VICTOR 1U6KL Online UPS 6kVA User Manual
Version: 1.X
1. Important Safety Warning
1-1. Transportation and Storage
Please transport the UPS system only in the original package to protect against shock and impact. The UPS must be stored in a ventilated and dry room.
1-2. Preparation
Condensation may occur if the UPS system is moved directly from a cold to a warm environment. The UPS system must be absolutely dry before installation. Allow at least two hours for the UPS system to acclimate. Do not install the UPS system near water or in moist environments, or where it would be exposed to direct sunlight or nearby heaters. Do not block ventilation holes. Ensure enough space on each side for ventilation.
1-3. Installation
Do not connect appliances or devices that would overload the UPS (e.g., large motor-type equipment) to the UPS output sockets or terminals. Place cables so no one can step on or trip over them. The UPS must be installed in a location with good ventilation. Ensure enough space on each side for ventilation. The UPS has an earthed terminal; in the final installed system configuration, equipotential earth bonding to external UPS battery cabinets is required. Installation should only be performed by qualified personnel. An appropriate disconnect device for short-circuit backup protection and an integral emergency switching device should be provided in the building wiring installation. Connect the earth before connecting to the building wiring terminal. Installation and wiring must comply with local electrical laws and regulations.
1-4. Connection Warnings
- There is no standard backfeed protection inside; isolate the UPS before working according to this circuit. The isolation device must be able to carry the UPS input current.
- This UPS should be connected with a TN earthing system.
- The power supply for this unit must be single-phase rated according to the equipment nameplate and must be suitably grounded.
- Use of this equipment in life support applications where failure could reasonably be expected to cause failure of life support equipment or significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the presence of a flammable anesthetic mixture with air, oxygen, or nitrous oxide.
- Connect your UPS power module's grounding terminal to a grounding electrode conductor.
- The UPS is connected to a DC energy source (battery). The output terminals may be live when the UPS is not connected to an AC supply. Before working on this circuit, isolate the Uninterruptible Power System (UPS), then check for hazardous voltage between all terminals, including the protective earth. Risk of Voltage Back feed.
1-5. Operation
Do not disconnect the earth conductor cable on the UPS or building wiring terminals at any time, as this would cancel the protective earth of the UPS system and all connected loads. The UPS system features its own internal current source (batteries). Output sockets or terminal blocks may be electrically live even if the UPS system is not connected to the building wiring outlet. To fully disconnect the UPS system, first press the "OFF" button and then disconnect the mains. Ensure no liquid or foreign objects can enter the UPS system. The UPS can be operated by individuals with no previous experience.
2. Installation and Setup
2-1. Unpacking and Inspection
Inspect the unit before installation. Ensure nothing inside the package is damaged. Keep the original package in a safe place for future use.
The shipping package contains:
- Power Module UPS: 1x UPS unit, 1x Manual, 1x USB cable, 1x Ear bracket, 1x External battery cable A.
- EBC (LiPo) Battery pack: 1x Battery pack, 1x Manual, 1x Ear bracket, 1x External battery cable B, 1x Com cable.
If there is any damage or missing parts, notify the carrier and dealer immediately. Do not turn on the unit.
2-2. Front and Rear Panel Views
Power Module Front Panel:
- LCD Display
- Buttons
- COM port (to EBC), RJ45
- USB port
- WIFI signal reserved port
- Connector for bypass detection
- Slot for optional card
- EPO (Emergency Power Off)
Power Module Rear Panel:
- Terminals (input, battery, output)
- LED Display
- Circuit Breaker
- Grounding Screw
- External Battery Connectors
- COM ports
- Manual On/Off Button
2-3. Rack Installation
This UPS can be mounted in a 19" rack chassis. Before installing the UPS and EBC, install the rail kit into the cabinet. Follow these steps:
- Mount the ear kit to the unit.
- Install to cabinet and screw it securely.
2-4. UPS and EBC Setup
Remove the terminal block cover on the rear panel of the UPS. Connect wires according to the terminal block diagrams. Connect the earth wire first and disconnect it last.
