R95C 8-Port Analog In to ModBus® Hub
Instruction Manual
Features
The R95C is a compact analog to ModBus® device converter that connects up to eight analog sources and outputs the values. It features a rugged over-molded design that meets IP65, IP67, and IP68 standards. The hub connects directly to a sensor or anywhere in-line for ease of use, providing a quick, easy, and economical way to integrate non-ModBus devices into a ModBus system.
Model: R95C-8UI-MQ
Function: 8-port voltage/current analog input converter
Control: ModBus®
Connectors: (8) Integral 4-pin M12 female quick-disconnect connectors and (1) Integral 5-pin M12 male quick-disconnect connector.
Overview
When an analog input value is received by the R95C-8UI-MQ hub, the numerical representational value is represented via ModBus registers.
Analog Ranges
- Voltage: 0 mV to 11,000 mV
- Current: 0 μA to 24,000 μA
ModBus Configuration
Analog In Port Type
ModBus Register Address | Description | I/O Range | Comments | Default | Access | Notes |
---|---|---|---|---|---|---|
40000 | Port Definition | 0..255 | Voltage = 0, Current = 1 | 0b11111111 | RW | [P8 P7|P6|P5|P4|P3|P2|P1] Set to 255 for all ports to be current in. Set to 0 for all ports to be voltage in. |
Device Port States
ModBus Register Address | Description | I/O Range | Comments | Default | Access | Notes |
---|---|---|---|---|---|---|
40001 | Measurement Value - Analog In 1 | 0..65535 | Voltage = mV, Current = μA | - | RO | - |
40002 | Measurement Value - Analog In 2 | 0..65535 | Voltage = mV, Current = μA | - | RO | - |
40003 | Measurement Value - Analog In 3 | 0..65535 | Voltage = mV, Current = μA | - | RO | - |
40004 | Measurement Value - Analog In 4 | 0..65535 | Voltage = mV, Current = μA | - | RO | - |
40005 | Measurement Value - Analog In 5 | 0..65535 | Voltage = mV, Current = μA | - | RO | - |
40006 | Measurement Value - Analog In 6 | 0..65535 | Voltage = mV, Current = μA | - | RO | - |
40007 | Measurement Value - Analog In 7 | 0..65535 | Voltage = mV, Current = μA | - | RO | - |
40008 | Measurement Value - Analog In 8 | 0..65535 | Voltage = mV, Current = μA | - | RO | - |
Analog Input Active States
ModBus Register Address | Description | I/O Range | Comments | Default | Access | Notes |
---|---|---|---|---|---|---|
40009 | Analog Input Active States | 0..255 | Inactive = 0, Active = 1 | - | RO | 0b[P8][P7][P6][P5][P4][P3][P2][P1], where Active for a [P#], signifies that the analog input LED is on, and that the values are between the minimum and maximum setpoints for that port, as defined in registers 40100 to 40139 |
Analog In - Range Setpoints
ModBus Register Address | Description | I/O Range | Comments | Default | Access | Notes |
---|---|---|---|---|---|---|
40100 | Port 1 - Voltage Minimum LED setpoint value | 0..10999 | Must be less than the maximum setpoint. | 0 mV | RW | - |
40101 | Port 1 - Voltage Maximum LED setpoint value | 0..11000 | Must be greater than the minimum setpoint. | 10000 mV | RW | If the value > Max I/O Range, value = Max |
40102 | Port 1 - Voltage Hysteresis | 0..500 | mV | 50mV | RW | - |
40103 | Port 1 - Current Minimum LED setpoint value | 0..23999 | Must be less than the maximum setpoint. | 4000 μA | RW | - |
40104 | Port 1 - Current Maximum LED setpoint value | 0..24000 | Must be greater than the minimum setpoint. | 20000 μA | RW | If the value > Max I/O Range, value = Max |
40105 | Port 1 - Current Hysteresis | 0..500 | μA | 100 μA | RW | - |
40106 | Port 2 - Voltage Minimum LED setpoint value | 0..10999 | Must be less than the maximum setpoint. | 0 mV | RW | - |
40107 | Port 2 - Voltage Maximum LED setpoint value | 0..11000 | Must be greater than the minimum setpoint. | 10000 mV | RW | If the value > Max I/O Range, value = Max |
40108 | Port 2 - Voltage Hysteresis | 0..500 | mV | 50mV | RW | - |
