Daikin Room Air Conditioner Installation Manual

Models: FTXF20F5V1B, FTXF25F5V1B, FTXF35F5V1B, FTXF42F5V1B

1. About the Documentation

Make sure that the user has the printed documentation and ask him/her to keep it for future reference.

Target audience: Authorised installers

This appliance is intended to be used by expert or trained users in shops, in light industry, and on farms, or for commercial and household use by lay persons.

Documentation set

This document is part of a documentation set. The complete set consists of:

The latest revision of the supplied documentation is published on the regional Daikin website and is available via your dealer. The original instructions are written in English. All other languages are translations of the original instructions.

Technical engineering data

2. Specific Installer Safety Instructions

Always observe the following safety instructions and regulations.

Unit installation

Installation shall be done by an installer, the choice of materials and installation shall comply with the applicable legislation. In Europe, EN378 is the applicable standard.

Installation site

Check if the installation location can support the unit's weight. Poor installation is hazardous. It can also cause vibrations or unusual operating noise.

Provide sufficient service space.

Do NOT install the unit so that it is in contact with a ceiling or a wall, as this may cause vibrations.

Storage

The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).

Connecting the refrigerant piping

No brazing or welding on site for units with R32 refrigerant charge during shipment.

During installation of the refrigeration system, joining of parts with at least one part charged shall be performed taking into account the following requirements: inside occupied spaces non-permanent joints are NOT allowed for R32 refrigerant except for site made joints directly connecting the indoor unit to piping. Site made joints directly connecting piping to indoor units shall be of non-permanent type.

Use the flare nut fixed to the unit.

To prevent gas leakage, apply refrigeration oil ONLY to the inside of the flare. Use refrigeration oil for R32 (FW68DA).

Do NOT reuse joints.

Do NOT use mineral oil on flared part.

Do NOT reuse piping from previous installations.

NEVER install a drier to this R32 unit to guarantee its lifetime. The drying material may dissolve and damage the system.

Connect the refrigerant piping securely before running the compressor. If the refrigerant piping is NOT connected and the stop valve is open when the compressor is run, air will be sucked in. This will cause abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.

Incomplete flaring may cause refrigerant gas leakage.

Do NOT re-use flares. Use new flares to prevent refrigerant gas leakage.

Use flare nuts that are included with the unit. Using different flare nuts may cause refrigerant gas leakage.

Do NOT open the valves before flaring is complete. This would cause refrigerant gas leakage.

Do NOT open the stop valves before the vacuum drying is finished.

Charging refrigerant

The refrigerant inside the unit is mildly flammable, but normally does NOT leak. If the refrigerant leaks in the room and comes in contact with fire from a burner, a heater, or a cooker, this may result in fire, or the formation of a harmful gas.

Turn OFF any combustible heating devices, ventilate the room, and contact the dealer where you purchased the unit.

Do NOT use the unit until a service person confirms that the part from which the refrigerant leaked has been repaired.

Only use R32 as refrigerant. Other substances may cause explosions and accidents.

R32 contains fluorinated greenhouse gases. Its global warming potential (GWP) value is 675. Do NOT vent these gases into the atmosphere.

When charging refrigerant, ALWAYS use protective gloves and safety glasses.

To avoid compressor breakdown, do NOT charge more than the specified amount of refrigerant.

NEVER directly touch any accidental leaking refrigerant. This could result in severe wounds caused by frostbite.

Electrical installation

The appliance MUST be installed in accordance with national wiring regulations.

All wiring MUST be performed by an authorised electrician and MUST comply with the national wiring regulation.

Make electrical connections to the fixed wiring.

All components procured on-site and all electrical construction MUST comply with the applicable legislation.

If the power supply has a missing or wrong N-phase, equipment might break down.

Establish proper earthing. Do NOT earth the unit to a utility pipe, surge absorber, or telephone earth. Incomplete earthing may cause electrical shocks.

Install the required fuses or circuit breakers.

