AJAX FireProtect 2 (Heat / Smoke / CO) Jeweller

Wireless smoke, heat, and carbon monoxide detector. Featured with a built-in siren for alarm and event notification. It can operate as part of the Ajax security system and autonomously without a hub.

Find the detailed information on the device at: support.ajax.systems/en/manuals/fireprotect-2-heat-smoke-co/

The device is available in two options. The model with replaceable batteries has a mark RB in the name, and with non-replaceable batteries – the SB.

Key features

Accurate detection of threats

Advanced hardware and software

Operating principle

Smoke detection

FireProtect 2 detects smoke and does not react to water vapour thanks to a bispectral optical sensor with blue and infrared LEDs. LEDs emit light with different wavelengths, which allows the detector to determine the size of the volatile particles and react only to smoke.

The detector's smoke chamber is protected from dust, dirt, and insects. Even if dust enters and settles in the smoke chamber, it does not threaten or impair the detection. The optical system is designed so that non-volatile particles or insects cannot be in two beams simultaneously and cause a false alarm.

Detection of a rapid temperature rise

Two built-in thermistors are responsible for the reaction to temperature rise. Thermistors are located outside the detector for faster threat detection.

If the room temperature exceeds 64°C or increases at more than 10°C per minute, the detector recognizes this as a rapid temperature rise and raises the alarm. The temperature alarm can trigger even if there is no smoke in the room.

Detection of a dangerous concentration of carbon monoxide

A built-in chemical sensor with a service life of at least 10 years is responsible for detecting a dangerous concentration of carbon monoxide in FireProtect 2.

Carbon monoxide (CO) is a colourless, tasteless, and odourless gas produced due to incomplete fuel combustion in automobile engines and heating appliances that use coal or other natural fuels. For example, it can be made by fireplaces, boilers, or heating systems. In airtight or closed rooms with poor ventilation, life-threatening concentrations of carbon monoxide can accumulate.

Interconnected fire detectors alarms

The detector supports interconnected fire alarms. The feature activates built-in sirens of all Ajax fire detectors at the facility if at least one of them is triggered. In case of a fire, this allows alerting as many people as possible.

FireProtect 2 detectors have an improved interconnected fire alarm algorithm that activates all fire detectors' sirens within 20 seconds. The function is available only when the detectors operate with the hub.

Operation without a hub

FireProtect 2 detectors can be used without connecting to an Ajax hub. In this case, the detector notifies fire alarms with a built-in siren and LED indication but does not send a notification to the user's smartphone, Ajax Translator, or PRO Desktop.

Manual and automatic testing

FireProtect 2 regularly checks the status of batteries and built-in sensors. If a malfunction is detected, the hub will notify users and the monitoring station instantly. And the detector will turn on the light and sound alert by the built-in siren and LEDs. All detector states can be checked at any time in Ajax apps.

The detector supports manual testing mode. It is activated by pressing the device's front panel. The front panel has a mechanical button, which can be pressed either manually or with a floor mop. During the test, the built-in siren and testing of sensors are run. This allows the installer to test the device at any time and to demonstrate to the detector the light and sound indication of the detector for various types of alarms.

Autonomous operation

Two models of FireProtect 2 (Heat / Smoke / CO) are available - with replaceable and non-replaceable batteries. Detectors with replaceable batteries operate for up to 7 years with pre-installed CR123A batteries. After their discharge, the batteries can be replaced with new ones. The model with non-replaceable batteries works from built-in lithium batteries for at least 10 years. After the batteries are discharged, such a detector should be substituted with a new one.

Jeweller communication technology

Jeweller is a radio protocol for fast and reliable two-way communication between hubs and connected devices. The protocol provides a wireless radio communication range with FireProtect 2 up to 1700 meters. This communication range allows you to install detectors even on large-scale objects.

Jeweller is responsible for transmitting alarms and events. The radio protocol also provides an interconnected fire detectors alarm activation within 20 seconds in a system with any number of FireProtect 2. Thanks to Jeweller, users and the monitoring station can always see the current status of detectors in Ajax apps.

Quick pairing and installation

To install FireProtect 2, it is not necessary to disassemble the detector enclosure. Replaceable or non-replaceable batteries are pre-installed, and the SmartBracket mount is removed from the detector without tools.

SmartBracket mounting panel has a degree of freedom of 90°. This allows the installer to align the position of the device after installation.

The detector connects to the Ajax security system in less than a minute. An installer needs to open the Ajax app, scan the QR code, and add the device to the room and security group.

