Brink Ease 200 Enthalpy

Technical Data Sheet

1 Scope of delivery

Before starting the installation of the heat recovery appliance, check that it has been supplied in complete and undamaged condition.

The delivery size of the heat recovery appliance type Ease 200 Enthalpy consists of the following components:

  1. Heat recovery appliance.
  2. Wall mounting installation kit consisting of:
    • wall bracket.
    • 2 x rubber strip.
  3. Installation quick guide.
  4. Drilling and mounting template.

A diagram shows the heat recovery appliance with numbered components: 1. Heat recovery appliance, 2. Wall mounting bracket, 3. Rubber strips, 4. Drilling and mounting template.

2 Technical specifications

2.1 Technical information

ParameterValue
Ease 200 Enthalpy
Supply voltage [V/Hz]230V/50Hz
Dimensions (wxhxd) [mm]560 x 660 x 315
Duct diameter [mm]Ø 125
Weight [kg]20
Filter classISO Coarse 60%
Fan setting0, 1, 2, 3, max
Airflow m³/h (factory set values)50, 75, 100, 150, 200
Permissible resistance of duct system [Pa]3, 9, 7, 21, 13, 38, 28, 84, 50, 150
Rated power [W]8.5, 9.2, 11.0, 12.8, 17.0, 20.7, 39.6, 50.2, 77.5, 100.4
Rated current [A]0.12, 0.13, 0.13, 0.15, 0.17, 0.21, 0.35, 0.43, 0.64, 0.82
Cos φ0.310, 0.316, 0.372, 0.383, 0.425, 0.437, 0.496, 0.507, 0.528, 0.535
Max rated current [A]1.5
Permitted ambient conditionsBetween +2°C and +40°C. RH <90% non condensing
Storage and transport conditionsBetween -20°C and +45°C. RH <90% non condensing
Permitted air temperature through applianceBetween -20°C and +45°C

Sound power

Ventilation capacity [m³/h]Static pressure [Pa]80120160200
Sound power level Lw(A)255075100
Casing radiation [dB(A)]36.241.746.249.7
Duct "From dwelling" [dB(A)] *37.545.550.555.5
Duct "To dwelling" [dB(A)] *5361.566.570.5

* Duct sound level including end correction

In practice the value may differ by 1dB(A) through measurement tolerances.

A graph shows the relationship between flow rate and resistance for different fan settings, with capacity in Watts indicated in circles.

2.2 Dimensions

All indicated dimensions are in mm.

Diagrams illustrate the dimensions of the Ease 200 Enthalpy unit from the front, side, and top views, with key measurements provided.

2.3 Connections

The Ease 200 Enthalpy appliance is available in a left-hand and right-hand version.

Left-hand version: The “warm” connections supply air (1) and extract air (3) are on the left-hand side of the appliance.

Right-hand version: The “warm” connections supply air (1) and extract air (3) are on the right-hand side of the appliance.

Diagrams show the left-hand and right-hand versions of the appliance with numbered connections:

2.4 Overview internal parts

The appliance shown is a left-hand version; in a right-hand version all the internal parts are mirrored.

Diagrams illustrate the internal components of the appliance, with a corresponding list:

3 Service parts

3.1 Exploded view service articles

A diagram shows an exploded view of the service articles for the appliance.

3.2 Service parts list

No.Article descriptionArticle code
1Filter caps (2 pcs)532977
2Front cover533046
3Filter ISO Coarse 60% (2 pcs)*532994
4Fan holder (1 pcs)533049
5Bypass valve with motor complete533048
6Button PCB532979
7Main PCB**532978
8Mounting bracket533044
9Cable set533043
10Mains plug and cable 230V ***532756
11Outdoor air temperature sensor NTC1 10K531775
12Extract air temperature sensor NTC2 10K531775
13Fan (1 pcs) (Without fan housing)****533042
14Heat exchanger enthalpy532976

* It is also possible to order filters via www.brinkclimatesystems.nl

** When replacing the main PCB, always use the Service Tool to set the correct DIP-switch value and serial number. Without the correct DIP-switch value the unit will NOT function! See → Ordering service parts -> page 11 for information

*** The power cable is fitted with a circuit board connector. When replacing it, always order a replacement mains cable from Brink Climate Systems B.V..

To prevent dangerous situations, a damaged mains connection can only be replaced by a qualified expert.

**** Brink Climate Systems B.V. supplies fans from different suppliers under the same service article number. All ordered Ease 200 Enthalpy fans are compatible for the appliance.

3.3 Ordering service parts

Warning: Without the correct DIP-switch value set in the main PCB the appliance will NOT function!

When a replacement main PCB is ordered, the DIP-switch settings and serial number need to be programmed correctly into the PCB after installation.

Set the DIP-switch and serial number in the PCB with the Service Tool under the tab "Diagnostics".

The DIP-switch value can be found on the type plate (3 digits on the far right in the frame with the device name, the first 0 should not be entered).

The serial number can be found on the type plate as well.

The type plate is located on top of the appliance on the PCB cover.

A sample type plate is shown with fields for Type, Serial number, Year of construction, Maximum current consumption, Average power consumption, and Power supply. It also includes installation address information in multiple languages.

When ordering parts, in addition to the article code number (see exploded view), please state the heat recovery appliance type, the serial number, the year of production and the name of the part:

Example
Appliance typeEase 200 Enthalpy
Serial number433100250101
Year of production2024
PartFan
Article code533042
Quantity1

4 Declaration of Conformity

This declaration of conformity is issued under the sole responsibility of the manufacturer.