Secure the electrical wiring with cable ties so that the cables do NOT come in contact with sharp edges or piping, particularly on the high-pressure side.

Do NOT use taped wires, extension cords, or connections from a star system. They can cause overheating, electrical shocks or fire.

Do NOT install a phase advancing capacitor, because this unit is equipped with an inverter. A phase advancing capacitor will reduce performance and may cause accidents.

ALWAYS use multicore cable for power supply cables.

Use an all-pole disconnection type breaker with at least 3 mm between the contact point gaps that provides full disconnection under overvoltage category III.

If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.

Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.

Do NOT use locally purchased electrical parts inside the product.

Do NOT branch the power supply for the drain pump, etc. from the terminal block. This could result in electrical shock or fire.

Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.

DANGER: RISK OF ELECTROCUTION

All electrical parts (including thermistors) are powered by the power supply. Do NOT touch them with bare hands.

DANGER: RISK OF ELECTROCUTION

Disconnect the power supply for more than 10 minutes, and measure the voltage at the terminals of main circuit capacitors or electrical components before servicing. The voltage MUST be less than 50 V DC before you can touch electrical components. For the location of the terminals, see the wiring diagram.

DANGER: RISK OF ELECTROCUTION

Make sure that the system is earthed properly.

Turn OFF the power supply before servicing.

Install the switch box cover before turning ON the power supply.

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

Do NOT perform the test operation while working on the indoor unit(s).

When performing the test operation, NOT ONLY the outdoor unit, but the connected indoor unit will operate as well. Working on an indoor unit while performing a test operation is dangerous.

Do NOT insert fingers, rods or other objects into the air inlet or outlet. Do NOT remove the fan guard. When the fan is rotating at high speed, it will cause injury.

WARNING: MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable.

3. About the Box

3.1 Indoor unit

The following figures are examples and may NOT completely match your system layout.

3.1.1 To remove the accessories from the indoor unit

1. Remove:

Diagram Description: A visual representation showing the contents of the accessory bag, including an installation manual, operation manual, general safety precautions, a spare SSID sticker, indoor unit fixing screws (M4x12L), AAA LR03 dry batteries for the user interface, a holder for the wireless remote control, the wireless remote control itself, and a mounting plate.

2. Spare SSID sticker: Do NOT throw away the spare sticker. Keep it in a safe place in case it is needed in future (e.g. in case the front grille was replaced, attach it to the new front grille).

4. About the Unit

WARNING: MILDLY FLAMMABLE MATERIAL The refrigerant inside this unit is mildly flammable.

4.1 System Layout

The following figures are examples and may NOT completely match your system layout.

Diagram Description: An illustration of the indoor unit's internal components, showing the air filter, a titanium apatite deodorizing and silver particle filter, refrigerant piping, drain hose, interconnection cable, and insulation tape.

4.2 Operation Range

Use the system in the following temperature and humidity ranges for safe and effective operation.

Operation mode Operation range
Cooling(a)(b) Outdoor temperature: -10~48°C DB
Indoor temperature: 18~32°C DB
Indoor humidity: ≤80%
Heating(a) Outdoor temperature: -15~24°C DB
Indoor temperature: 10~30°C DB
Drying(a) Outdoor temperature: -10~48°C DB
Indoor temperature: 18~32°C DB
Indoor humidity: ≤80%

(a) A safety device might stop the operation of the system if the unit runs outside its operation range.

(b) Condensation and water dripping might occur if the unit runs outside its operation range.

4.3 About the wireless LAN

For detailed specifications, installation instructions, setting methods, FAQ, declaration of conformity and the latest version of this manual, visit app.daikineurope.com.

Declaration of conformity: Daikin Europe N. V. declares that the radio equipment type inside of this unit is in compliance with Directive 2014/53/EU and S.I. 2017/1206: Radio Equipment Regulations 2017. This unit is considered as combined equipment according to the definition of Directive 2014/53/EU and S.I. 2017/1206: Radio Equipment Regulations 2017.

