R95C 8-Port Analog In to ModBus® Hub

Instruction Manual

Features

The R95C is a compact analog to ModBus® device converter that connects up to eight analog sources and outputs the values. It features a rugged over-molded design that meets IP65, IP67, and IP68 standards. The hub connects directly to a sensor or anywhere in-line for ease of use, providing a quick, easy, and economical way to integrate non-ModBus devices into a ModBus system.

Model: R95C-8UI-MQ

Function: 8-port voltage/current analog input converter

Control: ModBus®

Connectors: (8) Integral 4-pin M12 female quick-disconnect connectors and (1) Integral 5-pin M12 male quick-disconnect connector.

Overview

When an analog input value is received by the R95C-8UI-MQ hub, the numerical representational value is represented via ModBus registers.

Analog Ranges

ModBus Configuration

Analog In Port Type

ModBus Register Address Description I/O Range Comments Default Access Notes
40000 Port Definition 0..255 Voltage = 0, Current = 1 0b11111111 RW [P8 P7|P6|P5|P4|P3|P2|P1] Set to 255 for all ports to be current in. Set to 0 for all ports to be voltage in.

Device Port States

ModBus Register Address Description I/O Range Comments Default Access Notes
40001 Measurement Value - Analog In 1 0..65535 Voltage = mV, Current = μA - RO -
40002 Measurement Value - Analog In 2 0..65535 Voltage = mV, Current = μA - RO -
40003 Measurement Value - Analog In 3 0..65535 Voltage = mV, Current = μA - RO -
40004 Measurement Value - Analog In 4 0..65535 Voltage = mV, Current = μA - RO -
40005 Measurement Value - Analog In 5 0..65535 Voltage = mV, Current = μA - RO -
40006 Measurement Value - Analog In 6 0..65535 Voltage = mV, Current = μA - RO -
40007 Measurement Value - Analog In 7 0..65535 Voltage = mV, Current = μA - RO -
40008 Measurement Value - Analog In 8 0..65535 Voltage = mV, Current = μA - RO -

Analog Input Active States

ModBus Register Address Description I/O Range Comments Default Access Notes
40009 Analog Input Active States 0..255 Inactive = 0, Active = 1 - RO 0b[P8][P7][P6][P5][P4][P3][P2][P1], where Active for a [P#], signifies that the analog input LED is on, and that the values are between the minimum and maximum setpoints for that port, as defined in registers 40100 to 40139