40109 | Port 2 - Current Minimum LED setpoint value | 0..23999 | Must be less than the maximum setpoint. | 4000 μA | RW | - |
40110 | Port 2 - Current Maximum LED setpoint value | 0..24000 | Must be greater than the minimum setpoint. | 20000 μA | RW | If the value > Max I/O Range, value = Max |
40111 | Port 2 - Current Hysteresis | 0..500 | μA | 100 μA | RW | - |
40112 | Port 3 - Voltage Minimum LED setpoint value | 0..10999 | Must be less than the maximum setpoint. | 0 mV | RW | - |
40113 | Port 3 - Voltage Maximum LED setpoint value | 0..11000 | Must be greater than the minimum setpoint. | 10000 mV | RW | If the value > Max I/O Range, value = Max |
40114 | Port 3 - Voltage Hysteresis | 0..500 | mV | 50mV | RW | - |
40115 | Port 3 - Current Minimum LED setpoint value | 0..23999 | Must be less than the maximum setpoint. | 4000 μA | RW | - |
40116 | Port 3 - Current Maximum LED setpoint value | 0..24000 | Must be greater than the minimum setpoint. | 20000 μA | RW | If the value > Max I/O Range, value = Max |
40117 | Port 3 - Current Hysteresis | 0..500 | μA | 100 μA | RW | - |
40118 | Port 4 - Voltage Minimum LED setpoint value | 0..10999 | Must be less than the maximum setpoint. | 0 mV | RW | - |
40119 | Port 4 - Voltage Maximum LED setpoint value | 0..11000 | Must be greater than the minimum setpoint. | 10000 mV | RW | If the value > Max I/O Range, value = Max |
40120 | Port 4 - Voltage Hysteresis | 0..500 | mV | 50mV | RW | - |
40121 | Port 4 - Current Minimum LED setpoint value | 0..23999 | Must be less than the maximum setpoint. | 4000 μA | RW | - |
40122 | Port 4 - Current Maximum LED setpoint value | 0..24000 | Must be greater than the minimum setpoint. | 20000 μA | RW | If the value > Max I/O Range, value = Max |
40123 | Port 4 - Current Hysteresis | 0..500 | μA | 100 μA | RW | - |
40124 | Port 5 - Voltage Minimum LED setpoint value | 0..10999 | Must be less than the maximum setpoint. | 0 mV | RW | - |
40125 | Port 5 - Voltage Maximum LED setpoint value | 0..11000 | Must be greater than the minimum setpoint. | 10000 mV | RW | If the value > Max I/O Range, value = Max |
40126 | Port 5 - Voltage Hysteresis | 0..500 | mV | 50mV | RW | - |
40127 | Port 5 - Current Minimum LED setpoint value | 0..23999 | Must be less than the maximum setpoint. | 4000 μA | RW | - |
40128 | Port 5 - Current Maximum LED setpoint value | 0..24000 | Must be greater than the minimum setpoint. | 20000 μA | RW | If the value > Max I/O Range, value = Max |
40129 | Port 5 - Current Hysteresis | 0..500 | μA | 100 μA | RW | - |
40130 | Port 6 - Voltage Minimum LED setpoint value | 0..10999 | Must be less than the maximum setpoint. | 0 mV | RW | - |
40131 | Port 6 - Voltage Maximum LED setpoint value | 0..11000 | Must be greater than the minimum setpoint. | 10000 mV | RW | If the value > Max I/O Range, value = Max |
40132 | Port 6 - Voltage Hysteresis | 0..500 | mV | 50mV | RW | - |
40133 | Port 6 - Current Minimum LED setpoint value | 0..23999 | Must be less than the maximum setpoint. | 4000 μA | RW | - |
40134 | Port 6 - Current Maximum LED setpoint value | 0..24000 | Must be greater than the minimum setpoint. | 20000 μA | RW | If the value > Max I/O Range, value = Max |
40135 | Port 6 - Current Hysteresis | 0..500 | μA | 100 μA | RW | - |
40136 | Port 7 - Voltage Minimum LED setpoint value | 0..10999 | Must be less than the maximum setpoint. | 0 mV | RW | - |
40137 | Port 7 - Voltage Maximum LED setpoint value | 0..11000 | Must be greater than the minimum setpoint. | 10000 mV | RW | If the value > Max I/O Range, value = Max |
40138 | Port 7 - Voltage Hysteresis | 0..500 | mV | 50mV | RW | - |
40139 | Port 7 - Current Minimum LED setpoint value | 0..23999 | Must be less than the maximum setpoint. | 4000 μA | RW | - |
40140 | Port 7 - Current Maximum LED setpoint value | 0..24000 | Must be greater than the minimum setpoint. | 20000 μA | RW | If the value > Max I/O Range, value = Max |