4.3.1 Precautions when using the wireless LAN

Do NOT use near:

4.3.2 Basic parameters

What Value
Frequency range 2400 MHz~2483.5 MHz
Radio protocol IEEE 802.11b/g/n
Radio frequency channel 1~13
Output power 13 dBm
Effective radiated power 15 dBm (11b) / 14 dBm (11g) / 14 dBm (11n)
Power supply DC 14 V / 100 mA

5. Unit Installation

5.1 Preparing the installation site

The appliance shall be stored in a room without continuously operating ignition sources (example: open flames, an operating gas appliance or an operating electric heater).

The appliance using R32 refrigerant shall be stored so as to prevent mechanical damage and in a well-ventilated room without continuously operating ignition sources (e.g. open flames, an operating gas appliance, or an operating electric heater). The room size shall be as specified in the General safety precaution.

5.1.1 Installation site requirements of the indoor unit

The sound pressure level is less than 70 dBA.

Diagram Description: Illustrates minimum clearance requirements around the indoor unit: 50mm from the top, 50mm from the sides, and 30mm from the bottom.

5.1.2 Additional installation site requirements of the outdoor unit in cold climates

Protect the outdoor unit against direct snowfall and take care that the outdoor unit is NEVER snowed up. In heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat exchanger coil is NOT affected by the snow. If necessary, install a snow cover or shed and a pedestal.

5.2 Opening the indoor unit

5.2.1 To remove the front panel

1. Hold the front panel by the panel tabs on both sides and open it.

2. Remove the front panel by sliding it to the left or the right and pulling it toward you. Result: The front panel shaft on 1 side will be disconnected.

3. Disconnect the front panel shaft on the other side in the same manner.

5.2.2 To re-install the front panel

1. Attach the front panel. Align the shafts with the slots and push them all the way in.

2. Close the front panel slowly; press at both sides and at the centre.

5.2.3 To remove the front grille

Wear adequate personal protective equipment (protective gloves, safety glasses,...) when installing, maintaining or servicing the system.

1. Remove the front panel to remove the air filter.

2. Remove 2 screws (class 20~35) or 3 screws (class 50~71) from the front grille.

3. Push down the 3 upper hooks marked with a symbol with 3 circles.

Diagram Description: Shows the location of the upper hooks on the front grille, marked with a symbol of three circles.

4. We recommend opening the flap before removing the front grille.

5. Place both hands under the centre of the front grille, push it up and then toward you.

5.2.4 To re-install the front grille

1. Install the front grille and firmly engage the 3 upper hooks.

2. Install 2 screws back on the front grille.

3. Install the air filter and then mount the front panel.

5.2.5 To remove the electrical wiring box cover

Prerequisite: Remove the front grille.

1. Remove 1 screw from the electrical wiring box.

2. Open the electrical wiring box cover by pulling the protruding part on the top of the cover.

3. Unhook the tab on the bottom and remove the electrical wiring box cover.

5.2.6 To open the service cover

1. Remove 1 screw from the service cover.

2. Pull out the service cover horizontally away from the unit.

5.3 Mounting the indoor unit

5.3.1 To install the mounting plate

1. Install the mounting plate temporarily.

2. Level the mounting plate.

3. Mark the centres of the drilling points on the wall using a tape measure. Position the end of tape measure at symbol " $\rightarrow$ ".

4. Finish the installation by securing the mounting plate on the wall using M4×25L screws (field supply).

The removed pipe port cover can be kept in the mounting plate pocket.

Diagram Description: A detailed diagram of the mounting plate showing recommended fixing spots, the pocket for the pipe port cover, markings for liquid and gas pipe ends, tabs for a spirit level, the unit center, and holes for embedded piping (Ø65 mm). It also indicates piping hole centers (160mm left, 170mm right) and dimensions for pipe lengths and drain hose.

5.3.2 To drill a wall hole

For walls containing a metal frame or a metal board, use a wall embedded pipe and wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.

