Fujitsu Halcyon 18,000 BTU Single Zone Wall Mounted System
Submittal: 18LPAS1
Product Features
- Auto Changeover
- Weekly & 24 hr. Timer
- Auto Louver
- Minimum Heat Mode
- Auto Restart
- Economy Mode
- Energy Saving Program (ESP)
- Wireless Remote control
- Outdoor Unit Low Noise Schedule
Model Numbers
- Indoor Unit: ASUH18LPAS
- Outdoor Unit: AOUH18LPAS1
- System: 18LPAS1
Efficiencies
Metric | Value |
---|---|
SEER | 20 |
EER | 11 |
HSPF | 3.97 |
COP | 13.50 |
Capacities
Capacity Type | Rated | Min.-Max. | Unit |
---|---|---|---|
Cooling | 18,000 | 4,000-19,000 | BTU/h |
Heating | 18,000 | 2,800-24,000 | BTU/h |
Outdoor Temperature Operation Range
Condition | Temperature Range (°F/°C) |
---|---|
Cooling | 14 to 115 (-10 to 46) |
Heating | 5 to 75 (-15 to 24) |
Warranty Information
7 Year Compressor,
5 Year Parts
(out-of-the-box)
10 Year Compressor,
10 Year Parts
(when registered within 60 days of installation in a residence)
12 Year Compressor,
12 Year Parts
(when registered within 60 days of installation in a residence, and installed by a Fujitsu Elite contractor)
Lineset Requirements
Requirement | Size | Unit |
---|---|---|
Connection Method | Flare | |
Liquid Line Length | Ø 1/4 | in (mm) |
Gas Line Length | Ø 1/2 | in (mm) |
Pre-Charge Length | 49 | ft (m) |
Minimum Length | 16 | ft (m) |
Maximum Length | 66 | ft (m) |
Max. Height Difference | 49 | ft (m) |
Indoor Dimensions & Weight
Dimension | Value | Unit |
---|---|---|
Net (H x W x D) | 11 x 38-9/16 x 9-7/16 | in |
280 x 980 x 240 | mm | |
Gross (H x W x D) | 12-11/16 x 42-7/16 x 13-5/8 | in |
322 x 1,078 x 346 | mm | |
Net Weight | 29 | lb (kg) |
Gross Weight | 37 | lb (kg) |
Outdoor Dimensions & Weight
Dimension | Value | Unit |
---|---|---|
Net (H x W x D) | 24-7/8 x 31-7/16 x 11-7/16 | in |
632 x 799 x 290 | mm | |
Gross (H x W x D) | 27-1/4 x 37 x 14-3/4 | in |
692 x 940 x 375 | mm | |
Net Weight | 86 | lb (kg) |
Gross Weight | 95 | lb (kg) |
Fan Data
Fan Speed | Indoor Unit Airflow Rate (CFM / m³/h) | Outdoor Unit Airflow Rate (CFM / m³/h) | ||
---|---|---|---|---|
Cooling | Heating | Cooling | Heating | |
High | 530 (900) | 506 (860) | 1,348 (2,290) | 1,348 (2,290) |
Medium | 471 (800) | 406 (690) | ||
Low | 377 (640) | 330 (560) | ||
Quiet | 241 (410) | 247 (420) |
Sound Pressure
Sound Pressure Level | Indoor Unit (dB(A)) | Outdoor Unit (dB(A)) | ||
---|---|---|---|---|
Cooling | Heating | Cooling | Heating | |
High | 43 | 43 | 50 | 50 |
Medium | 39 | 39 | 44 | 42 |
Low | 34 | 34 | 37 | |
Quiet | 26 | 28 |
Electrical Specifications
Specification | Value | Unit |
---|---|---|
Voltage/Frequency/Phase | 208/230 V/10/60Hz | |
Voltage Range | 187-253V~60Hz | |
Rated Current | Cooling: 6.7, Heating: 5.9 | A |
Maximum Operating Current | Cooling: 9.9, Heating: 11.9 | A |
Starting Current | 14.7 | A |
MCA | 14.7 | |
Maximum Circuit Breaker | 15 | A |
Input Power | Cooling: 1.33 kW, Heating: 1.5 kW | kW |
Power Factor | Cooling: 97.3%, Heating: 98% | % |
Other
Feature | Details |
---|---|
Moisture Removal | 4.0 pints/h (1.9 L/h) |
Energy Star Qualified | Yes |
Drain Hose Material | PP+HDPE |
Refrigerant Type | R410A |
Refrigerant Charge | 2 lb 16 oz (1.350 kg) |
Oil Type | RB68 |
Operation Range (Cooling) | 64 to 90 °F (18 to 32 °C) |
Operation Range (Heating) | 80% RH or less (30 °C or less) |
Accessories
- Wired Remote Controller (Touch Panel) UTY-TFSXF1
- Simple Remote Control UTY-RNRUZ5
- Simple Remote Control (Hospitality) UTY-RSRY
- Dry Contact Wire Kit UTY-RHRY
- 3rd Party Thermostat Converter UTY-XWZXZ5
- Interface Kit UTY-TTRX
- WIFI Module UTY-TWRXZ2
Dimensions
Indoor Unit Dimensions (in/mm):
- Net (H x W x D): 11 x 38-9/16 x 9-7/16 (280 x 980 x 240)
- Gross (H x W x D): 12-11/16 x 42-7/16 x 13-5/8 (322 x 1,078 x 346)
Outdoor Unit Dimensions (in/mm):
- Net (H x W x D): 24-7/8 x 31-7/16 x 11-7/16 (632 x 799 x 290)
- Gross (H x W x D): 27-1/4 x 37 x 14-3/4 (692 x 940 x 375)
Wall Bracket Data:
Refer to diagrams for detailed wall bracket dimensions and pipe inlet sizes.
Diagram Description:
The diagram shows the top, front, side, bottom, and valve side views of the indoor unit. It includes dimensions for the unit's height, width, and depth, as well as the placement and size of mounting holes and the drain port. The top view specifically details the pitch of bolts for installation. The side views illustrate the airflow direction and the location of the valve part.
System Combination is Energy Star Qualified
This system combination is Energy Star qualified.
Availability: Apps available in Apple® App Store and Google® Play Store.
Certifications
- Indoor Unit ETL#: 91987
- Outdoor Unit ETL#: 91987