User Guide for EMERSON models including: Rosemount 248 Temperature Transmitter, Wireless Temperature Transmitter, 00825-0200-4248
Quick Start Guide 00825-0200-4248, Rev FA May 2020 Rosemount™ 248 Wireless Temperature Transmitter
Quick Start Guide. 00825-0200-4248, Rev GA. February 2021. Rosemount™ 248 Wireless Temperature. Transmitter ...
File Info : application/pdf, 28 Pages, 1.37MB
DocumentDocumentQuick Start Guide 00825-0200-4248, Rev GA February 2021 RosemountTM 248 Wireless Temperature Transmitter Quick Start Guide February 2021 Contents About this guide...........................................................................................................................3 Wireless considerations................................................................................................................6 Physical installation...................................................................................................................... 7 Verify operations........................................................................................................................11 Reference information............................................................................................................... 14 Power module replacement....................................................................................................... 17 Product certifications................................................................................................................. 19 Declaration of Conformity..........................................................................................................23 China RoHS................................................................................................................................ 26 2 Emerson.com/Rosemount February 2021 Quick Start Guide 1 About this guide This guide provides basic guidelines to install the Rosemount 248 Wireless Temperature Transmmitter. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, or installations. Refer to the Rosemount 248 Temperature Transmitter Reference Manual for more instruction. The manual and this guide are also available electronically at Emerson.com/Rosemount. 1.1 Safety messages WARNING Failure to follow these installation guidelines could result in death or serious injury. Ensure only qualified personnel perform the installation. Explosions Explosions could result in death or serious injury. Installation of device in an explosive environment must be in accordance with appropriate local, national, and international standards, codes, and practices. Review the Hazardous Locations Certifications for any restrictions associated with a safe installation. Process leaks Process leaks could result in death or serious injury. Install and tighten thermowells and sensors before applying pressure. Do not remove the thermowell while in operation. Electrical shock Electrical shock could cause death or serious injury. Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock. Unless marked, the conduit/cable entries in the housing use a ½14 NPT thread form. Entries marked "M20" are M20 × 1.5 thread form. On devices with multiple conduit entries, all entries will have the same thread form. Only use plugs, adapters, glands, or conduit with a compatible thread form when closing these entries. When installing in a hazardous location, use only appropriately listed or Ex certified plugs, glands, or adapters in cable/conduit entries. Quick Start Guide 3 Quick Start Guide February 2021 WARNING This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. This device must be installed to ensure a minimum antenna separation distance of 8-in. (20 cm) from all persons. The power module may be replaced in a hazardous area. The power module has surface resistivity greater than one gigaohm and must be properly installed in the wireless device enclosure. Care must be taken during transportation to and from the point of installation to prevent electrostatic charge build-up. Physical access Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users' equipment. This could be intentional or unintentional and needs to be protected against. Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users' assets. This is true for all systems used within the facility. NOTICE Power module considerations (Green Power Module, model number 701PGNKF) The green power module with the wireless unit contains one "D" size primary lithium-thionyl chloride battery (model number 701PGNKF). Each battery contains approximately 5.0 grams of lithium. Under normal conditions, the battery materials are self-contained and are not reactive as long as the batteries and the pack integrity are maintained. Care should be taken to prevent thermal, electrical or mechanical damage. Contacts should be protected to prevent premature discharge. Battery hazards remain when cells are discharged. Power modules should be stored in a clean and dry area. For maximum battery life, storage temperature should not exceed 86 °F (30 °C). 4 Emerson.com/Rosemount February 2021 Quick Start Guide NOTICE Shipping considerations for wireless products (lithium batteries: Green Power Module, model number 701PGNKF) The unit was shipped to you without the power module installed. Remove the power module prior to shipping. Each power module contains one "D" size primary lithium battery. Primary lithium batteries are regulated in transportation by the U.S. Department of Transportation, and are also covered by IATA (International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure compliance with these or any other local requirements. Consult current regulations and requirements before shipping. Quick Start Guide 5 Quick Start Guide February 2021 2 Wireless considerations 2.1 Power up sequence The Rosemount 248 Wireless Transmitter and all other devices should be installed only after the Wireless Gateway ("Gateway") has been installed and is functioning properly. Wireless devices should also be powered up in order of proximity from the Gateway, beginning with the closest. This will result in a simpler and faster network installation. Enable Active Advertising on the Gateway to ensure new devices join the network faster. For more information see the Emerson Wireless Gateway Reference Manual. 2.2 Antenna position The internal antenna is designed for multiple mounting orientations. The transmitter should be mounted according to best practices for your temperature measurement application. The transmitter should be approximately 3 ft. (1 m) from any large structure or building to allow clear communication to other devices. 2.3 Field Communicator connections The power module must be installed in the device for the Field Communicator to interface with the transmitter. The Field Communicator connections are located on the Green Power Module. To communicate to the transmitter, begin by removing the power module cover. This will expose the HART® communication terminals located on the Green Power Module. Next, connect the Field Communicator leads to the COMM port connections on the Green Power Module. This transmitter uses the Green Power Module; order model number 701PGNKF. The power module is keyed and can only be inserted in one orientation. Field communication with this device requires a HART-based Field Communicator. Refer to Figure 2-1 for instructions on connecting the Field Communicator to the transmitter. Figure 2-1: Field Communicator Connection 6 Emerson.com/Rosemount February 2021 Quick Start Guide 3 Physical installation The transmitter can be installed in one of two configurations: Direct Mount, where the sensor is connected directly to the transmitter conduit entry, or Remote Mount, where the sensor is mounted separately from the transmitter housing, then connected to the transmitter via conduit. Choose the installation sequence that corresponds to the mounting configuration. Upon installation of the transmitter, ensure that the conduit entry has an installed conduit fitting or cable gland with approved thread sealant. 3.1 Direct mount The direct mount installation should not be used when installing with a Swagelok® fitting. Procedure 1. Remove the transmitter enclosure cover. 2. Remove the LCD display (if applicable). 3. Loosen the captive screws and remove LCD display adapter plate (if applicable). Figure 3-1: Exploded View of LCD Display Assembly 4. Attach the sensor to the transmitter housing using the threaded conduit entry. Be sure to use an approved thread sealant on all connections. 5. Attach the sensor wiring to the terminals as indicated on Figure 5-1. 6. Reattach and secure LCD display adapter plate to 5 in-lb of torque (if applicable). 7. Reattach the LCD display (if applicable). 