Be sure to seal the gaps around the pipes with sealing material (field supply), in order to prevent water leakage.

1. Bore a 65 mm large feed-through hole in the wall with a downward slope towards the outside.

2. Insert a wall embedded pipe into the hole.

3. Insert a wall cover into the wall pipe.

4. After completing wiring, refrigerant piping and drain piping, do NOT forget to seal the gap with putty.

Diagram Description: Shows a cross-section of the wall hole with a wall embedded pipe, putty sealant, and a wall hole cover.

5.3.3 To remove the pipe port cover

To connect the piping on right-side, right-bottom, left-side or left-bottom, the pipe port cover MUST be removed.

1. Cut off the pipe port cover from inside the front grille using a coping saw.

2. Remove any burrs along the cut section using a half round needle file.

5.3.4 To provide drainage

Make sure condensation water can be evacuated properly. This involves:

General guidelines

Install the drain hose with a downward slope.

Traps are NOT permitted.

Do NOT put the end of the hose in water.

Drain hose extension: To extend the drain hose, use a field supplied hose with inner Ø16 mm. Do NOT forget to use a heat insulation tube on the indoor section of the extension hose.

Diagram Description: Illustrates the drain hose connection, showing the supplied drain hose, an optional drain socket, and an optional rigid polyvinyl chloride pipe. It also shows the recommended insulation for the extension hose.

Condensation: Take measures against condensation. Insulate the complete drain piping in the building.

1. Insert the drain hose in the drain pipe as shown in the following figure, so it will NOT be pulled out of the drain pipe.

Diagram Description: Shows the correct insertion of the drain hose into the drain pipe, ensuring it is securely seated.

To connect the piping on right side, right-back, or right-bottom

The factory default is right-side piping. For left-side piping, remove the piping from the right side and install it on the left side.

1. Attach the drain hose with adhesive vinyl tape to the bottom of the refrigerant pipes.

2. Wrap the drain hose and the refrigerant pipes together using insulation tape.

Diagram Description: Illustrates connecting the drain hose for right-side, right-bottom, and right-back piping configurations, showing how to remove the pipe port cover.

To connect the piping on left side, left-back, or left-bottom

The factory default is right-side piping. For left-side piping, remove the piping from the right side and install it on the left side.

1. Remove the insulation fixing screw on the right side and remove the drain hose.

2. Remove the drain plug on the left side and attach it to the right side.

Do NOT apply lubricating oil (refrigerant oil) to the drain plug when inserting it. The drain plug may deteriorate and cause drain leakage from the plug.

3. Insert the drain hose on the left side and do not forget to tighten it with the fixing screw; otherwise water leakage may occur.

4. Attach the drain hose to the refrigerant piping bottom side using adhesive vinyl tape.

Diagram Description: Illustrates connecting the drain hose for left-side, left-back, and left-bottom piping configurations, showing the removal of the pipe port cover.

To check for water leaks

1. Remove the air filters.

2. Gradually pour approximately 1 l of water in the drain pan, and check for water leaks.

6. Piping Installation

6.1 Preparing refrigerant piping

6.1.1 Refrigerant piping requirements

The piping and other pressure-containing parts shall be suitable for refrigerant. Use phosphoric acid deoxidised seamless copper for refrigerant piping.

Foreign materials inside pipes (including oils for fabrication) must be ≤30 mg/10 m.

Refrigerant piping diameter

Use the same diameters as the connections on the outdoor units:

Pipe outer diameter (mm) Liquid piping Gas piping
Ø6.4 (1/4") Ø9.5 (3/8")

Refrigerant piping material

Piping material Flare connections
Phosphoric acid deoxidised seamless copper Only use annealed material.

Piping temper grade and thickness

Outer diameter (Ø) Temper grade Thickness (t)(a)
6.4 mm (1/4") Annealed (O) ≥0.8 mm

(a) Depending on the applicable legislation and the maximum working pressure of the unit (see "PS High" on the unit name plate), larger piping thickness might be required.