40141 | Port 7 - Current Hysteresis | 0..500 | μA | 100 μA | RW | - |
40142 | Port 8 - Voltage Minimum LED setpoint value | 0..10999 | Must be less than the maximum setpoint. | 0 mV | RW | - |
40143 | Port 8 - Voltage Maximum LED setpoint value | 0..11000 | Must be greater than the minimum setpoint. | 10000 mV | RW | If the value > Max I/O Range, value = Max |
40144 | Port 8 - Voltage Hysteresis | 0..500 | mV | 50mV | RW | - |
40145 | Port 8 - Current Minimum LED setpoint value | 0..23999 | Must be less than the maximum setpoint. | 4000 μA | RW | - |
40146 | Port 8 - Current Maximum LED setpoint value | 0..24000 | Must be greater than the minimum setpoint. | 20000 μA | RW | If the value > Max I/O Range, value = Max |
40147 | Port 8 - Current Hysteresis | 0..500 | μA | 100 μA | RW | - |
ModBus Configuration
ModBus Register Address | Description | I/O Range | Comments | Default | Access | Notes |
---|---|---|---|---|---|---|
40601 | Baud Rate | 0 = 9.6k 1 = 19.2k 2 = 38.4k |
1 | RW | ||
40602 | Parity | 0 = None 1 = Odd 2 = Even |
0 | RW | ||
40603 | Address | 1-257 | - | 1 | RW | |
40604 | Reserved | None | - | - | RW | |
40605 | Restore Factory Configuration | 0 = No Operation, 1 = Restore | - | 1 | WO |
Device Information
ModBus Register Address | Description | I/O Range | Comments | Default | Access | Notes |
---|---|---|---|---|---|---|
40606-40615 | Banner Name | 0..65535 | Banner Engineering | - | RO | (9 words/18 characters) |
40616-40631 | Product Name | 0..65535 | R95C-8UI-MQ | - | RO | (16 words/32 characters) |
40632 | Item H | 0..65535 | 12 | - | RO | Banner Item Number |
40633 | Item L | 0..65535 | TBD split into two 16-bit registers | 28040 | RO | Banner Item Number |
40634 | Serial Number H | 0..65535 | - | - | RO | Serial Number is split into four 16-bit registers |
40635 | Serial Number | 0..65535 | - | - | RO | - |
40636 | Serial Number | 0..65535 | - | - | RO | - |
40637 | Serial Number L | 0..65535 | - | - | RO | - |
40644-40659 | User Define Tag | 0..65535 | User writable space | More Sensors. More Solutions. | RW | (16 words/32 characters) |
40680 | Discovery | 0..1 | 0 = Disabled, 1 = Enabled | - | RW | Flash all LEDs to find hub |
40681 | All-Time Run Time H | 0..65535 | - | - | RO | Upper 16 of 32 bits |
40682 | All-Time Run Time L | 0..65535 | - | - | RO | Lower 16 of 32 bits |
40683 | Resettable Run Time H | 0..65535 | - | - | RW | Upper 16 of 32 bits |
40684 | Resettable Run Time L | 0..65535 | - | - | RW | Lower 16 of 32 bits |
Mechanical Installation
Install the R95C to allow access for functional checks, maintenance, and service or replacement. Do not install the R95C in such a way to allow for intentional defeat.
Fasteners must be of sufficient strength to guard against breakage. The use of permanent fasteners or locking hardware is recommended to prevent the loosening or displacement of the device. The mounting hole (4.5 mm) in the R95C accepts M4 (#8) hardware.
See the figure below to help in determining the minimum screw length.
CAUTION: Do not overtighten the R95C's mounting screw during installation. Overtightening can affect the performance of the R95C.
Wiring
Port 1-Port 8 - Female
Pin | Signal Description |
---|---|
1 | 12 V DC to 30 V DC |
2 | Analog In |
3 | Ground |
4 | Not Used |
Male
Pin | Signal Description |
---|---|
1 | 12 V DC to 30 V DC |
2 | RS485/D1/B/+ |
3 | Ground |
4 | RS485/D0/A/- |
5 | Banner 1-wire |
Status Indicators
The R95C 8-Port Analog In to ModBus® Hub has matching amber LED indicators on both sides for each analog in port to allow for installation needs and still provide adequate indication visibility. There is also an additional amber LED indicator on both sides of the converter, which is specific to the ModBus communication.