Technical specifications

Communication with control panel or range extender Jeweller communication technology Compatibility
Frequency bands
866.0-866.5 MHz
868.0-868.6 MHz
868.7-869.2 MHz
905.0-926.5 MHz
915.85-926.5 MHz
921.0-922.0 MHz
Depends on the region of sales.
Maximum effective radiated power (ERP)
Up to 20 mW
Communication range
up to 1,700 m
Without obstacles.
Hubs
Hub Plus
Hub 2 (2G)
Hub 2 (4G)
Hub Plus
Hub Hybrid (2G)
Hub Hybrid (4G)
Range extenders
ReX
ReX 2
Compliance with special fire standards Smoke detection Detection of dangerous temperature Carbon monoxide (CO) detection Additional features Anti-sabotage protection Detection of communication failure
EN 14604:2005/AC:2008
EN 50291-1:2018
Qmark
Sensitive element double-spectrum optical sensor
Recognizes smoke by the size of particles in the air.
Protection from false alarms
The detector does not react to water vapour.
Patented smoke chamber
Protects the smoke sensor from dust, dirt, and insects.
Sensitive element thermistor
According to the requirements for temperature detectors of A1 class of EN 54-5 and BS 5446-2 standards.
High temperature Alarm
at temperatures above 64°C
Rapid temperature rise Alarm
when the temperature rises more than 10°C in 1 minute or less
Sensitive element chemical CO sensor
Alarm if accumulated dose of CO is exceeded
more than 50 ppm (0.005%) – no more than in 90 minutes
more than 100 ppm (0.01%) – no more than in 40 minutes
more than 300 ppm (0.03%) – no more than in 3 minutes
Sensor life
10 years
In-built siren volume 85 dB (at a distance of 3 meters) Tampering alarm
Protection against spoofing device authentication
within 15 minutes
The time to detect communication loss depends on the number of undelivered data packages setting (specified in the Jeweller or Jeweller/Fibra settings). The polling interval is fixed at 300 seconds.
Interconnected fire detectors alarms
All fire detectors in the system turn on built-in sirens if at least one of the detectors registers an alarm.
The interconnected alarm is activated after no more than 20 seconds.
LED indication
green is a power indication
Lights up once every 56 seconds.
yellow is an indication of malfunctions
Lights up when malfunctions are detected. For example, in the case of discharged batteries, contamination of the smoke chamber, or end of the service life.
red is an indication of fire alarms
Lights up when the detector detects a fire alarm.
Button on the front panel of the detector
In normal mode, when pressed, it starts the smoke chamber test.
In the event of an alarm or malfunction, the pressing turns off the detector sound notification.

Power supply

For FireProtect 2 RB (Heat/Smoke/CO)
2 x CR123A battery
Up to 7 years of battery life.

For FireProtect 2 SB (Heat/Smoke/CO)
2 non-replaceable lithium batteries
10 years of battery life.

Enclosure and installation

Dimensions
124 x 124 x 45 mm

Weight
TBC For FireProtect 2 RB (Heat/Smoke/CO).
TBC For FireProtect 2 SB (Heat/Smoke/CO).

Operating temperature range
from 0°C to +50°C

Operating humidity
up to 80%

Protection class
IP20

Colours
Black
White

Complete set

For FireProtect 2 RB (Heat/Smoke/CO)
FireProtect 2 RB (Heat/Smoke/CO) Jeweller
SmartBracket mounting panel
Installation kit
2 x CR123A batteries Pre-installed
Quick Start Guide

For FireProtect 2 SB (Heat/Smoke/CO)
FireProtect 2 SB (Heat/Smoke/CO) Jeweller
SmartBracket mounting panel
Installation kit
Quick Start Guide

Models: FireProtect 2 Smoke Detector Wireless Indoor, FireProtect 2, Smoke Detector Wireless Indoor, Detector Wireless Indoor, Wireless Indoor, Indoor

File Info : application/pdf, 8 Pages, 4.32MB

PDF preview unavailable. Download the PDF instead.

tds-fireprotect-2-heat- -smoke- -co---en iLovePDF

Related Documents

Preview Ajax FireProtect 2 (Heat/Smoke/CO) Jeweller User Manual
Comprehensive user manual for the Ajax FireProtect 2 (Heat/Smoke/CO) Jeweller wireless fire detector. Learn about its smoke, heat, and CO detection capabilities, installation, operation, and maintenance within the Ajax security system.
Preview Ajax FireProtect 2 AC (CO) Jeweller User Manual
Comprehensive user manual for the Ajax FireProtect 2 AC (CO) Jeweller, a wireless mains-powered fire detector with backup battery and built-in siren, designed for indoor installation and detection of carbon monoxide.
Preview Ajax FireProtect 2 AC (Heat) Jeweller User Manual - Installation, Features, and Operation
Comprehensive user manual for the Ajax FireProtect 2 AC (Heat) Jeweller wireless mains-powered fire detector. Covers installation, features, operation, testing, maintenance, and troubleshooting.
Preview AJAX FireProtect 2 (Heat) Jeweller User Manual - Wireless Fire Detector
Comprehensive guide to the AJAX FireProtect 2 (Heat) Jeweller wireless fire detector. Learn about installation, features, operation, testing, maintenance, and troubleshooting for optimal fire safety.
Preview FireProtect 2 (CO) Jeweller User Manual - Ajax Systems
Comprehensive user manual for the Ajax FireProtect 2 (CO) Jeweller wireless fire detector. Learn about its features, installation, operation, testing, maintenance, and troubleshooting for detecting carbon monoxide.
Preview Ajax FireProtect / FireProtect Plus Wireless Fire Detector User Manual
This user manual provides comprehensive information on the Ajax FireProtect and FireProtect Plus wireless indoor fire detectors. It covers product features, functional elements, operating principles for smoke, temperature, and carbon monoxide detection, setup and connection procedures to Ajax security systems and third-party systems, device states and settings, interconnected alarm functionality, indications, testing, installation guidelines, autonomous use, maintenance, battery replacement, technical specifications, and warranty information.
Preview AJAX FireProtect 2 SB (Heat/CO) Jeweller Quick Start Guide
Quick start guide for the AJAX FireProtect 2 SB (Heat/CO) Jeweller, a wireless heat and carbon monoxide alarm. Provides specifications, regulatory compliance information, warranty details, and manufacturer contact information.
Preview Ajax FireProtect Plus: Wireless Smoke, Heat, and CO Detector User Manual
This user manual provides comprehensive instructions for the Ajax FireProtect and FireProtect Plus wireless indoor fire detectors. It details features, operating principles, connection methods to Ajax and third-party security systems, device states, settings, interconnected alarm functionality, installation, maintenance, and technical specifications.