6.1.2 Refrigerant piping insulation

Use polyethylene foam as insulation material:

Insulation thickness:

Pipe outer diameter (Ø) Insulation inner diameter (Øi) Insulation thickness (t)
6.4 mm (1/4") 8~10 mm ≥10 mm

If the temperature is higher than 30°C and the humidity is higher than RH 80%, the thickness of the insulation materials should be at least 20 mm to prevent condensation on the surface of the insulation.

6.2 Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

Diagram Description: Shows tools for connecting piping: torque wrench, spanner, piping union, and flare nut. Also provides a table for piping size, tightening torque, flare dimensions, and flare shape.

Diagram Description: Illustrates connecting refrigerant piping to the indoor unit, showing the gas pipe, gas pipe insulation, interconnection cable, liquid pipe, liquid pipe insulation, finishing tape, and drain hose. It emphasizes the need to insulate all refrigerant piping.

6.3 Checking the refrigerant piping

6.3.1 To check for leaks

Do NOT exceed the unit's maximum working pressure (see "PS High" on the unit name plate).

ALWAYS use a recommended bubble test solution from your wholesaler.

NEVER use soap water:

1. Charge the system with nitrogen gas up to a gauge pressure of at least 200 kPa (2 bar). It is recommended to pressurize to 3000 kPa (30 bar) or higher (depending on local legislation) to detect small leaks.

2. Check for leaks by applying the bubble test solution to all connections.

3. Discharge all nitrogen gas.

6.3.2 To perform vacuum drying

1. Vacuum the system until the pressure on the manifold indicates -0.1 MPa (-1 bar).

2. Leave as is for 4-5 minutes and check the pressure:

If the pressure... Then...
Does not change There is no moisture in the system. This procedure is finished.
Increases There is moisture in the system. Go to the next step.

3. Vacuum the system for at least 2 hours to a manifold pressure of -0.1 MPa (-1 bar).

4. After turning the pump OFF, check the pressure for at least 1 hour.

5. If you do NOT reach the target vacuum or CANNOT maintain the vacuum for 1 hour, do the following:

7. Electrical installation

DANGER: RISK OF ELECTROCUTION

ALWAYS use multicore cable for power supply cables.

Use an all-pole disconnection type breaker with at least 3 mm between the contact point gaps that provides full disconnection under overvoltage category III.

If the supply cord is damaged, it MUST be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.

Do NOT connect the power supply to the indoor unit. This could result in electrical shock or fire.

Do NOT use locally purchased electrical parts inside the product.

Do NOT branch the power supply for the drain pump, etc. from the terminal block. This could result in electrical shock or fire.

Keep the interconnection wiring away from copper pipes without thermal insulation as such pipes will be very hot.

7.1 Specifications of standard wiring components

We recommend using solid wires. If stranded wires are used, slightly twist the strands to consolidate the end of the conductor for either direct use in the terminal clamp or insertion in a round crimp-style terminal. Details are described in "Guidelines when connecting the electrical wiring" in the installer reference guide.

Specifications Value
Voltage 220~240 V
Phase 1~
Frequency 50 Hz
Interconnection cable Only use harmonised wire providing double insulation and suitable for the applicable voltage. 4-core cable Minimum 1.5 mm²

7.2 To connect the electrical wiring to the indoor unit

Provide adequate measures to prevent that the unit can be used as a shelter by small animals. Small animals that make contact with electrical parts can cause malfunctions, smoke or fire.

Keep power supply wiring and interconnection wiring apart from each other. Interconnection wiring and power supply wiring may cross, but may NOT run parallel.

In order to avoid any electrical interference, the distance between both wirings should ALWAYS be at least 50 mm.

Electrical work should be carried out in accordance with the installation manual and the national electrical wiring rules or code of practice.

1. Set the indoor unit on the mounting plate hooks. Use the " $\rightarrow$ " marks as a guide.

Diagram Description: Shows the indoor unit being placed onto mounting plate hooks, with reference marks.