Power Indicator Green LED
Indication | Status |
---|---|
Off | Power off |
Solid Green | Power on |
Modbus Communication Amber LED
Indication | Status |
---|---|
Off | Modbus communications are not present |
Flashing Amber (4 Hz) | Modbus communications are active |
Solid Amber for 2 Seconds, Then to Off | Modbus communications are lost after connection |
Solid Amber for 2 Seconds, Then to Flashing Amber (4 Hz) | Modbus communications momentarily lost, but then communication was reestablished |
Analog In Amber LED
Indication | Status |
---|---|
Off | Analog current value is less than setpoint SP1 OR analog value is greater than setpoint SP2 |
Solid Amber | Analog current value is between setpoint SP1 AND setpoint SP2 |
Specifications
Supply Voltage
12 V DC to 30 V DC at 400 mA maximum
Power Pass-Through Current
500 mA per port maximum
Analog Input Impedance
- Current version: Approximately 250 ohms
- Voltage version: Approximately 14.3K ohms
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Leakage Current Immunity
400 μA
Indicators
- Green: Power
- Amber: ModBus communications
- Amber: Analog In status
Connections
- (8) Integral 4-pin M12 female quick-disconnect connector
- (1) Integral 5-pin M12 male quick-disconnect connector
Construction
- Coupling Material: Nickel-plated brass
- Connector Body: PVC translucent black
Vibration and Mechanical Shock
- Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55 Hz, 0.5 mm amplitude, 5 minutes sweep, 30 minutes dwell)
- Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine wave)
Certifications
- CE
- UK CA
- UL LISTED
Product Identification
SNAP SIGNAL
Environmental Rating
IP65, IP67, IP68, UL Type 1
Operating Conditions
- Temperature: -40 °C to +70 °C (-40 °F to +158 °F)
- 90% at +70 °C maximum relative humidity (non-condensing)
Storage Temperature
-40 °C to +80 °C (-40 °F to +176 °F)
Required Overcurrent Protection
WARNING: Electrical connections must be made by qualified personnel in accordance with local and national electrical codes and regulations.
Overcurrent protection is required to be provided by end product application per the supplied table. Overcurrent protection may be provided with external fusing or via Current Limiting, Class 2 Power Supply. Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to www.bannerengineering.com.
Supply Wiring (AWG) | Required Overcurrent Protection (A) | Supply Wiring (AWG) | Required Overcurrent Protection (A) |
---|---|---|---|
20 | 5.0 | 26 | 1.0 |
22 | 3.0 | 28 | 0.8 |
24 | 1.0 | 30 | 0.5 |
FCC Part 15 Class B
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
Industry Canada ICES-003(B)
This device complies with CAN ICES-3 (B)/NMB-3(B). Operation is subject to the following two conditions: 1) This device may not cause harmful interference; and 2) This device must accept any interference received, including interference that may cause undesired operation.
Cet appareil est conforme à la norme NMB-3(B). Le fonctionnement est soumis aux deux conditions suivantes: (1) ce dispositif ne peut pas occasionner d'interférences, et (2) il doit tolérer toute interférence, y compris celles susceptibles de provoquer un fonctionnement non souhaité du dispositif.
Dimensions
All measurements are listed in millimeters [inches], unless noted otherwise.
Diagram Description: Top, front, and side views of the R95C hub showing dimensions. The main body is rectangular with eight M12 connectors on the sides and two mounting holes on the top. Key dimensions include 81.1 mm [3.19 in], 50.0 mm [1.97 in], 95.0 mm [3.74 in], 116.7 mm [4.6 in], and 17.0 mm [0.67 in].
Accessories
Cordsets
4-Pin Threaded M12 Cordsets-Double Ended
Model | Length | Style | Dimensions | Pinout |
---|---|---|---|---|
MQDEC-401SS | 0.31 m (1 ft) | Female | 44 Typ. Ø 14.5 [0.57"] |
1 - Brown |
MQDEC-403SS | 0.91 m (2.99 ft) | |||
MQDEC-406SS | 1.83 m (6 ft) | 40 Typ. Ø 14.5 [0.57"] |
1 2 3 4 |
|
MQDEC-412SS | 3.66 m (12 ft) | |||
MQDEC-420SS | 6.10 m (20 ft) | |||
MQDEC-430SS | 9.14 m (30.2 ft) | M12 x 1 Male Straight/Female Straight | ||
MQDEC-450SS | 15.2 m (49.9 ft) | M12 x 1 Male |
Brackets
Description | ||
---|---|---|
SMBR90S | Stainless steel bracket 4x M4-07 pemnuts (B) Includes 2x M4 stainless steel hex head screws and flat washers Hole center spacing: A = 40, B = 20 Hole size: A = Ø 5 |
Diagram Description: A stainless steel bracket with dimensions and mounting hole details. |
SMBR95RA | Stainless steel right-angle bracket M4 x 0.7 mm #316SS screws (qty 2) |
Diagram Description: A stainless steel right-angle bracket with mounting hole details. |
Banner Engineering Corp Limited Warranty
Banner Engineering Corp. warrants its products to be free from defects in material and workmanship for one year following the date of shipment. Banner Engineering Corp. will repair or replace, free of charge, any product of its manufacture which, at the time it is returned to the factory, is found to have been defective during the warranty period. This warranty does not cover damage or liability for misuse, abuse, or the improper application or installation of the Banner product.
