal lighting supply, the emergency mode is functioning correctly. - ONCE EACH YEAR
All units should be placed into emergency mode and checked that the duration provided by the battery meets the specified time period.
This product may contain substances that can be hazardous to the environment if not disposed of properly. Electrical and electronic equipment should never be disposed of with general household waste but must be separated for its correct treatment and recovery. Where possible, recycle your packaging.
Self-Test Functionality
Self-Test fittings perform a self-commissioning test at first power on. After charging for 24 hours, a full duration test (3 hours) is performed. Initial function and duration tests are randomly generated. They are then performed in accordance with standard requirements (every 30 days for function tests and every 52 weeks for duration tests).
A single bi-colour indicator LED is fitted in all Self-Test products. This LED is clearly visible for manual inspection. It indicates the module status. The LED shows permanent green or flashing green when conditions are normal and flashing red if a fault condition is present.
Function Test
A function test is a 2 minutes test that simulates a mains failure and checks the operation of the emergency light source from the battery supply. The local indicator LED slow flashes green whilst the 2 minutes function test is in progress. If there is a failure during a function test, the local indicator LED changes to a flashing red.
Duration Test
A duration test simulates a mains failure. It also checks the operation of the emergency light source from the battery supply for the rated duration of the module. The local indicator LED fast flashes green whilst the duration test is in progress. If there is a failure during a duration test, the local indicator LED either changes to flashing red. The battery is required to be fully charged before a duration test can be started.
Test Button Functions
The test button of the unit has the following functions:
Test Button | Green LED | Status |
---|---|---|
Press for approx 1 Second | Off | Emergency mode for 1 second |
Press for approx 5 Seconds | Slow flash | Function for 30 seconds |
Press for approx 7 Seconds | Fast Flash | 3 Hour duration test |
Press for approx 10 Seconds | End the duration test |
Please refer to the following chart below for more complete description/fault indication:
Test Button | Green LED | Status |
---|---|---|
Mains on / No fault | ||
Slow flash | Function for 2 minutes | |
Fast flash | 3 hour duration test | |
1 Flash cycle | Battery fault | |
2 Flash cycle | Lamp fault | |
3 Flash cycle | Duration test fault |
Conducting additional manual tests of self-test fittings may significantly reduce battery life.
Diagram illustrating the self-test function and LED indications.
Testing & Commissioning for Emergency Luminaire
- Ensure the Load is connected.
- Connect the battery.
- Switch on the Unswitched Supply - Check the Charge LED illuminates.
- Switch on the Maintained Supply - Check the LED illuminates as normal.
- Switch off the Maintained Supply.
- Switch off the Unswitched Supply - Check the Charge LED extinguishes and the load LED illuminates at a reduced output.
- Enter the commissioning date on the Battery Pack. Switch on the Unswitched Supply.
Luminaire Ref/Location
In Case of difficulty, contact the Installation Engineers:-
Full Recharge Time: 24 Hours
Duration: 3 Hours
Lamp Type: LED
Routine Test Record
Monthly Test | Year 1 | Year 2 | Year 3 | Year 4 | Year 5 | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Signed | Date | Signed | Date | Signed | Date | Signed | Date | Signed | Date | ||
Functional | |||||||||||
Functional | |||||||||||
Functional | |||||||||||
Functional | |||||||||||
Functional | |||||||||||
Functional | |||||||||||
Functional | |||||||||||
Functional | |||||||||||
Functional | |||||||||||
Functional | |||||||||||
Functional | |||||||||||
Three Hour |