NEXYA COMMERCIAL DUCT [OS4/S5+IS5]
Monosplit ducted inverter for large rooms
Key Features
High Static Pressure: Duct indoor unit with static pressure up to 160 Pa.
Slim Design: The series is characterized by its compact design (210 mm height).
Automatic Airflow Control: The system automatically adapts to the connected ductwork.
Digital Display: External display on the indoor unit for optimal remote control signal reception (*Except for size 48T, which is equipped with the wired wall control B0969).
Characteristics
- Energy-efficient inverter technology with R32 refrigerant with low global warming potential.
- Optimal performance and high efficiency at low airflow and low noise levels.
- Automatic Airflow Adjustment: Innovative function for automatic airflow adjustment to adapt the system to the connected ducts.
- Reversible Air Return: The air inlet duct can be moved from the rear of the unit (standard configuration) to the bottom of the unit and replaced with a metal plate, making the product suitable for any installation situation.
- Fresh Air Inlet Connection: The indoor units of the commercial line are equipped with special air inlets for supplying outdoor or fresh air to the product.
- Condensate Lift Pump: The indoor units are equipped with a condensate lift pump.
- Remote ON-OFF: All units in the commercial line are equipped with terminals that allow remote control of the unit's on and off status via an external device.
- Alarm Contact: The commercial line units feature a contact for synchronizing the product's alarm status with an external device.
- Hydrophilic Aluminum Coating: Thanks to its excellent corrosion protection performance, it is also suitable for installation in coastal areas or particularly humid environments. Under the same environmental conditions, the new coating of the condensers guarantees a lifespan up to 7 times longer than conventional models.
Functions
- Cooling, Heating, Dehumidification, and Ventilation
- Auto, Sleep*, and Turbo* functions
- 24h Timer: For programming on and off times.
- Follow-Me Function: Precise temperature detection at the remote control's location.
- Gear Function*: 3 power options (50-75-100%) to optimize energy consumption.
*Functions not compatible with size 48T.
Technical Specifications
Feature | Nexya E Duct 18 [OS5+IS5] | Nexya E Duct 24 [OS5+IS5] | Nexya E Duct 36 [OS5+IS5] | Nexya E Duct 36T [OS5+IS5] |
---|---|---|---|---|
Indoor Unit Article Number | OS-SANDH18EI | OS-SANDH24E1 | OS-SANDH36EI | OS-SANDH36EI |
Indoor Unit EAN Code | 8021183119152 | 8021183119169 | 8021183119176 | 8021183119176 |
Outdoor Unit Article Number | OS-CANCH18EI | OS-CANCH24E1 | OS-CANCH36EI | OS-CANCHT36E1 |
Outdoor Unit EAN Code | 8021183119053 | 8021183119060 | 8021183119077 | 8021183119084 |
Cooling Capacity (min/nom/max) | 2.55/5.275/5.86 kW | 3.28/7.034/8.16 kW | 2.75/9.958/11.14 kW | 2.73/9.974/11.78 kW |
Heating Capacity (min/nom/max) | 2.20/5.569/6.15 kW | 2.81/7.62/8.49 kW | 2.78/11.723/12.78 kW | 2.78/11.245/12.84 kW |
Power Consumption Cooling (min/nom/max) | 0.71/1.53/2.15 kW | 0.75/2.178/2.96 kW | 0.9/3.041/4.15 kW | 0.89/3.04/4.2 kW |
Power Consumption Heating (min/nom/max) | 0.74/1.501/1.76 kW | 0.64/1.9/2.58 kW | 0.8/3.16/3.95 kW | 0.78/2.877/4 kW |
EER | 3.45 | 3.23 | 3.27 | 3.28 |
COP | 3.71 | 4.01 | 3.71 | 3.71 |
Energy Efficiency Class Cooling | A++ | A++ | A++ | A++ |
Energy Efficiency Class Heating (Average) | A+ | A+ | A+ | A+ |
SEER | 6.5 | 6.2 | 6.2 | 6.1 |
SCOP (Average) | 4 | 4 | 4 | 4 |
Sound Power Level Indoor Unit (LWA) | 58 dB(A) | 61 dB(A) | 61 dB(A) | 61 dB(A) |
Airflow Cooling (max/med/min) | 911-706-515 m³/h | 1229-1035-825 m³/h | 2100-1800-1500 m³/h | 2100-1800-1500 m³/h |
Nominal Fan Pressure | 25 Pa | 25 Pa | 37 Pa | 37 Pa |
Indoor Unit Dimensions (W x H x D) | 880x210x674 mm | 1100x249x774 mm | 1360x249x774 mm | 1360x249x774 mm |
Indoor Unit Weight | 24.4 kg | 32.3 kg | 40.5 kg | 40.5 kg |
Sound Power Level Outdoor Unit (LWA) | 65 dB(A) | 67 dB(A) | 70 dB(A) | 70 dB(A) |
Outdoor Unit Dimensions (W x H x D) | 805x554x330 mm | 890x673x342 mm | 946x810x410 mm | 946x810x410 mm |
Outdoor Unit Weight | 32.5 kg | 43.9 kg | 66.9 kg | 80.5 kg |
Liquid Line Diameter | 1/4" - 6.35 mm | 3/8" - 9.52 mm | 3/8" - 9.52 mm | 3/8" - 9.52 mm |
Suction Line Diameter | 1/2" - 12.7 mm | 5/8" - 15.9 mm | 5/8" - 15.9 mm | 5/8" - 15.9 mm |
Max Refrigerant Line Length | 30 m | 50 m | 75 m | 75 m |
Max Height Difference | 20 m | 25 m | 30 m | 30 m |
Refrigerant Type | R32 | R32 | R32 | R32 |
Refrigerant Charge | 1.15 kg | 1.5 kg | 2.4 kg | 2.4 kg |
Indoor Unit Power Supply | One Phase 220-240/1/50 | One Phase 220-240/1/50 | One Phase 220-240/1/50 | One Phase 220-240/1/50 |
Outdoor Unit Power Supply | One Phase 220-240/1/50 | One Phase 220-240/1/50 | One Phase 220-240/1/50 | Three Phase 380-415/3/50 |
Max Current | 13.5 A | 19 A | 22.5 A | 10 A |
Operating Limits Cooling (Indoor) | DB 32°C | DB 32°C | DB 32°C | DB 32°C |
Operating Limits Heating (Indoor) | DB 30°C | DB 30°C | DB 30°C | DB 30°C |
Operating Limits Cooling (Outdoor) | DB 16°C | DB 16°C | DB 16°C | DB 16°C |
Operating Limits Heating (Outdoor) | DB 24°C | DB 24°C | DB 24°C | DB 24°C |
Note: The specified data refers to conditions established in EN 14511, EN 14825, and Delegated Regulation (EU) 626/2011. Actual product energy consumption may vary under real usage conditions. Data is subject to change without prior notice.