8. Reattach and tighten the transmitter enclosure cover. 9. Remove the power module cover. 10. Connect the Green Power Module. 11. Reattach and tighten the power module cover. Quick Start Guide 7 Quick Start Guide February 2021 12. Always ensure a proper seal by installing the electronics housing cover(s) so that polymer contacts polymer (i.e. no O-ring visible). Use Rosemount O-rings. 13. Provide 1.75-in. (45 mm) of clearance for units without an LCD display. Provide 3-in. (76 mm) of clearance for units with an LCD display for cover removal. Figure 3-2: Direct Mount Dimensions are in inches (millimeters). Note Wireless devices should be powered up in order of proximity from the Gateway, beginning with the closest device to the Gateway. This will result in a simpler and faster network installation. 3.2 Remote mount Procedure 1. Remove the transmitter enclosure cover. 2. Remove the LCD display (if applicable). 3. Loosen the captive screws and remove LCD display adapter plate (if applicable). Refer to Figure 3-3. 8 Emerson.com/Rosemount February 2021 Quick Start Guide Figure 3-3: Exploded View of LCD Display Assembly 4. Run wiring (and conduit, if necessary) from the sensor to the transmitter. Note Use an ½-in. NPT when mating conduit to the transmitter. 5. Pull the wiring through the threaded conduit entry of the transmitter. 6. Attach the sensor wiring to the terminals as indicated on Figure 5-1. 7. Reattach and secure LCD display adapter plate to 5 in-lb of torque (if applicable). 8. Reattach the LCD display (if applicable). 9. Reattach and tighten the transmitter enclosure cover. 10. Remove the power module cover. 11. Connect the Green Power Module. 12. Reattach and tighten the power module cover. 13. Always ensure a proper seal by installing the electronics housing cover(s) so that polymer contacts polymer (i.e. no O-ring visible). Use Rosemount O-rings. 14. Provide 1.75-in. (45 mm) of clearance for units without an LCD display. Provide 3-in. (76 mm) of clearance for units with an LCD display for cover removal. Quick Start Guide 9 Quick Start Guide Figure 3-4: Remote Mount February 2021 Dimensions are in inches (millimeters). Note Wireless devices should be powered up in order of proximity from the Wireless Gateway, beginning with the closest device to the Gateway. This will result in a simpler and faster network installation. 10 Emerson.com/Rosemount February 2021 Quick Start Guide 4 Verify operations Operations can be verified in four locations: · at the device via the Local Display · using the Field Communicator · at the Gateway's integrated web interface · using AMS Wireless Configurator or AMS Device Manager 4.1 Local display During normal operation, the LCD display will display the PV value at the configured update rate. For Device Status screens, see LCD display screen messages on Rosemount 248 Wireless Reference Manual. 4.2 Field Communicator For HART® communication, a Rosemount 248 Wireless DD is required. To obtain the latest DD, visit the Emerson Easy Upgrade site at: Emerson.com/Rosemount/Device-Install-Kits The communication status may be verified in the wireless device using the following Fast Key sequence. Table 4-1: Fast Key Sequence Function Communications Key sequence 3, 4 Menu items Comm Status, Join Mode, Available Neighbors, Advertisement, Join Attempts 4.3 Emerson Wireless Gateway In the integrated web interface from the Gateway, navigate to the Explorer Status page. This page shows whether the device has joined the network and if it is communicating properly. Note It may take several minutes for the device to join the network. If the device joins the network and immediately has an alarm present, it is likely due to sensor configuration. Check the sensor wiring (see Figure 5-1) and configuration table (Table 5-1). Quick Start Guide 11 Quick Start Guide Figure 4-1: Wireless Gateway Network Settings February 2021 4.4 AMS Wireless Configurator When the device has joined the network, it will appear in the Wireless Configurator window as illustrated in figure below. For HART® communication, a Rosemount 248 Wireless DD is required. To obtain the latest DD, visit the Emerson Easy Upgrade site at: Emerson.com/Rosemount/Device-Install-Kits 12 Emerson.com/Rosemount February 2021 Figure 4-2: AMS Wireless Configurator Quick Start Guide 4.5 Troubleshooting If the device is not joining to the network, check to