Terminal Block Definition for Wiring:
Note 1: Ensure wires are tightly connected to terminals.
Note 2: Install an output breaker between the output terminal and the load. The breaker should have leakage current protective function if necessary.
Note 3: Wire harness needs to be mounted with the specified terminal options. Ensure suitable wire size.
Wire Size for Input, Output, and Battery Connection:
Connection | Wiring Spec (AWG / mm²) |
---|---|
Input | 10 / 5.3 |
Output | 10 / 5.3 |
Battery | 10 / 5.3 |
Ground | 10 / 5.3 |
Note 1: Use suitable wire or thicker for safety and efficiency.
Note 2: Wire colors should follow local electrical laws and regulations.
UPS Link to EBCs:
The UPS can link up to 5 EBC units in total. When multiple EBCs are paralleled, the first EBC linked to the UPS is the master, and others are slaves. Slave EBC information is sent to the master when needed. RS485 is used for communication, and CAN BUS is used between EBC #1 and EBC #N.
Warning: Ensure the UPS is not turned on before installation. The UPS should not be turned on during wiring connection.
Warning: There is a DC breaker on the EBC rear panel to disconnect the battery pack and the UPS. Switch off the battery breaker before installation.
Note: Set the battery pack breaker to "OFF" position before installing the battery pack.
Important Notes:
- Pay close attention to the rated battery voltage marked on the rear panel. If changing the number of battery packs, modify the setting simultaneously. Connecting with the wrong battery voltage may cause permanent damage. Ensure the battery pack voltage is correct.
- Pay close attention to the polarity marking on the external battery terminal block and ensure correct battery polarity is connected. Wrong connection may cause permanent damage.
- Ensure protective earth ground wiring is correct, checking current spec, color, position, connection, and conductance reliability.
- Ensure utility input & output wiring is correct, checking current spec, color, position, connection, and conductance reliability.
- Make sure the L/N terminals are correct and not reversed or short-circuited.
2-5. Turn on UPS and EBC
After UPS and EBC are linked properly, connect the UPS to the load and input power source. Follow these steps:
- Ensure all connections are ready.
- Switch the breaker on the EBC to the "ON" position.
- Press and hold the "On/Off switch" for 5 seconds and release. The EBC will start up and be ready for DC output after 10 seconds.
- Turn on the UPS. After 10 seconds, the UPS will operate normally.
2-6. Software Installation
For optimal computer system protection, install the UPS monitoring software to fully configure UPS shutdown and management.
3. Operations
3-1. Button Operation
Button | Function |
---|---|
ON/Mute Button |
|
OFF/Enter Button |
|
Select Button |
|
ON/Mute + Select Buttons | Switch to bypass mode: When main power is normal, press both buttons simultaneously for 5 seconds. Ineffective if input voltage is out of acceptable range. |
3-2. LCD Panel
The LCD panel displays various operational statuses:
- Remaining backup time: Indicated by a pie chart or numbers (H: hours, M: minute, S: second).
- Fault information: Indicates warnings and faults. Displays codes detailed in section 3-5.
- Mute operation: Indicates the UPS alarm is disabled.
- Output information: Displays output voltage and frequency (Vac, Hz).
- Load information: Indicates load level (0-25%, 26-50%, 51-75%, 76-100%). Indicates overload or short circuit.
- Mode operation information: Icons indicate connection to mains, battery operation, bypass circuit working, ECO mode enabled, Inverter circuit working, converter mode, and output status.
- Programmable outlets information: Indicates programmable management outlets are working.
- Battery information: Displays battery level (0-25%, 26-50%, 51-75%, 76-100%). Indicates battery fault or low battery level/voltage.
- Input & Battery voltage information: Displays input voltage, frequency, or battery voltage (Vac, Vdc, Hz).