2. Open the front panel, and then the service cover. Refer to "5.2 Opening the indoor unit" [5].

3. Pass the interconnection cable from the outdoor unit through the feed-through wall hole, through the back of the indoor unit and through the front side.

Note: In case the interconnection cable was stripped in advance, cover the ends with insulating tape.

4. Bend the end of the cable up.

5. Strip the wire ends approximately 15 mm.

6. Match wire colours with terminal numbers on the indoor unit terminal blocks and firmly screw the wires to the corresponding terminals.

7. Connect the earth wire to the corresponding terminal.

8. Firmly fix the wires with the terminal screws.

9. Pull the wires to make sure that they are securely attached, then retain the wires with the wire retainer.

10. Shape the wires so that the service cover fits securely, then close the service cover.

8. Finishing the indoor unit installation

8.1 To insulate the drain piping, refrigerant piping and interconnection cable

1. After the drain piping, refrigerant piping and the electrical wiring are finished, wrap refrigerant piping, interconnection cable and drain hose together using insulation tape. Overlap at least half the width of the tape with each turn.

Diagram Description: Shows the drain hose, interconnection cable, mounting plate, refrigerant piping, and indoor unit fixing screw, illustrating how to wrap them together with insulation tape.

8.2 To pass the pipes through the wall hole

1. Shape the refrigerant pipes along the pipe path marking on the mounting plate.

2. Pass the drain hose and refrigerant piping through the wall hole and seal the gap with a putty.

Diagram Description: Illustrates passing the drain hose and refrigerant piping through the wall hole and sealing the gap.

8.3 To fix the unit on the mounting plate

1. Set the indoor unit on the mounting plate hooks. Use the " $\rightarrow$ " marks as a guide.

2. Press the bottom frame of the unit with both hands to set it on the bottom hooks of the mounting plate. Make sure that the wires do NOT get squeezed anywhere.

Note: Take care that the interconnection cable does NOT get caught in the indoor unit.

3. Press the bottom edge of the indoor unit with both hands until it is firmly caught by the mounting plate hooks.

4. Secure the indoor unit to the mounting plate using 2 indoor unit fixing screws M4×12L (accessory).

9. Configuration

9.1 To set a different channel of the indoor unit infrared signal receiver

In case 2 indoor units are installed in 1 room, you can change the channel for the infrared signal receiver on the indoor unit to avoid the wireless remote control signal confusion.

Prerequisite: Perform the following setting for only 1 of the units

1. Remove the batteries from the user interface.

2. Cut the address jumper.

Diagram Description: Shows the location of the address jumper and the action of cutting it.

Be careful NOT to damage any of the surrounding parts when cutting the address jumper.

3. Turn the power supply on.

Result: The flap of the indoor unit will open and close to set the reference position.

In case you could NOT complete the setting in time, turn the power supply off and wait at least 1 minute before turning the power supply back on.

4. Press simultaneously:

Model Buttons
FTXF and ATXF TEMP $\uparrow$ , TEMP $\downarrow$ , and OFF

5. Press:

Model Buttons
FTXF and ATXF TEMP

6. Select:

Model Symbol
FTXF and ATXF $★$ (Star symbol)

7. Press:

Model Button
FTXF and ATXF FAN (ON/OFF)

8. Press the indoor unit ON/OFF switch while the operation lamp is blinking.

Diagram Description: Shows the indoor unit with an operation lamp and an ON/OFF switch.

Jumper settings for address are shown: Factory setting is 1, after cutting with nippers it becomes 2.

If the setting could NOT be completed while the operation lamp was blinking, repeat the setting process from the beginning.

9. When the setting is complete, press:

Model Button
FTXF and ATXF Keep FAN pressed for about 5 seconds.

Result: The user interface will return to the previous screen.

10. Commissioning

ALWAYS operate the unit with thermistors and/or pressure sensors/switches. If NOT, burning of the compressor might be the result.