THIS LIMITED WARRANTY IS EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES WHETHER EXPRESS OR IMPLIED (INCLUDING, WITHOUT LIMITATION, ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE), AND WHETHER ARISING UNDER COURSE OF PERFORMANCE, COURSE OF DEALING OR TRADE USAGE.
This Warranty is exclusive and limited to repair or, at the discretion of Banner Engineering Corp., replacement. IN NO EVENT SHALL BANNER ENGINEERING CORP. BE LIABLE TO BUYER OR ANY OTHER PERSON OR ENTITY FOR ANY EXTRA COSTS, EXPENSES, LOSSES, LOSS OF PROFITS, OR ANY INCIDENTAL, CONSEQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT, WHETHER ARISING IN CONTRACT OR WARRANTY, STATUTE, TORT, STRICT LIABILITY, NEGLIGENCE, OR OTHERWISE.
Banner Engineering Corp. reserves the right to change, modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Banner Engineering Corp. Any misuse, abuse, or improper application or installation of this product or use of the product for personal protection applications when the product is identified as not intended for such purposes will void the product warranty. Any modifications to this product without prior express approval by Banner Engineering Corp will void the product warranties. All specifications published in this document are subject to change; Banner reserves the right to modify product specifications or update documentation at any time. Specifications and product information in English supersede that which is provided in any other language. For the most recent version of any documentation, refer to: www.bannerengineering.com.
For patent information, see www.bannerengineering.com/patents.
File Info : application/pdf, 8 Pages, 1.97MB
DocumentDocumentReferences
Related Documents
![]() |
R95C 8-Port Discrete Bimodal to Modbus Hub Quick Start Guide | Banner Engineering Quick start guide for the Banner Engineering R95C 8-Port Discrete Bimodal to Modbus Hub. Learn about installation, specifications, status indicators, and compliance. |
![]() |
Sure Cross DXM150-S2 Wireless Modbus Slave Datasheet Datasheet for the Banner Sure Cross DXM150-S2 Wireless Modbus Slave, detailing its features, specifications, connectivity, and accessories for industrial wireless communication. |
![]() |
DXMR90-X1 Series Controller Instruction Manual Comprehensive guide for the Banner DXMR90-X1 Series Controller, covering setup, configuration, protocols (Modbus, EtherNet/IP, PROFINET), and IIoT applications. Includes software details and hardware specifications. |
![]() |
Sure Cross DXM100-Bx and DXM1000-Bx Wireless Controllers Instruction Manual This instruction manual provides comprehensive guidance for Banner Engineering's Sure Cross DXM100-Bx and DXM1000-Bx Wireless Controllers. It covers system overviews, hardware configurations, setup procedures, automation protocols, and detailed instructions for operation and maintenance, enabling users to leverage these devices for Industrial Internet of Things (IIoT) applications. |
![]() |
Q90R R-GAGE® Radar Sensor Instruction Manual | Banner Engineering Comprehensive instruction manual for the Banner Q90R R-GAGE® Radar Sensor, covering product description, installation, configuration, specifications, and product support. Learn how to set up and use this industrial radar sensor. |
![]() |
Banner DXM Firmware Release Notes Software release notes detailing firmware updates for Banner DXM controllers, including new features, enhancements, and bug fixes for various versions. |
![]() |
Banner K100 Programmable Display Beacon: Features, Specifications, and Accessories Discover the Banner K100 Programmable Display Beacon, a rugged industrial indicator offering 360-degree visibility with an alphanumeric display and customizable colors. Learn about its specifications, connectivity options including IO-Link and Modbus, and compatible accessories for industrial automation. |
![]() |
Sure Cross® MultiHop Radios Instruction Manual Comprehensive instruction manual for Banner Engineering's Sure Cross® MultiHop Radios, detailing setup, configuration, network modes (Modbus, Transparent), installation, and troubleshooting for industrial wireless communication systems. |