TOSOT Ductless Mini-Split Heat Pump Systems
Product Overview
This document provides detailed submittal data and extended performance ratings for various TOSOT ductless mini-split heat pump systems. These systems are designed for efficient and quiet operation, featuring high-efficiency DC inverter technology, wireless remote control, and Wi-Fi capability (sold separately).
Key general features across the product line include:
- Compact and Quiet Design
- High-Efficiency DC Inverter Technology
- Vertical Swing Louver (on select models)
- Wireless Remote with LCD Display
- Wi-Fi Ready (Optional, requires separate kit)
- Wired Controller Interface (XK-41, sold separately)
- Low Ambient Cooling down to 0°F (-18°C)
- Blue Fin Condenser Coil
- 5-year Limited Parts Warranty
- 7-year Limited Compressor Warranty
Model Specifications
The following tables detail the specifications for various TOSOT models:
TW09HQ2C2A (9,000 BTU/H, 115V)
Feature | Specification |
---|---|
Cooling Rated Capacity | 9,000 BTU/H |
Cooling Capacity Range | 2,764-10,918 BTU/H |
Power Input (Max) | 1,270 W |
SEER | 23.0 |
EER | 13.0 |
Heating at 47° F Rated Capacity | 9,900 BTU/H |
Heating Capacity Range | 2,081-13,989 BTU/H |
Power Input (Max) | 1,200 W |
HSPF | 10.5 |
COP | 3.1 |
Heating at 17° F Rated Capacity | 6,100 BTU/H |
Operating Range Cooling (Max/Min) | 115°F (46°C) / 0°F (-18°C) |
Operating Range Heating (Max/Min) | 75°F (24°C) / -4°F (-20°C) |
Gas Pipe Size (OD) | 3/8-in |
Liquid Pipe Size (OD) | 1/4-in |
Factory Charge | 42.3 oz |
Sound Pressure Level Cooling/Heating (Min/Max) | 26/43 db(A) |
Power Supply | 115 V, 1 Phase, 60 Hz |
TW12HQ2C2A (12,000 BTU/H, 115V)
Feature | Specification |
---|---|
Cooling Rated Capacity | 12,000 BTU/H |
Cooling Capacity Range | 3,514-14,569 BTU/H |
Power Input (Max) | 1,300 W |
SEER | 22.0 |
EER | 12.5 |
Heating at 47° F Rated Capacity | 12,200 BTU/H |
Heating Capacity Range | 2,764-16,582 BTU/H |
Power Input (Max) | 1,350 W |
HSPF | 11.0 |
COP | 3.6 |
Heating at 17° F Rated Capacity | 6,800 BTU/H |
Operating Range Cooling (Max/Min) | 115°F (46°C) / 0°F (-18°C) |
Operating Range Heating (Max/Min) | 75°F (24°C) / -4°F (-20°C) |
Gas Pipe Size (OD) | 1/4-in |
Liquid Pipe Size (OD) | 1/4-in |
Factory Charge | 47.6 oz |
Sound Pressure Level Cooling/Heating (Min/Max) | 29/45 db(A) |
Power Supply | 115 V, 1 Phase, 60 Hz |
TW18HQ2C2D (18,000 BTU/H, 208/230V)
Feature | Specification |
---|---|
Cooling Rated Capacity | 18,000 BTU/H |
Cooling Capacity Range | 6,800-20,000 BTU/H |
Power Input (Max) | 2,600 W |
SEER | 20.0 |
EER | 12.5 |
Heating at 47° F Rated Capacity | 19,800 BTU/H |
Heating Capacity Range | 7,340-23,500 BTU/H |
Power Input (Max) | 2,600 W |
HSPF | 11.0 |
COP | 4.7 |
Heating at 17° F Rated Capacity | 12,400 BTU/H |
Operating Range Cooling (Max/Min) | 115°F (46°C) / 0°F (-18°C) |
Operating Range Heating (Max/Min) | 75°F (24°C) / -4°F (-20°C) |
Gas Pipe Size (OD) | 5/8-in |
Liquid Pipe Size (OD) | 1/4-in |
Factory Charge | 56.4 oz |
Sound Pressure Level Cooling/Heating (Min/Max) | 39/47 db(A) |
Power Supply | 208/230 V, 1 Phase, 60 Hz |
TW24HQ2C2D (24,000 BTU/H, 208/230V)
Feature | Specification |
---|---|
Cooling Rated Capacity | 22,000 BTU/H |
Cooling Capacity Range | 6,824-27,296 BTU/H |
Power Input (Max) | 3,000 W |
SEER | 20.0 |
EER | 12.5 |
Heating at 47° F Rated Capacity | 23,000 BTU/H |
Heating Capacity Range | 6,824-30,708 BTU/H |