10.1 Checklist before commissioning

1. After the installation of the unit, check the items listed below.

2. Close the unit.

3. Power up the unit.

10.2 To perform a test run

Prerequisite: The power supply MUST be in the specified range.

Prerequisite: Test run may be performed in cooling or heating mode.

Prerequisite: Refer to the operation manual of the indoor unit for setting temperature, operation mode....

  1. In cooling mode, select the lowest programmable temperature. In heating mode, select the highest programmable temperature. The test run can be disabled if necessary.
  2. When the test run is finished, set the temperature to a normal level. In cooling mode: 26~28°C, in heating mode: 20~24°C.
  3. Make sure that all functions and parts are working properly.
  4. The system stops operating 3 minutes after the unit is turned OFF.
10.2.1 To perform a test run in winter season

When operating the air conditioner in Cooling mode in winter, set it to test run operation using the following method.

  1. Press TEMP $\uparrow$ , TEMP $\downarrow$ , and OFF simultaneously.
  2. Press TEMP $\uparrow$.
  3. Select 7.
  4. Press FAN.
  5. Press COOL to switch the system on.

Result: Test run operation will stop automatically after about 30 minutes.

6. To stop operation, press OFF.

Some of the functions CANNOT be used in the test run operation mode.

If a power failure occurs during operation, the system automatically restarts immediately after power is restored.

11. Disposal

Do NOT try to dismantle the system yourself: dismantling of the system, treatment of the refrigerant, oil and other parts MUST comply with applicable legislation. Units MUST be treated at a specialised treatment facility for reuse, recycling and recovery.

12. Technical Data

A subset of the latest technical data is available on the regional Daikin website (publicly accessible).

The full set of the latest technical data is available on the Daikin Business Portal (authentication required).

12.1 Wiring diagram

The wiring diagram is delivered with the unit, located inside of the outdoor unit (bottom side of the top plate).

12.1.1 Unified wiring diagram legend

For applied parts and numbering, refer to the wiring diagram on the unit. Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by "*" in the part code.

Symbol Meaning Symbol Meaning
Circuit breaker Protective earth
Noiseless earth Protective earth (screw)
Connection , Connector Rectifier
Earth Relay connector
Field wiring Short-circuit connector
Fuse Terminal
INDOOR Indoor unit Terminal strip
OUTDOOR Outdoor unit Wire clamp
Residual current device Heater
Symbol Colour Symbol Colour
BLK Black ORG Orange
BLU Blue PNK Pink
BRN Brown PRP, PPL Purple
GRN Green RED Red
GRY Grey WHT White
SKY BLU Sky blue YLW Yellow
Symbol Meaning Symbol Meaning
A*P Printed circuit board FG* Connector (frame ground)
BS* Pushbutton ON/OFF, operation switch H* Harness
BZ, H*O Buzzer H*P, LED*, V*L Pilot lamp, light emitting diode
C* Capacitor HAP Light emitting diode (service monitor green)
AC*, CN*, E*, HA*, HE*, HL*, HN*, HR*, MR*_A, MR*_B, S*, U, V, W, X*A, K*R_*, NE Connection, connector HIGH VOLTAGE High voltage
D*, V*D Diode IES Intelligent eye sensor
DB* Diode bridge IPM* Intelligent power module
DS* DIP switch K*R, KCR, KFR, KHUR, K*M Magnetic relay
E*H Heater L Live
FU*, F*U, (for characteristics, refer to PCB inside your unit) Fuse L* Coil
L*R Reactor
M* Stepper motor
M*C Compressor motor
M*F Fan motor
M*P Drain pump motor
MR*, MRCW*, MRM*, MRN* Magnetic relay
N Neutral
n=*, N=* Number of passes through ferrite core
PAM Pulse-amplitude modulation
PCB* Printed circuit board
PM* Power module
PS Switching power supply
PTC* PTC thermistor
Q* Insulated gate bipolar transistor (IGBT)
Q*C Circuit breaker
Q*DI, KLM Earth leak circuit breaker
Q*L Overload protector
Q*M Thermo switch
Q*R Residual current device
R* Resistor
R*T Thermistor
RC Receiver
S*C Limit switch
S*L Float switch
S*NG Refrigerant leak detector
S*NPH Pressure sensor (high)
S*NPL Pressure sensor (low)
S*PH, HPS* Pressure switch (high)
S*PL Pressure switch (low)
S*T Thermostat
S*RH Humidity sensor
S*W, SW* Operation switch
SA*, F1S Surge arrester
SR*, WLU Signal receiver
SS* Selector switch
SHEET METAL Terminal strip fixed plate
T*R Transformer
TC, TRC Transmitter
V*, R*V Varistor
V*R Diode bridge, Insulated-gate bipolar transistor (IGBT) power module
Symbol Meaning Symbol Meaning
WRC Wireless remote controller
X* Terminal
X*M Terminal strip (block)
Y*E Electronic expansion valve coil
Y*R, Y*S Reversing solenoid valve coil
Z*C Ferrite core
ZF, Z*F Noise filter
Models: FTXF20F5V1B, FTXF25F5V1B, FTXF35F5V1B, FTXF42F5V1B, FTXF20F5V1B Room Air Conditioner, FTXF20F5V1B, Room Air Conditioner, Air Conditioner, Conditioner