make sure that you have a power supply in your device. If the device is not joined to the network after power up, verify the correct configuration of the Network ID and Join Key, and verify that Active Advertising has been enabled on the Wireless Gateway. The Network ID and Join Key in the device must match the Network ID and Join Key of the Gateway. The Network ID and Join Key may be obtained from the Gateway on the Setup Network Settings page on the web server (see Figure 4-1). The Network ID and Join Key may be changed in the wireless device by using the following Fast Key sequence. Function Join Device to Network Key sequence 2,1,1 Menu items Join to Network Quick Start Guide 13 Quick Start Guide 5 Reference information Figure 5-1: Sensor Wiring Thermocouple and mV February 2021 4-Wire RTD and 3-Wire RTD and 2-Wire RTD and Figure 5-2: Sensor Connections 2-wire RTD and 3-wire RTD and 4-wire RTD and T/C and mV 14 Emerson.com/Rosemount February 2021 Quick Start Guide Note Emerson provides 4-wire sensors for all single element RTDs. Use these RTDs in 3- or 2-wire configurations by leaving the unneeded leads disconnected and insulated with electrical tape. Table 5-1: WirelessHART® Fast Key Sequences Function Device Information Guided Setup Manual Setup Wireless Configuration Sensor Calibration Key sequence 1, 7 2, 1 2, 2 2, 2, 1 3, 5, 2 Menu items Identification, Revisions, Radio, Security Join Device to Network, Configure Update Rate, Configure Sensor, Calibrate Sensor Wireless, Process Sensor, Percent of Range, Device Temperatures, Device Information, Other Network ID, Join to Network, Broadcast Info Sensor Value, Sensor Status, Current Lower Trim, Current Upper Trim, Lower Sensor Trim, Upper Sensor Trim, Recall Factory Trim Figure 5-3: RTD Lead Wire Configuration per IEC 60751 Note To configure a single element, 4-wire RTD as a 3-wire system, connect only one white lead. Insulate or terminate the unused white lead in a manner that prevents shorting to the ground. Quick Start Guide 15 Quick Start Guide February 2021 To configure a single element, 4-wire RTD as a 2-wire system, connect matching colored wires first and then connect the paired wires to the terminal. Figure 5-4: Thermocouple Lead Wire Configurations Type J K T IEC 60584 thermocouple colors POS(+) NEG(-) Black White Green White Brown White ASTM E-230 thermocouple colors POS(+) NEG(-) White Red Yellow Red Blue Red Note Dual thermocouple sensors are shipped with one pair of the wires shrink wrapped together. 16 Emerson.com/Rosemount February 2021 Quick Start Guide 6 Power module replacement Expected power module life is 10 years at reference conditions.(1) When power module replacement is required, remove the cover and remove the Green Power Module. Replace the Green Power Module (part number 701PGNKF) and replace the cover. Tighten to specification and verify operation. Figure 6-1: Exploded Power Module View 6.1 Handling considerations The Green Power Module with the wireless unit contains one "D" size primary lithium-thionyl chloride battery (Green Power Module, model number 701PGNKF). Each battery contains approximately 5.0 grams of lithium. Under normal conditions, the battery materials are self-contained and are not reactive as long as the batteries and the pack integrity are maintained. Care should be taken to prevent thermal, electrical or mechanical damage. Contacts should be protected to prevent premature discharge. Note Power modules should be stored in a clean and dry area. For maximum power module life, storage temperature should not exceed 86 °F (30 °C). (1) Reference conditions are 70° F (21° C), transmit rate of once per minute, and routing data for three additional network devices. Quick Start Guide 17 Quick Start Guide February 2021 CAUTION Use caution when handling the power module, it may be damaged if dropped from heights in excess of 20 feet. WARNING Battery hazards remain when cells are discharged. 6.2 Environmental considerations As with any battery, local environmental rules and regulations should be consulted for proper management of spent batteries. If no specific requirements exist, recycling through a qualified recycler is encouraged. Consult the material's safety data sheet for battery specific information. 