Manufacturer: Brink Climate Systems B.V.

Address: PO Box 11, NL-7950 AA, Staphorst, The Netherlands

Product: Ease 200 Enthalpy

The product described above complies with the following directives:

The product described above has been tested according to the following standards:

Staphorst, 18-11-2024

R.J.F. Maassen
Country Manager Heating and Ventilation etherlands

5 ERP values

Technical information sheet Ease 200 Enthalpy in accordance with Ecodesign (ErP), no. 1254/2014 (Annex IV)

Manufacturer:Brink Climate Systems B.V.
Model:Ease 200 Enthalpy
Climate zoneType of controlSEC Value in kWh/m²/aSEC ClassAnnual electricity consumption (AEC) in kWhAnnual heating saved (AHS) in kWh
Averagemanual-32,77B3714136
clock control-33,94B3394174
1x sensor (RH/CO2/VOC)-36,17A2804251
2 or more sensors (RH/CO2/VOC)-40,15A1834404
Coldmanual-66,95A+9088091
clock control-68,49A+8768166
1x sensor (RV/CO2/VOC)-71,45A+8178315
2 or more sensors (RH/CO2/VOC)-76,88A+7208614
Hotmanual-10,56E3261870
clock control-11,53E2941888
1x sensor (RH/CO2/VOC)-13,34E2351922
2 or more sensors (RH/CO2/VOC)-16,47E1381991

Type of ventilation unit: Balanced residential ventilation appliance with heat recovery

Fan: EC - fan with infinitely variable control

Type of heat exchanger: Recuperative plastic cross-counterflow heat exchanger

Thermal efficiency: 76%

Maximum flow rate: 200 m³/h

Maximum rated power: 152 W

Sound power level Lwa: 43,7 dB(A)

Reference flow rate: 140 m³/h

Reference pressure: 50 Pa

Specific Power Input (SEL): 0,26 Wh/m³

Control factor: 1.0 in combination with multiple position switch, 0.95 in combination with clock control, 0.85 in combination with 1 sensor, 0.65 in combination with 2 or more sensors

Leakage*: Internal: 1,40%, External: 0,90%

Position dirty filter indication: Permanently lit red LED on the appliance / on the multiple position switch (LED) / on the Brink Air Control or

Attention! For optimal energy efficiency and a proper operation, a regular filter inspection, cleaning or replacement is necessary.

Internet address for Assembly instructions: https://www.brinkclimatesystems.nl/support/downloads

Bypass: Yes, 100% Bypass

* Measurements executed by TZWL according to the EN 13141-7 standard

6 Recycling and disposal

Do not dispose of as household waste! ?

In accordance with the Waste Disposal Act, the following components must be disposed of or recycled in an environmentally compatible manner by means of appropriate collection points:

Environmentally compatible means separated by material groups to ensure the greatest possible recyclability of the basic materials with the minimum environmental impact.

  1. Dispose of packaging made of cardboard, recyclable plastics and synthetic filler materials in an environmentally compatible manner through appropriate recycling systems or a recycling center.
  2. Please observe the applicable national and local regulations.

PDF preview unavailable. Download the PDF instead.

ease-200-enthalpy-technical-data-sheet-gb-618129 AH Formatter V6.6 MR11 for Windows (x64) : 6.6.13.42545 (2020-02-03T11:23 09) Antenna House PDF Output Library 6.6.1548 (Windows (x64))

Related Documents

Preview Brink Ease 200 Technical Data Sheet
Comprehensive technical data sheet for the Brink Ease 200 ventilation unit, detailing specifications, dimensions, connections, service parts, and compliance information.
Preview Brink Flair 225 Enthalpy Technical Data Sheet
Technical data sheet for the Brink Flair 225 Enthalpy ventilation unit, including specifications, dimensions, appliance parts, service information, conformity declarations, ERP values, and recycling guidelines.
Preview Brink Flair 450/600 Technical Data Sheet | Heat Recovery Ventilation
Comprehensive technical data sheet for Brink Flair 450 and Flair 600 heat recovery ventilation appliances, detailing specifications, dimensions, service information, ERP values, and conformity declarations.
Preview Brink Flair 325 Technical Data Sheet and Specifications
Comprehensive technical data sheet for the Brink Flair 325 heat recovery ventilation appliance, covering specifications, connections, exploded views, service information, conformity, and ERP values.
Preview Installatievoorschriften Brink Renovent Excellent 300/400 (Plus)
Gedetailleerde installatiehandleiding voor de Brink Renovent Excellent 300/400 (Plus) ventilatie-unit met warmteterugwinning. Ontdek specificaties, installatieprocedures en onderhoud voor een gezond binnenklimaat.
Preview Brink Air Control Ventilation & Allure Installation Regulations and User Manual
Comprehensive installation regulations, user manual, and technical specifications for Brink Air Control Ventilation and Brink Air Control Allure clock thermostat systems by Brink Climate Systems B.V.
Preview Renovent Sky 150 Plus Installation Instructions
Comprehensive installation guide for the Brink Renovent Sky 150 Plus ventilation unit, detailing features, operation, and technical specifications for optimal setup and performance.
Preview Brink Renovent Sky 300 Plus Installation Instructions
Detailed installation guide for the Brink Renovent Sky 300 Plus heat recovery ventilation unit. Covers features, technical specifications, electrical connections, and setup for optimal indoor air quality and energy efficiency.