3-3. Audible Alarm
Description | Buzzer Status | Muted |
---|---|---|
UPS status | Beeping once every 2 minutes | Yes |
Bypass mode | Beeping once every 4 seconds | Yes |
Battery mode | Beeping continuously | No |
Fault mode | Beeping twice every second | No |
Warning | Beeping once every second | No |
Overload | Beeping twice every second | No |
Low battery | Beeping continuously | Yes |
Battery unconnected | Beeping once every second | No |
Over charge | Beeping once every second | Yes |
EPO enable | Beeping once every second | Yes |
Fan failure/Over temperature | Beeping once every second | Yes |
Charger failure | Beeping once every second | Yes |
Overload 3 times in 30min | Beeping once every second | Yes |
EPO status | Beeping once every second | Yes |
Cover of maintain switch is open | Beeping once every second | Yes |
Fault Bus start failure | Beeping continuously | No |
Fault Bus over | Beeping continuously | No |
Fault Bus under | Beeping continuously | No |
Fault Bus unbalance | Beeping continuously | No |
Inverter soft start failure | Beeping continuously | No |
High Inverter voltage | Beeping continuously | No |
Low Inverter voltage | Beeping continuously | No |
Inverter output short circuited | Beeping continuously | No |
Battery SCR short circuited | Beeping continuously | No |
Over temperature | Beeping continuously | No |
Overload | Beeping twice every second | No |
3-4. UPS Operation
1. Turn on the UPS with utility power supply (in AC mode):
- Connect power supply. For long-run models, set the battery pack breaker to "ON". Set the input breaker to "ON". The fan runs, and the UPS supplies power via bypass. The UPS operates in Bypass mode. (Note: In Bypass mode, the load is not protected by the UPS. Turn on the UPS for protection.)
- Press and hold the "ON" button for 1 second; the buzzer beeps once.
- After a few seconds, the UPS enters AC mode. If utility power is abnormal, it switches to Battery mode without interruption. (Note: The UPS shuts down automatically when the battery runs low. It auto-restarts in AC mode when utility power is restored.)
2. Turn on the UPS without utility power supply (in Battery mode):
- Ensure the battery pack breaker is "ON" (for long-run models).
- Press and hold the "ON" button for 1 second; the buzzer beeps once.
- After a few seconds, the UPS turns on and enters Battery mode.
3. Connect devices to UPS:
- After the UPS is on, connect devices one by one. The total load level is displayed on the LCD.
- For inductive loads (e.g., printers), carefully calculate in-rush current to ensure it meets UPS capacity.
- If the UPS is overloaded, the buzzer beeps twice per second. Remove loads immediately. It is recommended to keep total loads below 80% of nominal capacity.
- If overload exceeds acceptable time in AC mode, the UPS transfers to Bypass mode. It returns to AC mode after overload removal. If overload occurs 3 times in 30 minutes, the UPS locks in Bypass mode. It can only transfer to Line mode via manual restart. If bypass is enabled, it powers via bypass; otherwise, it cuts off output directly.
4. Charge the batteries:
- After connecting to utility power, the charger charges batteries automatically (except in Battery mode or during self-test).
- Charge batteries for at least 10 hours before use for expected backup time.
- Ensure battery number settings match the actual connection.
- Charging current can be adjusted from 1A to 6A via LCD or software. Ensure it suits battery specifications.
5. Battery mode operation:
- In Battery mode, the buzzer beeps based on battery capacity. If capacity > 25%, it beeps every 4 seconds. If battery voltage drops to alarm level, it beeps quickly (every second) indicating low battery and imminent shutdown. Users can switch off non-critical loads to extend backup time. If no loads can be switched off, shut down all loads promptly to protect devices or save data.
- To mute the buzzer in Battery mode, press the "Mute" button.
- Backup time for long-run models depends on external battery capacity.
- Backup time can vary with ambient temperature and load type.
- When the default backup time (e.g., 16.5 hours) is reached, the UPS shuts down to protect the battery. This protection can be enabled/disabled via LCD settings.
6. Turn off the UPS with utility power supply in AC mode:
- Turn off the inverter by pressing "OFF" for at least 1 second; the buzzer beeps once. The UPS enters Bypass mode. (Note 1: If bypass is enabled, utility power is still supplied to output sockets/terminals. Note 2: In Bypass mode, there is a risk of power loss. To cut off output, switch off the input breaker. The LCD will go blank, and the UPS is off.)