6.3 Shipping considerations The unit was shipped to you without the power module installed. Remove the power module prior to shipping the unit. 18 Emerson.com/Rosemount February 2021 Quick Start Guide 7 Product certifications 7.1 7.2 7.3 7.4 7.5 7.5.1 Rev 1.12 European Directive Information A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. Ordinary Location Certification As standard, the transmitter has been examined and tested to determine that the design meets the basic electrical, mechanical, and fire protection requirements by a nationally recognized test laboratory (NRTL) as accredited by the Federal Occupational Safety and Health Administration (OSHA). Telecommunication compliance All wireless devices require certification to ensure that they adhere to regulations regarding the use of the RF spectrum. Nearly every country requires this type of product certification. Emerson is working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage. FCC and IC This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions: This device may not cause harmful interference. This device must accept any interference received, including interference that may cause undesired operation. This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons. North America The US National Electrical Code® (NEC) and the Canadian Electrical Code (CEC) permit the use of Division marked equipment in Zones and Zone marked equipment in Divisions. The markings must be suitable for the area classification, gas, and temperature class. This information is clearly defined in the respective codes. USA I5 USA Intrinsically Safe Certificate 70008071 Quick Start Guide 19 Quick Start Guide February 2021 Standards FM 3600: 2011; FM 3610: 2010; FM 3611: 2004; UL 61010-1: 2012; UL 50E: 2012; ANSI/IEC 60529:2004 Markings Intrinsically Safe: CL I, DIV 1, GP A, B, C, D; CL I, DIV 2, GP A, B, C, D; Class I, Zone 0, AEx ia IIC T4/T5 Ga; T4 (-50 °C Ta +70 °C); T5 (-50 °C Ta +40 °C); WHEN INSTALLED PER ROSEMOUNT DWG 00249-2020; TYPE 4X, IP66/67 See Table 7-1 for entity parameters. 7.5.2 Special Condition for Safe Use (X) Battery exchange: The battery module can be changed inside hazardous gasexplosive locations. During battery change it must be assured that the connections are free from dust or dirt. Canada I6 Canada Intrinsically Safe Certificate 70008071 Standards CSA C22.2 No. 0-10; CSA C22.2 No. 94.2-07 (R2012); CSA C22.2 No. 213-M1987 (R2013); CAN/CSA-60079-0-11; CAN/ CSA-60079-11-14; CAN/CSA C22.2 No. 60529-05; CAN/CSAC22.2 No. 61010-1-12 Markings Intrinsically Safe: CL I, DIV 1, GP A, B, C, D; CL I, DIV 2, GP A, B, C, D; Ex ia IIC T4/T5 Ga; T4 (50 °C Ta +70 °C); T5 (50 °C Ta +40 °C); WHEN INSTALLED PER ROSEMOUNT DWG 00249-2020; TYPE 4X, IP66/67 See Table 7-1 for entity parameters. Special Condition for Safe Use (X) Battery exchange: The battery module can be changed inside hazardous gasexplosive locations. During battery change it must be assured that the connections are free from dust or dirt. 7.6 Europe I1 ATEX Intrinsic Safety Certificate Baseefa14ATEX0359X Standards EN IEC 60079-0: 2018; EN 60079-11: 2012 Markings II 1 G Ex ia IIC T4/T5 Ga; T4 (60 °C Ta +70 °C); T5 (60 °C Ta +40 °C) See Table 7-1 for entity parameters. 20 Emerson.com/Rosemount February 2021 Quick Start Guide Special Condition for Safe Use (X) The plastic enclosure may present a potential electrostatic ignition hazard and must not be rubbed or cleaned with a dry cloth. 7.7 International I7 IECEx Intrinsic Safety Certificate IECEx BAS 14.0158X Standards IEC 60079-0: 2017; IEC 60079-11: 2011 Markings Ex ia IIC T4/T5 Ga; T4 (-60 °C Ta +70 °C); T5 (-60 °C Ta +40 °C) See Table 7-1 for entity parameters. Special Condition for Safe Use (X) The plastic enclosure may present a potential electrostatic ignition hazard and must not be rubbed or cleaned with a dry cloth. 7.8 Brazil I2 INMETRO Intrinsic Safety Certificate UL-BR 15.0222X Standards ABNT NBR IEC 60079-0: 2008 + Corrigendum 1:2011; ABNT NBR IEC 60079-11: 2009 Markings Ex ia IIC T4/T5 Ga; T4 (60 °C Ta +70 °C); T5 (60 °C Ta +40 °C) See Table 7-1 for entity parameters. Special Condition for Safe Use (X) The plastic enclosure may present a potential electrostatic ignition hazard and must not be rubbed or cleaned with a dry cloth. 