Watlow DIN-A-MITE Power Controllers Wiring Safety Guide
Document Number: 2271-5649, 10-52315 Rev-
Safety Information
⚠️ CAUTION: Warning or Hazard that needs further explanation than the label on unit can provide. Consult User's Guide for further information.
⚡ Electrical Shock Hazard - Symbol (a lightning bolt in a triangle) precedes an electric shock hazard CAUTION or WARNING safety statement.
ESD Sensitive product, use proper grounding and handling techniques when installing or servicing product.
Do not throw in trash, use proper recycling techniques or consult manufacturer for proper disposal.
Unit is a Listed device per Underwriters Laboratories. It has been investigate to ANSI/UL® 508 standards for Industrial Control Switches and equivalent to CSA C22.2 #14. For more detail search for File E73741 on www.ul.com.
Unit is compliant with European Union directives. See Declaration of Conformity for further details on Directives and Standards used for Compliance.
Safety Notes
WARNING! To avoid damage to property and equipment, injury and loss of life, adhere to applicable electrical codes and standard wiring practices when installing and operating this product. Failure to do so could result in damage, injury and death.
WARNING! All service including inspection, installation, wiring, maintenance, troubleshooting, fuse or other user-serviceable component replacement must be performed only by properly qualified personnel. Service personnel must read this manual before proceeding with work. While service is being performed, other, unqualified personnel should not work on the unit or be allowed in the immediate vicinity.
WARNING! When in use, the power controller is connected to dangerous voltages. Do not remove the protective covers without first disconnecting and preventing power from being restored while servicing the unit.
WARNING! Electric Shock Hazard: when the power controller has been energized, after shutting off the power, wait at least one minute for internal capacitors to discharge before commencing work that brings you in to contact with power connections or internal components.
WARNING: The installation must be protected by fuses. Semiconductor fuses are classified for UL® as supplementary protection for semiconductor devices. They are not approved for branch circuit protection.
NOTE! The nominal current is specified for ambient temperatures at or below 50°C. Ensure the application design allows for adequate cooling of each power controller. The power controller must be mounted vertically. The cooling design must prevent air heated by one power controller from causing power controllers mounted above to exceed the ambient operating temperature limit. When power controllers are mounted side by side allow a minimum spacing of 15mm between them.
NOTE! Use only copper cables and wires rated for use at 75°C or greater.
Product Identification
The product identification label includes not only the part number, but also the voltage and current ratings.
Environment
Ambient operating temperature: 0 to 50°C. See User Manual for de-rating.
Ambient temperature maximum varies depending on unit.
Mount power controllers vertically.
5 to 90% RH (relative humidity), non-condensing.
Up to 6560 feet (2000m) above sea level maximum.
Storage temperature: -40 to 85°C maximum.
Pollution degree: Installation Category III, Pollution degree 2.
Install away from direct sun light, conductive dust, corrosive gas, vibration, water and corrosive salts.
SCCR Rating
SCCR Rating 200,000A up to 480 VAC.
Terminal Identification
The following illustrations show the locations for line power, load, earth ground and signal connections.
DIN-A-MITE Style A
Connection Locations DIN-A-MITE Style A shows terminals 1-10. Terminals 1, 2 are for Line connections. Terminals 3, 4 are for Load connections. Terminals 5, 6 are for Command Signal Inputs (DC+ / AC and DC- / AC respectively). Terminals 7-10 are marked 'Not used / no connection'.
Grounding: Use a grounding conductor terminal plate (fork terminal) having upturned lugs or the equivalent to hold the wire in position. Use 6 mm² (10 AWG) wire.
Terminal Descriptions
Terminal
Function
Notes
1
Line 1 power
Switched by SCR
2
Line 2 power / neutral
Internal bus-bar to terminal 4
3
T1 Load power
Output from SCR
4
T2 Load power
Internal bus-bar to terminal 2
5
DC+ / AC command signal
DA10-xx(C,F)x-xxxx takes DC
6
DC- / AC command signal
DA10-xxKx-xxxx takes AC
7, 8, 9, 10
Not used / no connection
DIN-A-MITE Style B
Single-phase Output
Connection Locations DIN-A-MITE Style B (Single-phase Output) shows terminals 1-6 for Power and Load Connections and terminals 7-16 for Command Signal Inputs. Terminals 1, 2 are for Line connections. Terminals 3, 4 are for Load connections. Terminals 5, 6 are for Command Signal Inputs.