7. Turn off the UPS without utility power supply in Battery mode:
- Turn off the UPS by pressing "OFF" for at least 1 second; the buzzer beeps once.
- The UPS cuts off power to the output, and the display panel goes blank.
8. Mute the buzzer:
- Press the "Mute" button for at least 1 second. Pressing again unmutes it.
- Some warning alarms cannot be muted until the error is fixed. Refer to section 3-3.
9. Operation in warning status:
- If the Fault LED flashes and the buzzer beeps once per second, there is an operational problem. Get the fault code from the LCD panel and check the troubleshooting table in Chapter 4.
- Some warning alarms cannot be muted until the error is fixed. Refer to section 3-3.
10. Operation in Fault mode:
- If the Fault LED illuminates and the buzzer beeps continuously, there is a fatal error. Get the fault code from the display panel and check the troubleshooting table in Chapter 4.
- Check loads, wiring, ventilation, utility, battery, etc., after a fault. Do not try to turn on the UPS again before solving problems. Contact the distributor or service personnel if problems persist.
- For emergencies, immediately disconnect utility, external battery, and output to avoid further risk.
11. Operation of changing battery numbers:
This operation is for professional or qualified technicians only.
- Turn off the UPS. If the load cannot be cut off, turn the maintenance switch to "BPS" position after removing the maintenance bypass switch cover.
- Switch off the input breaker and the battery breaker.
- Remove the cabinet cover and modify the jumpers (CN1) on the control board to set battery numbers according to the table below.
Battery Number | CN1 | |||||
---|---|---|---|---|---|---|
pin15 | Pin16 | Pin17 | Pin18 | Pin19 | Pin20 | |
16 | X | 1 | 0 | 0 | 0 | 0 |
17 | X | 0 | 1 | 0 | 0 | 0 |
18 | X | 0 | 0 | 1 | 0 | 0 |
19 | X | 0 | 0 | 0 | 1 | 0 |
20 | X | 0 | 0 | 0 | 0 | 1 |
Note: 1 = connect with jumper; 0 = no jumper; x = pins for other functions. |
5. Modify the battery pack for the setting number carefully. Replace the cover and switch on the battery breaker.
6. Switch on the input breaker; the UPS enters Bypass mode. If the UPS was in maintenance Bypass mode, turn the maintenance switch to "UPS" position and then turn on the UPS.
3-5. Abbreviation Meaning in LCD Display
Abbreviation | Display Content | Meaning |
---|---|---|
ENA | Enable | Enable |
DIS | Disable | Disable |
ATO | Auto | Auto |
BAT | Battery | Battery |
NCF | Normal mode (not CVCF mode) | Normal mode (not CVCF mode) |
CF | CVCF mode | CVCF mode |
SUB | Subtract | Subtract |
ADD | Add | Add |
ON | On | On |
OFF | Off | Off |
FBD | Not allowed | Not allowed |
OPN | Allow | Allow |
RES | Reserved | Reserved |
3-6. UPS Setting Parameter
There are three parameters to set up the UPS. Parameter 1 is for program alternatives. Parameters 2 and 3 are setting options or values for each program.
Parameter 1: Output Voltage Setting
Interface: Setting
Parameter 3: Output Voltage
Choose from:
- 208: Output voltage is 208Vac
- 220: Output voltage is 220Vac
- 230: Output voltage is 230Vac (Default)
- 240: Output voltage is 240Vac
Parameter 2: Frequency Converter Enable/Disable
Interface: Setting
Parameter 2: Output Frequency
Choose from:
- 50.0Hz: Output frequency is 50.0Hz.
- 60.0Hz: Output frequency is 60.0Hz.
- ATO: Output frequency is decided by the latest normal utility frequency. If input frequency is 46Hz-54Hz, output is 50.0Hz. If input frequency is 56Hz-64Hz, output is 60.0Hz. (Default)
Parameter 3: Frequency Mode
Set output frequency at CVCF mode or non-CVCF mode:
- CF: Setting UPS to CVCF mode. Output frequency is fixed at 50Hz or 60Hz (as per Parameter 2). Input frequency can be 46Hz-64Hz.