7.9 China I3 NEPSI Intrinsic Safety Certificate GYJ20.1147X Standards GB3836.1-2010, GB3836.4-2010, GB3836.20-2010 Markings Ex ia IIC T4/T5 Ga; T4 (60 °C Ta +70 °C); T5 (60 °C Ta +40 °C) See Table 7-1 for entity parameters. Quick Start Guide 21 Quick Start Guide February 2021 Special Conditions for Safe Use (X) 1. Non-metallic parts incorporated in the enclosure of the product shall only be cleaned with a damp cloth to avoid electrostatic charge. 2. Must use Rosemount Model 701PGNKF SmartPower Green Power Module provided by the manufacture. 7.10 Japan I4 TIIS Intrinsic Safety Certificate Markings CML 20JPN2243X Ex ia IIC T4, T5 Ga (-60 °C ~ +40/70 °C) See Table 7-1 for entity parameters. Special Conditions for Safe Use (X) 1. The plastic enclosure may present a potential electrostatic ignition hazard and must not be rubbed or cleaned with a dry cloth. 2. Power shall be provided only by a Model 701PGNKF SmartPower Green Power Module. 7.11 EAC IM Technical Regulation Customs Union (EAC) Intrinsic Safety Markings 0Ex ia IIC T4,T5 Ga X, T5 (60 °C Ta +40 °C), T4 (60 °C Ta +70 °C); IP66/IP68 Specific Condition for Safe Use (X) See certificate for special conditions. Table 7-1: Entity Parameters Voltage UO Current IO Power PO Capacitance CO Inductance LO 6.6 V 26.2 mA 42.6 mW 11 F 25 mH 22 Emerson.com/Rosemount February 2021 8 Declaration of Conformity Quick Start Guide EU Declaration of Conformity No: RMD 1082 Rev. L We, Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA declare under our sole responsibility that the product, RosemountTM 248 Wireless Temperature Transmitter manufactured by, Rosemount, Inc. 8200 Market Boulevard Chanhassen, MN 55317-9685 USA to which this declaration relates, is in conformity with the provisions of the European Union Directives, including the latest amendments, as shown in the attached schedule. Assumption of conformity is based on the application of the harmonized standards and, when applicable or required, a European Union notified body certification, as shown in the attached schedule. (s ig n ature) Chris LaPoint (name) Vice President of Global Quality (function) 24-Feb-2020 (date of issue) Page 1 of 3 Quick Start Guide 23 Quick Start Guide February 2021 EU Declaration of Conformity No: RMD 1082 Rev. L EMC Directive (2014/30/EU) Harmonized Standards: EN 61326-1: 2013 EN 61326-2-3: 2013 Radio Equipment Directive (RED) (2014/53/EU) Harmonized Standards: EN 300 328 V2.1.1 EN 301 489-1 V2.2.0 EN 301 489-17 V3.2.0 EN 61010-1: 2010 EN 62479: 2010 ATEX Directive (2014/34/EU) Rosemount 248 Wireless Temperature Transmitter (Polymer housing) Baseefa14ATEX0359X Intrinsic Safety Certificate Equipment Group II, Category 1 G Ex ia IIC T4/T5 Ga Harmonized Standards: EN IEC 60079-0: 2018, EN60079-11: 2012 Page 2 of 3 24 Emerson.com/Rosemount February 2021 Quick Start Guide EU Declaration of Conformity No: RMD 1082 Rev. L ATEX Notified Body SGS FIMCO OY [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland ATEX Notified Body for Quality Assurance SGS FIMCO OY [Notified Body Number: 0598] P.O. Box 30 (Särkiniementie 3) 00211 HELSINKI Finland Page 3 of 3 Quick Start Guide 25 Quick Start Guide 9 China RoHS February 2021 26 Emerson.com/Rosemount February 2021 Quick Start Guide Quick Start Guide 27 *00825-0200-4248* Quick Start Guide 00825-0200-4248, Rev. GA February 2021 Emerson Automation Solutions 6021 Innovation Blvd. Shakopee, MN 55379, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RFQ.RMD-RCC@Emerson.com Latin America Regional Office Emerson Automation Solutions 1300 Concord Terrace, Suite 400 Sunrise, FL 33323, USA +1 954 846 5030 +1 954 846 5121 RFQ.RMD-RCC@Emerson.com Asia Pacific Regional Office Emerson Automation Solutions 1 Pandan Crescent Singapore 128461 +65 6777 8211 +65 6777 0947 Enquiries@AP.Emerson.com North America Regional Office Emerson Automation Solutions 8200 Market Blvd. Chanhassen, MN 55317, USA +1 800 999 9307 or +1 952 906 8888 +1 952 949 7001 RMT-NA.RCCRFQ@Emerson.com Europe Regional Office Emerson Automation Solutions Europe GmbH Neuhofstrasse 19a P.O. Box 1046 CH 6340 Baar Switzerland +41 (0) 41 768 6111 +41 (0) 41 768 6300 RFQ.RMD-RCC@Emerson.com Middle East and Africa Regional Office Emerson Automation Solutions Emerson FZE P.O. Box 17033 Jebel Ali Free Zone - South 2 Dubai, United Arab Emirates +971 4 8118100 +971 4 8865465 RFQ.RMTMEA@Emerson.com Linkedin.com/company/EmersonAutomation-Solutions Twitter.com/Rosemount_News Facebook.com/Rosemount Youtube.com/user/ RosemountMeasurement ©2021 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property of their respective owners.