3-phase, 2-leg Output
Connection Locations DIN-A-MITE Style B (3-phase, 2-leg Output) shows terminals 1-6 for Power and Load Connections and terminals 7-16 for Command Signal Inputs. Terminals 1, 2, 3 are for Line connections. Terminals 4, 5, 6 are for Load connections. Terminals 7-16 are for Command Signal Inputs.
Grounding: Use a grounding conductor terminal plate (fork terminal) having upturned lugs or the equivalent to hold the wire in position. Use 6 mm² (10 AWG) wire.
Terminal Descriptions
Power and Load Connections D(B or C)1x-xxxx-xxxx
Terminal
Function
Notes
1
Not used / no connection
2
Line 1 power
Switched by SCR
3
Line 2 power / neutral
Internal bus-bar to terminal 6
4
Not used / no connection
5
T1 Load power
Output from SCR
6
T2 Load power
Internal bus-bar to terminal 3
Power and Load Connections D(B or C)2x-xxxx-xxxx or D(B or C)8x-xxxx-xxx
Terminal
Function
Notes
1
Line 1 power
Switched by SCR 1
2
Line 2 power / neutral
Internal bus-bar to terminal 5
3
Line 3 power
Switched by SCR 2
4
T1 Load power
Output from SCR 1
5
T2 Load power
Internal bus-bar to terminal 2
6
T3 Load power
Output from SCR 2
Power and Load Connections D(B or C)3x-xxxx-xxxx or D(B or C)9x-xxxx-xxxx
Terminal
Function
Notes
1
Line 1 power
Switched by SCR 1
2
Line 2 power
Switched by SCR 2
3
Line 3 power
Switched by SCR 3
4
T1 Load power
Output from SCR 1
5
T2 Load power
Internal bus-bar to terminal 2
6
T3 Load power
Output from SCR 3
NOTE: For D(B or C)(8 or 9) models. All zones can be on same phase input or multi-phase input. Each zone is controlled independent of other zones.
DIN-A-MITE Style C
Single phase, Output
Connection Locations DIN-A-MITE Style C (Single phase, Output) shows terminals 1-6 for Power and Load Connections and terminals 7-20 for Signal, Alarm, and Current Transformer inputs. Terminals 1, 2 are for Line connections. Terminals 3, 4 are for Load connections. Terminals 7-12 are for Signal inputs (Zone 1, 2, 3, Gain, Bias, Limit). Terminals 13, 14 are for Alarm Output. Terminals 15-20 are for Current Transformer (CT) inputs.
3-phase, 2-leg Output
Similar terminal layout for Line 1, 2, 3 and Load T1, T2, T3, with signal, alarm, and CT inputs.
3-phase, 3-leg Output, Four Wire Wye
Similar terminal layout for Line 1, 2, 3 and Load T1, T2, T3, with neutral, signal, alarm, and CT inputs.
Fan Cooled
Describes fan power terminals and signal/alarm/CT inputs.
Grounding: Use a grounding conductor terminal plate (fork terminal) having upturned lugs or the equivalent to hold the wire in position. Use 6 mm² (10 AWG) wire.
Terminal Descriptions
Command Signal Inputs DIN-A-MITE Style B and Style C
Terminal
Models
Command Signal Input
7
Dx(1,2,3)x-xx(C,F)x-xxxx Dx(1,2,3)x-xxKx-xxxx DC1x-xx(L,P)x-xxxx or DC(1,2,3)x-xxSx-xxxx
DC1x-xxLx-xxxx or Dxxx-xxxx-(H,S)xxx All other models
Alarm 100-240AC 300mA max.
16
DC1x-xxLx-xxxx or Dxxx-xxxx-(H,S)xxx All other models
Not used / no connection
17,18,19,20
DCxx-xxxx-xxxx
Current transformer input
Not used / no connections
DIN-A-MITE Style D
Connection Locations DIN-A-MITE Style D: Single Phase, Output and Input Wiring. Describes Line 1, 2, Heater, Neutral terminals. Mentions 4 to 20mA input, 4.5 to 32Vdc input, Vac input. Also describes Alarm/Current Transformer Output and Current Sensing/Non-latching Alarm options.
Terminal Descriptions
Terminal
Function
Notes / Model
1
Line 1 power
Switched by SCR 1
2
T1 Load power
Output from SCR
3
DC+ / AC command signal
DD10-xx(C,F)x-xxxx takes DC, DD10-xxKx-xxxx takes AC
4
DC- / AC command signal
5
Not used / no connection
DD10-xxxx-0xxx
6
Current transformer output
DD10-xxxx-1xxx
Alarm 100-240 AC 300mA max.