- NCF: Setting UPS to normal mode (non-CVCF mode). Output frequency synchronizes with input frequency within 46~54 Hz (for 50Hz) or 56~64 Hz (for 60Hz). If 50 Hz is selected in Parameter 2, UPS transfers to battery mode if input frequency is outside 46~54 Hz. If 60 Hz is selected, it transfers to battery mode if input frequency is outside 56~64 Hz.
*If Parameter 2 is ATO, Parameter 3 will show the current frequency.
Parameter 3: Voltage range for bypass
Interface: Setting
Parameter 2: Set acceptable low voltage for bypass. Range: 110V to 209V. Default: 110V.
Parameter 3: Set acceptable high voltage for bypass. Range: 231V to 276V. Default: 264V.
Parameter 4: Frequency range for bypass
Interface: Setting
Parameter 2: Set acceptable low frequency for bypass.
- 50 Hz system: 46.0Hz to 49.0Hz.
- 60 Hz system: 56.0Hz to 59.0Hz.
- Default: 46.0Hz/56.0Hz.
Parameter 3: Set acceptable high frequency for bypass.
- 50 Hz: 51.0Hz to 54.0 Hz.
- 60 Hz: 61.0Hz to 64.0Hz.
- Default: 54.0Hz/64.0Hz.
Parameter 8: Bypass mode setting
Interface: Setting
Parameter 2:
- OPN: Bypass allowed. UPS runs in Bypass mode based on bypass enabled/disabled setting.
- FBD: Bypass not allowed. Not allowed to run in Bypass mode under any situation.
Parameter 3: Only valid for OPN option.
- ENA: Bypass enabled. Bypass mode is activated.
- DIS: Bypass disabled. Automatic bypass is acceptable, but manual bypass is not allowed. Manual bypass means users manually operate UPS for Bypass mode (e.g., pressing OFF button in AC mode).
Parameter 9: Autonomy limitation setting
Interface: Setting
Parameter 3: Set maximum discharge time from 0 to 999 minutes. UPS shuts down to protect the battery after discharge time is reached. Default: 990 min. DIS: Disable battery discharge protection; backup time depends on battery capacity.
Parameter 13: Battery voltage calibration
Interface: Setting
Parameter 2: Select "Add" or "Sub" to calibrate battery voltage to the real figure.
Parameter 3: Voltage setting range: 0V to 5.7V. Default: 0V.
Parameter 15: Inverter voltage calibration
Interface: Setting
Parameter 2: Select "Add" or "Sub" to calibrate inverter voltage.
Parameter 3: Voltage setting range: 0V to 6.4V. Default: 0V.
Parameter 16: Floating charger voltage adjustment
Interface: Setting
Parameter 2: Select "Add" or "Sub" to adjust floating charger voltage.
Parameter 3: Voltage range: 0V to 5.7V. Default: 0V.
Parameter 17: Constant charger voltage adjustment
Interface: Setting
Parameter 2: Select "Add" or "Sub" to adjust constant charger voltage.
Parameter 3: Voltage range: 0V to 5.7V. Default: 0V.
Parameter 18: Maximum charger current setting
Interface: Setting
Parameter 3: Maximum charging current can be adjusted. Default: 4A (long run model), 1A (standard model). Options: 1A, 2A, 4A, 6A. 6A is only available for 16 batteries.
Parameter 19: Battery capacity and groups setting
Interface: Setting
Parameter 2: Set battery capacity (e.g., 7AH, 9AH, 10AH, 12AH, 17AH, 26AH, 40AH, 65AH, 100AH). Default: 9AH.
Parameter 3: Set battery group range from 1 to 6. Default: 1 group. These parameters are for battery backup time calculation.
Parameter 20: Backup time calibration
Interface: Setting
Parameter 3: Calibrate displayed backup time by adjusting this multiplier factor. Formula: Displayed backup time = Original calculated backup time x Multiplier factor. Default: 1.0. Range: 0.5 to 2.
