Installation Guide for ACI Series Cassette Air Conditioners
This guide provides essential information for the installation of ACI series cassette air conditioners. Please read all instructions carefully before proceeding.
Safety Precautions
UV-C Lamp Safety (If Applicable): This appliance may contain a UV-C lamp. Always read the maintenance instructions before opening the appliance.
- Do not operate UV-C lamps outside the appliance.
- Do not operate obviously damaged appliances.
- Unintended use or damage to the housing can expose users to dangerous UV-C radiation, which can harm eyes and skin.
- It is recommended to disconnect power before opening doors or access panels with the ULTRAVIOLET RADIATION hazard symbol for user maintenance.
- UV-C lamps cannot be cleaned, repaired, or replaced by the user.
- UV-C BARRIERS with the ULTRAVIOLET RADIATION hazard symbol should not be removed.
Millimeter-wave Radar Safety: RF Frequency range: 61.332-63.940 GHz RF MAX. Power (EIRP): 15.62 dBm NOTE: Install and operate this equipment with a minimum distance of 20cm between the radiator (installed on the panel) and your body.
Installation Overview
This section details the mounting and connection requirements for the indoor unit.
Mounting Dimensions and Clearances
Ensure adequate space around the indoor unit for proper ventilation and maintenance. Recommended clearances are as follows:
- Clearance from ceiling to unit: Minimum 59.1 inches (150cm), 78.7 inches (200cm) recommended.
- Horizontal clearance: Minimum 59.1 inches (150cm) on sides, 78.7 inches (200cm) recommended.
- Vertical clearance: Minimum 157.5 inches (400cm) above the unit.
- Clearance from ground: Minimum 90.6 inches (230cm).
Ceiling Hole and Panel Dimensions:
MODEL | Length of A (Ceiling Hole) | Length of H (Distance from ceiling) | Length of B (Panel) |
---|---|---|---|
7K/9K/12K/18K | 9.6in (245mm) | 10.8in (275mm) | 23.6in (600mm) |
24K / 36K | 8.03in (205mm) | 9.06in (230mm) | 35.4in (900mm) |
48K | 9.65in (245mm) | 10.7in (271mm) | 35.4in (900mm) |
Note on Dimensions: Specific dimensions for suspension bolts, body, ceiling opening, and panel are provided for different model series (e.g., 7K/9K/12K/18K) with values like 20.5in/521mm, 22.4in/570mm, 23.6in/600mm, and 24.4in/620mm.
Refrigerant Piping and Drain Hose
Ensure minimum clearances for refrigerant piping (e.g., >39in/1000mm) and drain hose connections.
Electrical Connections and Tightening Torques
Proper electrical connections and torque specifications are crucial for safe operation.
Torque Specifications:
- 32-39 N.m (320-390 kgf.cm)
- 49-59 N.m (490-590 kgf.cm)
- 57-71 N.m (570-710 kgf.cm)
- 67-101 N.m (670-1010 kgf.cm)
- 85-110 N.m (850-1100 kgf.cm)
Note: Specific torque values may vary based on the connection type and component.
Panel Installation
Follow these steps for installing the front panel:
- Remove the front grille: Push both tabs towards the middle simultaneously to unlock the grille hook. Hold the grille at a 45° angle, lift slightly, and detach it from the main body.
- Attach the panel hook: The panel hook is pre-hung to the indoor unit flow guide ring.
- Install the panel: Secure the panel using four M5 screws.
Model Information
This installation guide applies to various ACI series models, including but not limited to:
- ACI-25HRDC1C
- ACI-35HRDC1C
- ACI-53HRDC1C
- ACI-71HRDC1A
- ACI-105HRDC3A
- ACI-140HRDC3A
- ACI-180HRDC3A
The document also references "Cassette type PRO II" and "Mexico side discharge inverter split type" units, with specific model series like 36K and 47K-60K mentioned.