Analog In - Range Setpoints

ModBus Register Address Description I/O Range Comments Default Access Notes
40100 Port 1 - Voltage Minimum LED setpoint value 0..10999 Must be less than the maximum setpoint. 0 mV RW -
40101 Port 1 - Voltage Maximum LED setpoint value 0..11000 Must be greater than the minimum setpoint. 10000 mV RW If the value > Max I/O Range, value = Max
40102 Port 1 - Voltage Hysteresis 0..500 mV 50mV RW -
40103 Port 1 - Current Minimum LED setpoint value 0..23999 Must be less than the maximum setpoint. 4000 μA RW -
40104 Port 1 - Current Maximum LED setpoint value 0..24000 Must be greater than the minimum setpoint. 20000 μA RW If the value > Max I/O Range, value = Max
40105 Port 1 - Current Hysteresis 0..500 μA 100 μA RW -
40106 Port 2 - Voltage Minimum LED setpoint value 0..10999 Must be less than the maximum setpoint. 0 mV RW -
40107 Port 2 - Voltage Maximum LED setpoint value 0..11000 Must be greater than the minimum setpoint. 10000 mV RW If the value > Max I/O Range, value = Max
40108 Port 2 - Voltage Hysteresis 0..500 mV 50mV RW -
40109 Port 2 - Current Minimum LED setpoint value 0..23999 Must be less than the maximum setpoint. 4000 μA RW -
40110 Port 2 - Current Maximum LED setpoint value 0..24000 Must be greater than the minimum setpoint. 20000 μA RW If the value > Max I/O Range, value = Max
40111 Port 2 - Current Hysteresis 0..500 μA 100 μA RW -
40112 Port 3 - Voltage Minimum LED setpoint value 0..10999 Must be less than the maximum setpoint. 0 mV RW -
40113 Port 3 - Voltage Maximum LED setpoint value 0..11000 Must be greater than the minimum setpoint. 10000 mV RW If the value > Max I/O Range, value = Max
40114 Port 3 - Voltage Hysteresis 0..500 mV 50mV RW -
40115 Port 3 - Current Minimum LED setpoint value 0..23999 Must be less than the maximum setpoint. 4000 μA RW -
40116 Port 3 - Current Maximum LED setpoint value 0..24000 Must be greater than the minimum setpoint. 20000 μA RW If the value > Max I/O Range, value = Max
40117 Port 3 - Current Hysteresis 0..500 μA 100 μA RW -
40118 Port 4 - Voltage Minimum LED setpoint value 0..10999 Must be less than the maximum setpoint. 0 mV RW -
40119 Port 4 - Voltage Maximum LED setpoint value 0..11000 Must be greater than the minimum setpoint. 10000 mV RW If the value > Max I/O Range, value = Max
40120 Port 4 - Voltage Hysteresis 0..500 mV 50mV RW -
40121 Port 4 - Current Minimum LED setpoint value 0..23999 Must be less than the maximum setpoint. 4000 μA RW -
40122 Port 4 - Current Maximum LED setpoint value 0..24000 Must be greater than the minimum setpoint. 20000 μA RW If the value > Max I/O Range, value = Max
40123 Port 4 - Current Hysteresis 0..500 μA 100 μA RW -
40124 Port 5 - Voltage Minimum LED setpoint value 0..10999 Must be less than the maximum setpoint. 0 mV RW -
40125 Port 5 - Voltage Maximum LED setpoint value 0..11000 Must be greater than the minimum setpoint. 10000 mV RW If the value > Max I/O Range, value = Max
40126 Port 5 - Voltage Hysteresis 0..500 mV 50mV RW -
40127 Port 5 - Current Minimum LED setpoint value 0..23999 Must be less than the maximum setpoint. 4000 μA RW -
40128 Port 5 - Current Maximum LED setpoint value 0..24000 Must be greater than the minimum setpoint. 20000 μA RW If the value > Max I/O Range, value = Max
40129 Port 5 - Current Hysteresis 0..500 μA 100 μA RW -
40130 Port 6 - Voltage Minimum LED setpoint value 0..10999 Must be less than the maximum setpoint. 0 mV RW -
40131 Port 6 - Voltage Maximum LED setpoint value 0..11000 Must be greater than the minimum setpoint. 10000 mV RW If the value > Max I/O Range, value = Max
40132 Port 6 - Voltage Hysteresis 0..500 mV 50mV RW -
40133 Port 6 - Current Minimum LED setpoint value 0..23999 Must be less than the maximum setpoint. 4000 μA RW -
40134 Port 6 - Current Maximum LED setpoint value 0..24000 Must be greater than the minimum setpoint. 20000 μA RW If the value > Max I/O Range, value = Max
40135 Port 6 - Current Hysteresis 0..500 μA 100 μA RW -
40136 Port 7 - Voltage Minimum LED setpoint value 0..10999 Must be less than the maximum setpoint. 0 mV RW -
40137 Port 7 - Voltage Maximum LED setpoint value 0..11000 Must be greater than the minimum setpoint. 10000 mV RW If the value > Max I/O Range, value = Max
40138 Port 7 - Voltage Hysteresis 0..500 mV 50mV RW -
40139 Port 7 - Current Minimum LED setpoint value 0..23999 Must be less than the maximum setpoint. 4000 μA RW -
40140 Port 7 - Current Maximum LED setpoint value 0..24000 Must be greater than the minimum setpoint. 20000 μA RW If the value > Max I/O Range, value = Max
40141 Port 7 - Current Hysteresis 0..500 μA 100 μA RW -
40142 Port 8 - Voltage Minimum LED setpoint value 0..10999 Must be less than the maximum setpoint. 0 mV RW -
40143 Port 8 - Voltage Maximum LED setpoint value 0..11000 Must be greater than the minimum setpoint. 10000 mV RW If the value > Max I/O Range, value = Max
40144 Port 8 - Voltage Hysteresis 0..500 mV 50mV RW -
40145 Port 8 - Current Minimum LED setpoint value 0..23999 Must be less than the maximum setpoint. 4000 μA RW -
40146 Port 8 - Current Maximum LED setpoint value 0..24000 Must be greater than the minimum setpoint. 20000 μA RW If the value > Max I/O Range, value = Max
40147 Port 8 - Current Hysteresis 0..500 μA 100 μA RW -

ModBus Configuration

ModBus Register Address Description I/O Range Comments Default Access Notes
40601 Baud Rate 0 = 9.6k
1 = 19.2k
2 = 38.4k
1 RW
40602 Parity 0 = None
1 = Odd
2 = Even
0 RW
40603 Address 1-257 - 1 RW
40604 Reserved None - - RW
40605 Restore Factory Configuration 0 = No Operation, 1 = Restore - 1 WO

