Description
The Wattstopper PLUS Wireless Manager is the central intelligence point in the system for wireless devices. It collects information from photo sensors, occupancy sensors, and wallstations to enable multiple lighting control strategies. It then determines appropriate brightness levels or ON/OFF status for each luminaire and zone.
? This symbol indicates DC voltage.
Specifications
Specification | Value |
---|---|
Voltage | 48VDC, via Power over Ethernet (PoE) |
Current Consumption | 0.7A |
Wireless Range | 30 m (100 ft) line of sight, 15.2 m (50 ft) through standard walls |
Radio Frequency Range | 2405-2480 MHz |
Channel Space | 5MHz |
Modulation Type | O-QPSK |
Transmit Power | 13.40dBm EIRP (max) |
Operating Temperature | 32° to 104°F (0° to 40°C) |
Certifications | UL/cUL Listed, Energy Management Equipment (UL 916), CE, FCC Part 15/ICES-003, Class B |
EMC Standards | EN 61000-4-2, EN 61000-4-4, EN 61000-4-5 |
[WEEE Symbol] This product bears the selective sorting symbol for Waste electrical and electronic equipment (WEEE). This means that this product must be handled pursuant to European directive 2012/19/EU in order to be recycled or dismantled to minimize its impact on the environment. User has the choice to give his product to a competent recycling organization or to the retailer when he buys a new electrical or electronic equipment.
Product Safety
When using electrical equipment, basic safety precautions should always be followed, including the following:
- ⚠️ Do not mount near gas or electric heaters or let power supply cords touch hot surfaces.
- Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel.
- The use of accessory equipment is not recommended by Legrand as it may cause an unsafe condition.
- Do not use this equipment for other than the intended use.
Wireless System Overview
Diagram illustrating the Wattstopper PLUS System. It shows an 'Integrated Controller' connected to two 'Sensors' and two 'User Interfaces'. These components communicate wirelessly with the 'Wireless Manager'. Also visible are an 'SSU' and a 'Polaris Monitor'. A 'Wire Key' indicates that connections can be made via 'Ethernet' or 'Wireless'.
Mounting Instructions
Ceiling Mount
To mount on a ceiling tile: Cut a 85.7 x 31.8 mm (3.375 x 1.25 inches) hole in the ceiling tile. Assemble the Wireless Manager and the ceiling tile mount bracket. Push the ceiling tile mount bracket until it snaps into the groove. Place the assembled Wireless Manager through the ceiling tile hole. Place the upper bracket on to the Wireless Manager (above the ceiling tile from the plenum area) until it locks with the lower bracket installed.
Diagram Description: Ceiling mount installation showing an 'Upper Bracket', 'Ceiling Tile Mounting Bracket' with a 'Groove' and 'Locking Mechanism'. Dimensions for the 'Ceiling Opening' (85.7 x 31.8 mm or 3.375 x 1.25 inches) and screw hole size (Ø3.2 mm or 0.125 inch, 4x) are provided.
Wall Mount
To mount on a wall: Align the Wireless Manager screw holes with the screws on the Junction Box (Switch wall box) and slide slightly to secure it with the junction box. Using a needle nose plier, push down to open a hole and pull the Ethernet cable through.
Diagram Description: Wall mount installation showing the 'Wireless Manager' unit and its 'Wall Mount Screw Holes'. The process involves aligning screw holes with a junction box and using pliers to 'Push Down' to create an opening for the Ethernet cable.
Wiring
The Wireless Manager connects via Power over Ethernet (PoE). The maximum cable length is 100m (328 ft).
Diagram Description: A simple diagram showing the 'Wireless Manager' connected to 'PoE', with the maximum cable length specified.
Warranty Information
Wattstopper warranties its products to be free of defects in materials and workmanship for a period of five (5) years. There are no obligations or liabilities on the part of Wattstopper for consequential damages arising out of, or in connection with, the use or performance of this product or other indirect damages with respect to loss of property, revenue or profit, or cost of removal, installation or reinstallation.