DD10-xxxx-Sxxx
Not used / no connection
DD10-xxxx-0xxx
Current transformer output
DD10-xxxx-1xxx
Alarm 100-240 AC 300mA max.
DD10-xxxx-Sxxx
Mounting Information
DIN-A-MITE Style A
Dimensions: Front 34 mm (1.34 in) for #8 Fastener (M4), 49 mm (1.92 in) for Grounding Hardware (#6). Overall height 83 mm (3.25 in). Rail mounting: DIN-EN 50022 35 mm by 7.5 mm Rail (Clipping Distance 34.7 mm (1.37 in) to 35.3 mm (1.39 in)).
DIN-A-MITE Style B
Dimensions: Front 54 mm (2.11 in), 46 mm (1.81 in), 38 mm (1.51 in) for #8 fastener (M4). Overall height 83 mm (3.25 in), 49 mm (1.92 in), 49 mm (1.91 in). Rail mounting: DIN-EN 50022 35 mm by 7.5 mm rail (clipping distance 34.7 mm (1.366 in) to 35.3 (1.390 in)).
DIN-A-MITE Style C
DCxT
Front: 102 mm (4.0 in) minimum clearance for air flow (top and bottom). Panel Opening Outline dimensions provided. Ground lug (2-8 GA). Drill 5.8 mm (0.228 in) (8) holes for M5 screws with M5 washers. Heatsink Outline and reference dimensions provided. 10 mm (0.4 in) minimum clearance for air flow (both sides).
DCx(0,1,2,3)
Front: 38 mm (1.51 in), 46 mm (1.81 in), 54 mm (2.11 in) allowance for M4 (#8 Fastener). Rail mounting: DIN-EN 50022 35 by 7.5 mm rail (clipping distance = 34.7 to 35.3 mm [1.366 to 1.390 in]).
DIN-A-MITE Style D
Dimensions: 67 mm (2.63 in), 67 mm (2.63 in), 61 mm (2.38 in). Allowance for No. 10 Fastener Metric = M5. 13 mm (0.50 in) allowance.
Wiring Instructions
Choose line and load wire size based on National Electric Code NFPA 70 or local electric codes for the current to be carried. When using 90°C wire, choose wire gauge based on 75°C table. See the table below for ground wire size recommendations.
Branch Circuit Protection Rating
Ground Wire Size
15 Amps
14 AWG
20 Amps
12 AWG
30 - 60 Amps
10 AWG
100 Amps
8 AWG
100 - 125 Amps
6 AWG
Wiring Instructions (Continued)
Line and Load Torquing Guidelines
Properly torque line and load terminals, hold torque for 30 seconds.
Re-torque after 48 hours to minimize wire cold flow.
Re-torque line and load terminals every three to six months.
Control Signal Torque
4.4 in.-lb. (0.5 Nm)
Line Power, Load and Earth Ground Torque
Model Line/Load Driver
Line, Load & Earth Ground
Earth Ground Driver
DIN A
1/4 in. Flat blade 12 in.-lbs. (1.4 Nm)
1/4 in. Flat blade or hex
DIN B
Pozi drive #2 12 in.-lbs. (1.4 Nm)
1/4 in. Flat blade or hex
DIN C
Pozi drive #2 24 in.-lbs. (2.7 Nm)
1/4 in. Flat blade
DIN D
3/16 in. Hex 85 in.-lbs. (9.6 Nm)
3/8 in. Hex
Fusing
NOTE: Use recommended fusing to meet 200KA SCCR, type 1 and 2 approved. Other fusing limits SCCR to 5KA per UL508A and NEC guidelines.
See "UL® and NEC® Requirements for Electrical Panel Assemblies Marked with Fault Current or SCCR" on the Watlow website for more information.
200kA Fusing
Use recommended fusing to meet 200KA SCCR, type 1 and 2 approved. Other fusing limits SCCR to 5KA per UL508A and NEC guidelines.