Parameter 00: Exit setting
Select this to exit the setting mode.
3-7. Operating Mode Description
- AC mode: When input voltage is within range, UPS provides stable AC power. Charges battery. LCD display: [AC Mode Icon].
- CVCF mode: When input frequency is 46-64Hz, UPS provides constant output frequency (50Hz or 60Hz). Charges battery. LCD display: [CVCF Mode Icon].
- Battery mode: When input voltage is out of range or power fails, UPS uses battery power. Alarm beeps every 4 seconds. LCD display: [Battery Mode Icon].
- Bypass mode: When input voltage is within range and bypass is enabled, UPS enters Bypass mode after being turned off. Alarm beeps every two minutes. LCD display: [Bypass Mode Icon].
- Battery Test: In AC or CVCF mode, press "Test" for >1s. UPS beeps once and starts Battery Test. Line between I/P and inverter icons blinks. Used to check battery status. LCD display: [Battery Test Icon].
- Fault status: UPS has a fault. Displays fault codes on LCD. LCD display: [Fault Icon].
3-8. Fault Code
Fault Event | Fault Code | Icon |
---|---|---|
Bus start failure | 01 | [No Icon] |
Bus over | 02 | [No Icon] |
Bus under | 03 | [No Icon] |
Bus unbalance | 04 | [No Icon] |
Inverter soft start failure | 11 | [No Icon] |
High Inverter voltage | 12 | [No Icon] |
Low Inverter voltage | 13 | [No Icon] |
Inverter output short circuited | 14 | [No Icon] |
Battery SCR short circuited | 21 | [No Icon] |
Over temperature | 41 | [No Icon] |
Overload | 43 | [No Icon] |
3-9. Warning Indicator
Warning | Icon | Alarm |
---|---|---|
Battery low | [Flashing Icon] | Beeping every second |
Overload | [Flashing Icon] | Beeping twice every second |
Battery unconnected | [Flashing Icon] | Beeping every second |
Over charge | [Flashing Icon] | Beeping once every second |
EPO enable | [Flashing Icon] | Beeping once every second |
Over temperature | [Flashing Icon] | Beeping once every second |
Charger failure | [Flashing Icon] | Beeping once every second |
Overload 3 times in 30min | [Flashing Icon] | Beeping once every second |
Cover of maintain switch is open | [Flashing Icon] | Beeping once every second |
4. Troubleshooting
Symptom | Possible Cause | Remedy |
---|---|---|
No indication and alarm in the front display panel even though the mains is normal. | The AC input power is not connected well. | Check if input cable is firmly connected to the mains. |
The [AC Mode Icon] and [Warning Code Icon] flash on LCD display and alarm beeps every second. | EPO function is enabled. | Set the circuit in closed position to disable EPO function. |
The [Battery Mode Icon] and [Warning Code Icon] flash on LCD display and alarm beeps every second. | The external or internal battery is incorrectly connected. | Check if all batteries are connected well. |
The [Overload Icon] and [Warning Code Icon] flash on LCD display and alarm beeps twice every second. | UPS is overload. | Remove excess loads from UPS output. |
Fault code is shown as 43. The [Overload Icon] lights on LCD display and alarm beeps continuously. | UPS is overloaded. Devices connected to the UPS are fed directly by the electrical network via the Bypass. After repetitive overloads, the UPS is locked in the Bypass mode. Connected devices are fed directly by the mains. | Remove excess loads from UPS output. Remove excess loads from UPS output first. Then shut down the UPS and restart it. |
Fault code is shown as 14, the [Short Circuit Icon] lights on LCD display, and alarm beeps continuously. | UPS is overload too long and becomes fault. Then UPS shut down automatically. The UPS shut down automatically because short circuit occurs on the UPS output. | Remove excess loads from UPS output and restart it. Check output wiring and if connected devices are in short circuit status. |