Power Input (Max) | 3,000 W |
HSPF | 10.0 |
COP | 3.4 |
Heating at 17° F Rated Capacity | 14,600 BTU/H |
Operating Range Cooling (Max/Min) | 115°F (46°C) / 0°F (-18°C) |
Operating Range Heating (Max/Min) | 75°F (24°C) / -4°F (-20°C) |
Gas Pipe Size (OD) | 5/8-in |
Liquid Pipe Size (OD) | 1/4-in |
Factory Charge | 77.6 oz |
Sound Pressure Level Cooling/Heating (Min/Max) | 36/48 db(A) |
Power Supply | 208/230 V, 1 Phase, 60 Hz |
TW30HQ2B4D (30,000 BTU/H, 208/230V)
Feature | Specification |
---|---|
Cooling Rated Capacity | 28,000 BTU/H |
Cooling Capacity Range | 7,404-35,997 BTU/H |
Power Input (Max) | 3,900 W |
SEER | 18.0 |
EER | 10.4 |
Heating at 47° F Rated Capacity | 28,400 BTU/H |
Heating Capacity Range | 9,997-32,994 BTU/H |
Power Input (Max) | 4,000 W |
HSPF | 9.0 |
COP | 3.0 |
Heating at 17° F Rated Capacity | 19,200 BTU/H |
Operating Range Cooling (Max/Min) | 115°F (46°C) / 0°F (-18°C) |
Operating Range Heating (Max/Min) | 75°F (24°C) / -4°F (-20°C) |
Gas Pipe Size (OD) | 5/8-in |
Liquid Pipe Size (OD) | 1/4-in |
Factory Charge | 84.7 oz |
Sound Pressure Level Cooling/Heating (Min/Max) | 37/51 db(A) |
Power Supply | 208/230 V, 1 Phase, 60 Hz |
TW36HQ2B4D (36,000 BTU/H, 208/230V)
Feature | Specification |
---|---|
Cooling Rated Capacity | 33,600 BTU/H |
Cooling Capacity Range | 7,404-35,997 BTU/H |
Power Input (Max) | 4,300 W |
SEER | 18.0 |
EER | 8.2 |
Heating at 47° F Rated Capacity | 34,600 BTU/H |
Heating Capacity Range | 14,979-35,997 BTU/H |
Power Input (Max) | 4,300 W |
HSPF | 9.0 |
COP | 2.7 |
Heating at 17° F Rated Capacity | 20,200 BTU/H |
Operating Range Cooling (Max/Min) | 115°F (46°C) / 0°F (-18°C) |
Operating Range Heating (Max/Min) | 75°F (24°C) / -4°F (-20°C) |
Gas Pipe Size (OD) | 5/8-in |
Liquid Pipe Size (OD) | 1/4-in |
Factory Charge | 91.7 oz |
Sound Pressure Level Cooling/Heating (Min/Max) | 37/54 db(A) |
Power Supply | 208/230 V, 1 Phase, 60 Hz |
Extended Ratings
Detailed cooling and heating performance ratings across various indoor and outdoor temperature conditions are provided in the following tables for each model. These tables include Total Capacity (TC) and Sensible Heat Capacity (SHC) in BTU/H.
(Note: Full extended ratings tables are extensive and are omitted here for brevity, but are available in the original document.)
Dimensional Specifications
Minimum spacing requirements for indoor and outdoor units are critical for optimal performance and airflow. These include clearances from walls, ceilings, and floors, as well as surrounding structures.
Indoor Unit Spacing Requirements:
- From Wall: 6 inches (152 mm)
- From Ceiling: 6 inches (152 mm)
- From Floor: 60 inches (1520 mm)
Outdoor Unit Spacing Requirements:
- From Any Structure (Sides): 20 inches (508 mm)
- From Any Structure (Front/Back): 12 inches (305 mm)
- Discharge: 78 inches (1980 mm)
- Inlet: 12 inches (305 mm)
Indoor Unit Dimensions:
(Note: Specific dimensions for each model vary and are detailed in the original document's diagrams and tables.)
Outdoor Unit Dimensions:
(Note: Specific dimensions for each model vary and are detailed in the original document's diagrams and tables.)
Notes on Installation:
- Recommended Interconnecting Cable Type: 14 AWG-4 Stranded Copper Conductors THHN 600V Wire.
- Power wiring cable size must comply with applicable national and local codes.
- Test conditions are based on AHRI 210/240.