R. STAHL Load Disconnect Switches and Motor Starters
Molded Case Circuit Breaker for Motor Protection
8146/5-V27-208-065-12-21-1 Art. No. 249208
Key Features:
- Conductor and system protection for Ex e and Ex d motors
- Robust enclosure made of glass fibre reinforced polyester resin
- Optional: Undervoltage release, shunt trip, ammeter, auxiliary contact
Product Description:
R. STAHL Series 8146/5-V27 molded case circuit breakers are designed for motor protection in Ex e and Ex d applications, as well as for associated conductors and systems. Standard versions include adjustable, phase-sensitive thermal overcurrent release or an electromagnetic quick release, which must be specified during the ordering process and cannot be retrofitted.
Technical Data
Explosion Protection
Area of application | European Union (ATEX), IECEx |
Application range (zones) | 1, 2, 21, 22 |
IECEx gas certificate | IECEx PTB 06.0090 |
IECEx gas explosion protection | Ex db eb IIC T5 Gb |
IECEx dust certificate | IECEx PTB 06.0090 |
IECEx dust explosion protection | Ex tb IIIC T95 °C Db |
ATEX gas certificate | PTB 01 ATEX 1024 |
ATEX gas explosion protection | II 2 G Ex db eb IIC T5 Gb |
ATEX dust certificate | PTB 01 ATEX 1024 |
ATEX dust explosion protection | II 2 D Ex tb IIIC T95 °C Db |
Certificates | ATEX (PTB), Canada (FM), China (NEPSI), IECEx (PTB), India (PESO) |
Declaration of conformity | ATEX (EUK), China (CCC) |
Electrical Data
Switching capacity | 12.4 kW |
AC release voltage | 400 V |
Current-setting range | 1 - 1.6 A |
Ammeter present | No |
Auxiliary contacts | 1 NC, 1 NO |
Release | Undervoltage release |
No. of poles | 3 |
Frequency range | 50 - 60 Hz |
Ambient Conditions
Ambient temperature | -20°C ... +40°C |
Ambient temperature | -4 °F ... +104 °F |
Mechanical Data
Degree of protection (IP) | IP66 |
Degree of protection note | according to EN/IEC 60529 |
Enclosure material | Polyester resin, Glass fibre reinforced |
Min. solid conn. cr.-sect. AWG | AWG 16 |
Max. solid conn. cr.-sect. AWG | AWG 8 |
Min. f.stra. con. cr.-sec. AWG | AWG 16 |
Type of screw connection | 8161 |
Width | 170 mm |
Width, inches | 6.69 in |
Height | 227 mm |
Height in inches | 8.94 in |
Depth | 131 mm |
Depth in inches | 5.16 in |
Handle colour | Black |
Protective collar colour | Black |
Rotary actuator labelling | 0-1 |
Seal | Silicone, foamed |
Lockable in | Three times in 0 position |
Weight | 2.7 kg |
Weight | 5.95 lb |
Components
Cable glands and entries: 3 x M25 Ø 7 17 mm
Dimensional Drawings: (All Dimensions in mm [inches]) – Subject to Alterations
Diagram: A visual representation showing the dimensions of the circuit breaker. Key dimensions include width (170mm/6.69in), height (227mm/8.94in), and depth (131mm/5.16in). A circular detail shows a 7mm/0.28in diameter opening.
Cable entries:
Version | Auxiliary contacts | Cable glands Series 8161 | Stopping plugs Series 8290 |
Current-setting range up to 16 A | without | M25 x 1.5, M32 x 1.5 | M25 x 1.5 |
with A, B, C | - | C | |
Current-setting range 16 to 20 A, 20 to 22.5 A | without | A, B | C |
with C | A, B, C | C |
R. STAHL reserves the right to make alterations to the technical data, dimensions, weights, designs and products available without notice. The illustrations cannot be considered binding.