Device Information

ModBus Register Address Description I/O Range Comments Default Access Notes
40606-40615 Banner Name 0..65535 Banner Engineering - RO (9 words/18 characters)
40616-40631 Product Name 0..65535 R95C-8UI-MQ - RO (16 words/32 characters)
40632 Item H 0..65535 12 - RO Banner Item Number
40633 Item L 0..65535 TBD split into two 16-bit registers 28040 RO Banner Item Number
40634 Serial Number H 0..65535 - - RO Serial Number is split into four 16-bit registers
40635 Serial Number 0..65535 - - RO -
40636 Serial Number 0..65535 - - RO -
40637 Serial Number L 0..65535 - - RO -
40644-40659 User Define Tag 0..65535 User writable space More Sensors. More Solutions. RW (16 words/32 characters)
40680 Discovery 0..1 0 = Disabled, 1 = Enabled - RW Flash all LEDs to find hub
40681 All-Time Run Time H 0..65535 - - RO Upper 16 of 32 bits
40682 All-Time Run Time L 0..65535 - - RO Lower 16 of 32 bits
40683 Resettable Run Time H 0..65535 - - RW Upper 16 of 32 bits
40684 Resettable Run Time L 0..65535 - - RW Lower 16 of 32 bits

Mechanical Installation

Install the R95C to allow access for functional checks, maintenance, and service or replacement. Do not install the R95C in such a way to allow for intentional defeat.

Fasteners must be of sufficient strength to guard against breakage. The use of permanent fasteners or locking hardware is recommended to prevent the loosening or displacement of the device. The mounting hole (4.5 mm) in the R95C accepts M4 (#8) hardware.

See the figure below to help in determining the minimum screw length.

CAUTION: Do not overtighten the R95C's mounting screw during installation. Overtightening can affect the performance of the R95C.

Wiring

Port 1-Port 8 - Female

Pin Signal Description
1 12 V DC to 30 V DC
2 Analog In
3 Ground
4 Not Used

Male

Pin Signal Description
1 12 V DC to 30 V DC
2 RS485/D1/B/+
3 Ground
4 RS485/D0/A/-
5 Banner 1-wire

Status Indicators

The R95C 8-Port Analog In to ModBus® Hub has matching amber LED indicators on both sides for each analog in port to allow for installation needs and still provide adequate indication visibility. There is also an additional amber LED indicator on both sides of the converter, which is specific to the ModBus communication.

Power Indicator Green LED

Indication Status
Off Power off
Solid Green Power on

Modbus Communication Amber LED

Indication Status
Off Modbus communications are not present
Flashing Amber (4 Hz) Modbus communications are active
Solid Amber for 2 Seconds, Then to Off Modbus communications are lost after connection
Solid Amber for 2 Seconds, Then to Flashing Amber (4 Hz) Modbus communications momentarily lost, but then communication was reestablished

Analog In Amber LED

Indication Status
Off Analog current value is less than setpoint SP1 OR analog value is greater than setpoint SP2
Solid Amber Analog current value is between setpoint SP1 AND setpoint SP2

Specifications

Supply Voltage

12 V DC to 30 V DC at 400 mA maximum

Power Pass-Through Current

500 mA per port maximum

Analog Input Impedance

Supply Protection Circuitry

Protected against reverse polarity and transient voltages

Leakage Current Immunity

400 μA

Indicators

Connections

Construction

Vibration and Mechanical Shock

Certifications

Product Identification

SNAP SIGNAL

Environmental Rating

IP65, IP67, IP68, UL Type 1

Operating Conditions

Storage Temperature

-40 °C to +80 °C (-40 °F to +176 °F)

Required Overcurrent Protection

WARNING: Electrical connections must be made by qualified personnel in accordance with local and national electrical codes and regulations.

Overcurrent protection is required to be provided by end product application per the supplied table. Overcurrent protection may be provided with external fusing or via Current Limiting, Class 2 Power Supply. Supply wiring leads < 24 AWG shall not be spliced.

For additional product support, go to www.bannerengineering.com.

Supply Wiring (AWG) Required Overcurrent Protection (A) Supply Wiring (AWG) Required Overcurrent Protection (A)
20 5.0 26 1.0
22 3.0 28 0.8
24 1.0 30 0.5

FCC Part 15 Class B

This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

Industry Canada ICES-003(B)

This device complies with CAN ICES-3 (B)/NMB-3(B). Operation is subject to the following two conditions: 1) This device may not cause harmful interference; and 2) This device must accept any interference received, including interference that may cause undesired operation.

Cet appareil est conforme à la norme NMB-3(B). Le fonctionnement est soumis aux deux conditions suivantes: (1) ce dispositif ne peut pas occasionner d'interférences, et (2) il doit tolérer toute interférence, y compris celles susceptibles de provoquer un fonctionnement non souhaité du dispositif.