DIN-A-MITE Style A, Style B Recommended Fuses
Fuse
Watlow Semiconductor
Eaton® Semiconductor
Watlow Combination
Eaton® Combination
20A
17-8020
FWC20A10F
0808-0325-0020
DFJ20
25A
17-8025
FWC25A10F
0808-0325-0025
DFJ25
32A
17-8030
FWP32A14F
0808-0325-0030
DFJ30
40A
17-8040
FWP40A14F
0808-0325-0040
DFJ40
50A
17-8050
FWP50A14F
0808-0325-0050
DFJ50
Recommended Fuse and Fuse Holder (Style A/B)
Fuse
Watlow
Mersen® (formerly Ferraz)®
Eaton® Combination
15 to 30A
17-5110
USM1i
CH30J1i
35 to 60A
17-5114
USM141i
CH60J1i
DIN-A-MITE Style C Recommended Fuses
Semiconductor Fuses for Applications Through 600V ~ (ac):
Semiconductor Fuse Rating
Watlow Fuse P/N
Eaton® Fuse P/N
Watlow Holder P/N
Mersen® Holder P/N
30A
17-8030
FWP30A14F
17-5114
USM141i
40A
17-8040
FWP40A14F
17-5114
USM141i
50A
17-8050
FWP50A14F
17-5114
USM141i
63A
17-8063
FWP63A22F
17-5122
US22i
80A
17-8080
FWP80A22F
17-5122
US22i
100A
17-4100
FWP100A22F
17-5122
US22i
Combination Fuses for Applications Through 600V ~ (ac):
Semiconductor use Rating
Watlow Fuse P/N
Eaton® Fuse P/N
Watlow Holder P/N
Mersen® Holder P/N
30A
0808-0325-0030
DFJ30
0808-0326-1530
CH30J1i
40A
0808-0325-0040
DFJ40
0808-0326-3560
CH60J1i
50A
0808-0325-0050
DFJ50
0808-3026-3560
CH60J1i
63A
0808-0325-0060
DFJ60
0808-3026-3560
CH60J1i
80A
0808-0325-0080
DFJ80
0808-0326-7010
J60100-1CR
100A
0808-0325-0100
DFJ100
0808-0326-7010
J60100-1CR
DIN-A-MITE Style D Replacement Fuses
Watlow
0808-0096-0000
Eaton
170N3437
Torque for Replacement Fuses 40 in-lbs (4.52 Nm)
EMC Filters
Filters for EMC conducted emissions compliance.
Description
Crydom® Filter
Watlow Filter
Single-phase, 230V~ (ac)
1F25
14-0019
Three-phase, 440V~ (ac)
3F20
14-0020
Agency Approval and Regulatory
cULus® 508 Listed File E73741
cULus® Listed to C22.2 No. 14
IP 20 with all covers in place
Utilization Category: AC-51, AC-55b, AC-56a
SCCR rating 200,000A up to 480 VAC
DCxT models UL® 50 Type 4x approved
Class 1 Division 2 Groups A, B, C, D Temperature Code T4 Hazardous Locations
If you encounter a problem with your Watlow controller, review your configuration information to verify that your selections are consistent with your application: inputs, outputs, alarms, limits, etc. If the problem persists, you can get technical assistance from your local Watlow representative (see back cover), by e-mailing your questions to wintechsupport@watlow.com or by dialing +1 (507) 494-5656 between 7 a.m. and 5 p.m. Central Time USA & Canada. Ask for an Applications Engineer. Please have the complete model number available when calling.
How to Reach Us
Watlow Electric Manufacturing Company 12001 Lackland Road St. Louis, MO 63146
Adobe PDF Library 17.0 Adobe InDesign 18.0 (Windows)
Related Documents
WATLOW PM3 LEGACY PID Controller Quick Start Guide Quick start guide for the WATLOW PM3 LEGACY PID Controller, covering panel mounting, sensor input connection, output wiring, power connection, and basic keypad/menu operations. Includes CE Declaration of Conformity details.
Watlow PM Plus 1/8 DIN Controller Quick Start Guide A quick start guide for the Watlow PM Plus 1/8 DIN Controller, covering panel mounting, sensor input connection, wiring outputs, power connection, and setup procedures for sensor input, outputs, and control loops. Includes CE Declaration of Conformity.
Watlow PM Plus 1/4 DIN Controller Quick Start Guide A quick start guide for the Watlow PM Plus 1/4 DIN controller, covering controller interface, mounting, sensor input, output wiring, power connection, sensor setup, output setup, alarm setup, and control loop mode.
Watlow Temperature Sensors and Accessories Catalog A comprehensive catalog from Watlow detailing a wide range of industrial temperature sensors, including thermocouples, RTDs, and thermistors, alongside essential accessories such as fittings, thermowells, connectors, and transmitters. The document provides detailed product specifications, safety guidelines, and application information for industrial and commercial use.
Watlow EZ-ZONE PM User's Guide: Limit Controller Models Comprehensive user's guide for Watlow EZ-ZONE PM series limit controllers, covering installation, operation, setup, features, and troubleshooting for industrial temperature control applications.
Watlow PM LEGACY Express Limit Controller User Guide User guide for the Watlow PM LEGACY Express Limit Controller (PM3 and PM6 models), detailing features, installation, wiring, operation, and specifications for industrial temperature control applications.