File Info : application/pdf, 16 Pages, 4.82MB

PDF preview unavailable. Download the PDF instead.

FTXF20-42F Installation manual 3PEN748643-9M English

References

ST4 PDF Engine (Build 14.0.1.0) SCHEMA ST4

Related Documents

Preview Daikin Factbox 2025: A Global Leader in HVAC Technology
Discover the Daikin Factbox 2025, detailing Daikin's global leadership in heating, cooling, ventilation, air purification, and refrigerant technology. Explore their extensive product range, commitment to sustainability, and innovation in HVAC-R solutions for residential, commercial, and industrial applications.
Preview Daikin BAF552AA160 High Performance Pre-filter Installation Manual
Comprehensive installation guide for the Daikin BAF552AA160 high performance pre-filter, detailing compatibility, step-by-step installation, field settings, and proper disposal procedures for authorized installers.
Preview Daikin Multi-Part Series R32 Installation Manual
Comprehensive installation guide for Daikin Multi-Part Series R32 air conditioning systems, covering safety, unit mounting, piping, refrigerant charging, electrical connections, and commissioning procedures.
Preview Daikin Classroom Unit Ventilator Installation and Maintenance Manual
Comprehensive installation and maintenance manual for Daikin's self-contained Classroom Unit Ventilators, models AZQ, AZU, and AZR, covering safety, electrical, controls, and operation.
Preview Daikin VRV System Air Conditioner Installation Manual
Comprehensive installation manual for Daikin VRV System Air Conditioners, specifically the Branch Selector unit models BS4Q54TAVJ, BS10Q54TAVJ, and BS12Q54TAVJ. This guide provides detailed instructions, safety precautions, and technical specifications for proper installation.
Preview Daikin Room Air Conditioner Operation Manual FT25JV1A FT35JV1A
This operation manual provides detailed instructions for Daikin Room Air Conditioners, models FT25JV1A and FT35JV1A. It covers safety precautions, installation guidelines, operation modes (DRY, COOL, FAN, POWERFUL, Timer), care and cleaning procedures, and troubleshooting tips.
Preview Daikin AKJ Series Immersion Oil Cooling Units: Features, Specifications, and Applications
Explore the Daikin AKJ series of immersion-type oil cooling units for industrial applications. This document details features, specifications, dimensions, and performance charts for models AKJ189, AKJ359, AKJ459, AKJ569, and AKJ909.
Preview Daikin R32 Split System Installation Manual
Comprehensive installation guide for Daikin R32 Split Systems, covering unit preparation, installation procedures, refrigerant handling, electrical connections, commissioning, and technical specifications. Includes safety warnings and compliance information.