Dimensions

All measurements are listed in millimeters [inches], unless noted otherwise.

Diagram Description: Top, front, and side views of the R95C hub showing dimensions. The main body is rectangular with eight M12 connectors on the sides and two mounting holes on the top. Key dimensions include 81.1 mm [3.19 in], 50.0 mm [1.97 in], 95.0 mm [3.74 in], 116.7 mm [4.6 in], and 17.0 mm [0.67 in].

Accessories

Cordsets

4-Pin Threaded M12 Cordsets-Double Ended
Model Length Style Dimensions Pinout
MQDEC-401SS 0.31 m (1 ft) Female

44 Typ.
[1.73"]

Ø 14.5 [0.57"]

1 - Brown
2 - White
3 - Blue
4 - Black

MQDEC-403SS 0.91 m (2.99 ft)
MQDEC-406SS 1.83 m (6 ft)

40 Typ.
[1.58"]

Ø 14.5 [0.57"]

1

2

3

4

MQDEC-412SS 3.66 m (12 ft)
MQDEC-420SS 6.10 m (20 ft)
MQDEC-430SS 9.14 m (30.2 ft) M12 x 1 Male Straight/Female Straight
MQDEC-450SS 15.2 m (49.9 ft) M12 x 1 Male

Brackets

Description
SMBR90S Stainless steel bracket
4x M4-07 pemnuts (B)
Includes 2x M4 stainless steel hex head screws and flat washers
Hole center spacing: A = 40, B = 20
Hole size: A = Ø 5

Diagram Description: A stainless steel bracket with dimensions and mounting hole details.

SMBR95RA Stainless steel right-angle bracket
M4 x 0.7 mm #316SS screws (qty 2)

Diagram Description: A stainless steel right-angle bracket with mounting hole details.

Banner Engineering Corp Limited Warranty

Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.

THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.

This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.

Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to: www.bannerengineering.com.

For patent information, see www.bannerengineering.com/patents.

Models: R95C-8UI-MQ, R95C-8UI-MQ 8 Port Analog In To ModBus Hub, 8 Port Analog In To ModBus Hub, Analog In To ModBus Hub, ModBus Hub, Hub

File Info : application/pdf, 8 Pages, 1.97MB

PDF preview unavailable. Download the PDF instead.

233568

References

Related Documents

Preview R95C 8-Port Discrete Bimodal to Modbus Hub Quick Start Guide | Banner Engineering
Quick start guide for the Banner Engineering R95C 8-Port Discrete Bimodal to Modbus Hub. Learn about installation, specifications, status indicators, and compliance.
Preview Sure Cross DXM150-S2 Wireless Modbus Slave Datasheet
Datasheet for the Banner Sure Cross DXM150-S2 Wireless Modbus Slave, detailing its features, specifications, connectivity, and accessories for industrial wireless communication.
Preview DXMR90-X1 Series Controller Instruction Manual
Comprehensive guide for the Banner DXMR90-X1 Series Controller, covering setup, configuration, protocols (Modbus, EtherNet/IP, PROFINET), and IIoT applications. Includes software details and hardware specifications.
Preview Sure Cross DXM100-Bx and DXM1000-Bx Wireless Controllers Instruction Manual
This instruction manual provides comprehensive guidance for Banner Engineering's Sure Cross DXM100-Bx and DXM1000-Bx Wireless Controllers. It covers system overviews, hardware configurations, setup procedures, automation protocols, and detailed instructions for operation and maintenance, enabling users to leverage these devices for Industrial Internet of Things (IIoT) applications.
Preview Q90R R-GAGE® Radar Sensor Instruction Manual | Banner Engineering
Comprehensive instruction manual for the Banner Q90R R-GAGE® Radar Sensor, covering product description, installation, configuration, specifications, and product support. Learn how to set up and use this industrial radar sensor.
Preview Banner DXM Firmware Release Notes
Software release notes detailing firmware updates for Banner DXM controllers, including new features, enhancements, and bug fixes for various versions.
Preview Banner K100 Programmable Display Beacon: Features, Specifications, and Accessories
Discover the Banner K100 Programmable Display Beacon, a rugged industrial indicator offering 360-degree visibility with an alphanumeric display and customizable colors. Learn about its specifications, connectivity options including IO-Link and Modbus, and compatible accessories for industrial automation.
Preview Sure Cross® MultiHop Radios Instruction Manual
Comprehensive instruction manual for Banner Engineering's Sure Cross® MultiHop Radios, detailing setup, configuration, network modes (Modbus, Transparent), installation, and troubleshooting for industrial wireless communication systems.