Other fault codes are shown on LCD display and alarm beeps continuously. | A UPS internal fault has occurred. | Contact your dealer. |
Batteries are not charged fully. Battery backup time is shorter than nominal value. Batteries defect. | Possible cause: Batteries are not charged fully. Possible cause: Batteries defect. | Charge the batteries at least 7 hours and check capacity. If the problem still persists, consult your dealer. Contact your dealer to replace the battery. |
The [Over Temperature Icon] and [Warning Code Icon] flash on LCD display and alarm beeps every second. | The UPS temperature is too high. | Check fans and notify dealer. |
UPS can not start up, the [EPO Icon] flashes on LCD display, and alarm beeps every second. | Cover of maintain switch is open. | Check if the cover of maintain switch is screwed tightly. |
5. Specifications
MODEL | VICTOR 1U6KL | |
---|---|---|
PHASE | Single phase (L+N+PE) | |
CAPACITY | 6000 VA / 4800 W | |
INPUT | Nominal Voltage | 208*/220/230/240VAC |
Voltage Range | 110-300VAC ± 3% at 50% load; 176-300VAC ± 3% at 100% load | |
Frequency Range | 46~54Hz / 56~64 Hz | |
Power Factor | ≥ 0.99 @ Nominal Voltage (100% load) | |
THDi | ≤ 4 % @100% load ; ≤ 6 % @ 50% load | |
OUTPUT | Output Voltage | 208*/220/230/240VAC ± 1% |
Voltage Regulation | ± 1% | |
Frequency Range (Synchronized Range) | 46~ 54 Hz or 56 ~ 64 Hz | |
Frequency Range (Batt. Mode) | 50 Hz or 60Hz ± 0.1 Hz | |
Current Crest Ratio | 3:1 (max.) | |
Harmonic Distortion | ≤ 2 % THD (Linear Load) / ≤ 4 % THD (Non-linear Load) | |
Transfer Time | Zero | |
AC to DC | 4 ms (Typical) | |
Inverter to Bypass | Pure Sinewave | |
Waveform (Batt. Mode) | Pure Sinewave | |
Overload AC Mode | 100% load 105% Warning only; 105%< load ≤ 125% 1min; >125%: 1 sec | |
Overload Battery Mode | 100% load 105% Warning only; 105%< load ≤ 125% 30 sec; >125%: 1 sec | |
EFFICIENCY | To AC Mode | 95% |
To Battery Mode | 93% | |
Charger | Nominal Voltage | 192 VDC |
Charging Current | 6.0 A | |
Charging Voltage | 210VDC ±1% | |
Battery Connector | 2Poles (50A max.) | |
Lithium Battery Pack | Model Name | LIO 192003 |
Capacity | 3 Ah | |
Nominal DC Voltage | 192 VDC | |
Cell Type and nominal capacity | LiFeO4 and 3.2V/3Ah | |
Continuous discharge current | 30A max. | |
Battery Connector | 2Poles (50A max.) | |
INDICATORS & COM | Status indicating | LED, battery level, status |
Com ports | RS485 x 2: RS485 (Pack to UPS), CAN (pack to pack) | |
Capacity extension | YES, max up to 5 packs | |
PHYSICAL | Unit Dimension, D x W x H (mm) | 530 x 438 x 44 |
Package Dimension, D x W x H (mm) | 770 x 590 x 160 | |
N.W /G.W of Pack | 15.5 Kg / 18.2 Kg | |
MANAGEMENT | LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
Communication ports | USB, Mini Slot | |
Emergency Power Off (EPO) | YES, max up to 5 packs | |
ENVIRONMENT | Humidity | 0-95 % RH @ 0-40°C (non-condensing) |
Altitude | 0~2000meters without derating; 2000~3000 meters, derating 1% every 100meters; >3000 meters, not working | |
Noise Level | Less than 55dBA @ 1 Meter | |
MANAGEMENT | USB | Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix, and MAC |
Optional SNMP | Power management from SNMP manager and web browser | |
Optional WiFi module | App for Wifi linking |
* Output will be derated when the output voltage is adjusted to 208VAC.
** Product specifications are subject to change without further notice.