Emerson Sentronic+ Electronic Oil Pressure Control

An overview of the Sentronic+ system for precise oil pressure management in Copeland compressors.

Introduction to Sentronic+

The Sentronic+ electronic oil pressure safety control by Emerson Climate Technologies offers advanced features for monitoring and protecting compressors. It utilizes a pressure sensor and an electronic module to accurately measure oil pump differential pressure, eliminating common leak points found in traditional mechanical controls. A key advantage is its precise electronic timing circuit for the two-minute time-out function, unaffected by ambient temperature or voltage fluctuations, ensuring consistent safety operation.

Key Features and Benefits

  • Precise electronic timing for a reliable 2-minute time-out.
  • Visual LED indicator for immediate oil pressure status and troubleshooting.
  • Enhanced electronic noise suppression, eliminating the need for shielded cables.
  • Designed to meet stringent Emerson approval requirements, including durability and calibration stability.
  • Non-adjustable, manual reset control with specific cut-out and cut-in pressure settings (7-9 PSID and 12-14 PSID respectively).
  • Module base accommodates both threaded and push-in electrical conduit connections.

Operational Overview

The Sentronic+ sensor is mounted directly to the compressor's oil pump. It measures the differential oil pressure. If the pressure drops below the safety threshold for a set duration (two minutes), the electronic module opens a control circuit, shutting down the compressor. The system also detects and reacts to fluctuating oil pressures and retains memory of oil pressure levels during power interruptions.

Installation and Troubleshooting

This document provides detailed instructions for installing the Sentronic+ sensor and module, including torque specifications and wiring guidance. It also outlines troubleshooting steps, LED interpretation for fault diagnosis, and procedures for checking the sensor and module functionality, including a bench test procedure. Information on interchangeability with older Sentronic models is also provided.

For detailed installation and troubleshooting, refer to the specific diagrams and procedures within the full document.

PDF preview unavailable. Download the PDF instead.

ae1314 Microsoft Word 2016

Related Documents

Preview Copeland Scroll ZB Series Large Refrigeration Compressors | Emerson Technical Specifications
Explore the technical specifications, features, and protection systems of Emerson's Copeland Scroll ZB Series large refrigeration compressors. This document details models, performance data, CoreSense and Kriwan protection modules, and essential safety controls for commercial refrigeration applications.
Preview Emerson OMB/OMC Series Oil Management Control | Product Specifications and Features
Detailed information on Emerson's OMB/OMC Series Oil Management Controls, engineered to ensure optimal compressor crankcase oil levels. This document provides comprehensive details on features, technical specifications, model nomenclature, and available parts for various applications including CO2 and Ammonia systems.
Preview Emerson Electronic Valves and Controls: Energy Saving Solutions for Refrigeration & HVAC
Explore Emerson's EX4-EX8 series electronic control valves and EXD controllers for efficient energy management in industrial cooling, air conditioning, and heat pump applications. Discover features, applications, and product specifications.
Preview Emerson EXD-HP1/2 Autonomous Overheat and Economizer Controller Technical Information
Comprehensive technical specifications, features, and configuration parameters for the Emerson EXD-HP1/2 autonomous controllers. These controllers are designed for precise overheat and economizer control in various HVAC, refrigeration, and heating systems, offering Modbus communication capabilities and advanced diagnostics.
Preview CoreSense Diagnostics v2.11 for Copeland Discus Compressors - Installation and Service Manual
This Application Engineering Bulletin provides comprehensive installation, operation, and troubleshooting guidance for Emerson's CoreSense Diagnostics v2.11 system, designed for Copeland Discus compressors, enhancing system reliability and performance.
Preview Copeland Scroll™ Fusion Compressor User Manual for Refrigeration Applications
Comprehensive user manual for Emerson's Copeland Scroll™ Fusion compressors, detailing installation, operation, safety, technical specifications, and maintenance for refrigeration applications.
Preview Copeland Scroll Compressor Training Kit: Hands-On HVACR Education
Explore the Copeland Scroll Compressor Training Kit from Emerson, designed for hands-on HVACR education. Learn scroll compression fundamentals with a disassembled compressor, safety equipment, and digital resources.
Preview Emerson 16E09-101 Electronic Temperature Control Installation and Operation Manual
This document provides detailed instructions for the installation, wiring, user menu operation, and troubleshooting of the Emerson 16E09-101 single-stage electronic temperature control. It covers features like differential, anti-short cycle delay, set back, offset, alarms, and sensor compatibility.