Extended Charge Procedure

Commercial Application

Elite® Series 6 – 20 Ton

AIR CONDITIONERS 6 - 20 TONS

Document Number: 508349-02 | Revision: 3/2025

▲ WARNING

Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a licensed professional HVAC installer or equivalent, or service agency.

▲ IMPORTANT

The Clean Air Act of 1990 bans the intentional venting of refrigerant (CFCs, HCFCs and HFCs) as of July 1, 1992. Approved methods of recovery, recycling or reclaiming must be followed. Fines and/or incarceration may be levied for noncompliance.

▲ CAUTION

As with any mechanical equipment, contact with sharp sheet metal edges can result in personal injury. Take care while handling this equipment and wear gloves and protective clothing.

▲ WARNING

To prevent serious injury or death:

  1. Lock-out/tag-out before performing maintenance.
  2. If system power is required (e.g., smoke detector maintenance), disable power to blower, remove fan belt where applicable, and ensure all controllers and thermostats are set to the “OFF” position before performing maintenance.
  3. Always keep hands, hair, clothing, jewelry, tools, etc. away from moving parts.

General

This instruction is a complementary procedure. Installation should refer to the main unit instructions for the application considerations and proper installation procedures. This ELKC and ELKP outdoor air conditioners are designed for use with R-454B refrigerant only. This unit must be installed with an approved indoor air handler or coil and line set as outlined in the ELKC or ELKP Engineering Handbook. This outdoor unit is designed for use in thermal expansion valve (TXV) systems only.

Refrigerant Charge

NOTE: This extended R-454B charging procedure applies to non-matched Indoor and Outdoor units only. For matched Indoor and Outdoor units with same full load capacity, see unit instructions for charging procedure.

The ELITE units have a factory holding charge of 2 pounds of R-454B in each circuit. The outdoor unit should be charged during warm weather. However, applications arise in which charging must occur in the colder months. The method of charging is determined by the outdoor ambient temperature. Before charging the unit, determine the liquid line temperature and the outdoor ambient temperature.

Charge Using the Subcooling Method

Outdoor Temperature > 65°F (18.3°C)

  1. Attach pressure gauge set to liquid and suction service valves. Operate unit for at least five (5) minutes to allow system pressures to stabilize, then, use a thermometer to record the liquid line temperature.
  2. At the same time, record the liquid line pressure reading. Use a temperature/pressure chart for R-454B to determine the saturation temperature for the liquid line pressure reading.
  3. Subtract the liquid line temperature from the saturation temperature (according to the chart) to determine subcooling (Saturation temperature - Liquid line temperature = Subcooling Value).
  4. Compare the subcooling value with those in table for the specific system match. If subcooling is greater than shown, recover some refrigerant. If subcooling is less than shown, add refrigerant.
  5. Repeat steps 1-5 anytime refrigerant is added or recovered.
  6. For Heat Pump models – Switch to heating mode and let the system stabilize at least 10 minutes. Then confirm that the pressures obtained from the connected gauges match the normal operating pressures (heating mode) in table for the specific system match.

Charge Using Normal Operating Pressures/Approach Method (High Capacity)

Outdoor Temperature ≥ 65°F (18.3°C)

For best results, indoor temperature should be 70°F (21°C) to 80°F (26°C). Monitor system pressures while charging.

  1. Attach pressure gauge set to liquid and suction service valves.
  2. Operate unit for at least five (5) minutes to allow system pressures to stabilize. Record pressures.
  3. Compare stabilized pressures with those provided in table for the specific system match. Minor variations are to be expected; significant differences could mean that the system is not properly charged or that a problem exists with some component in the system. The approach method is not valid for grossly over or under-charged systems.
  4. Pressures higher than those listed indicate that the system is overcharged. Pressures lower than those listed indicate that the system is undercharged. Add or recover charge until the pressures are within the tolerances on the table.
  5. Repeat steps 2-4 each time refrigerant is added or recovered.
  6. Verify charge using the approach method.
  7. Use the same thermometer to measure and record liquid line temperature.
  8. Subtract the outdoor temperature from the liquid line temperature to determine the approach value (Liquid line temperature – Ambient temperature = Approach Temperature).
  9. The approach temperature should match value given in table for the specific system match. If the values don't agree with the those in table, add refrigerant to lower the approach temperature or recover refrigerant from the system to increase the approach temperature.
  10. Operate unit for at least five (5) minutes to allow system pressures to stabilize.
  11. Repeat steps 7-10 each time refrigerant is added or recovered.
  12. For Heat Pump models – Switch to heating mode and let the system stabilize at least 10 minutes. Then confirm that the pressures obtained from the connected gauges match the normal operating pressures (heating mode) in table for the specific system match.

Outdoor Temperature < 65°F (18.3°C)

When the outdoor ambient temperature is below 65°F (18.3°C) it may be necessary to restrict the air flow through the outdoor coil to achieve pressures in the 325-375 psig (2240-2485 kPa) range. These higher pressures are necessary for checking the charge. Block equal sections of air intake panels and move obstructions sideways until the liquid pressure is in the 325-375 psig (2240-2485 kPa) range. See FIGURE 1. Once pressure is in range, charge using Normal Operating Pressures/Approach Method (High Capacity).

Table of Contents

Commercial Cooling Model(s) – Normal Operating Pressures and Temperatures

Figure 1: Blocking Outdoor Coil

This figure illustrates the method of blocking sections of the outdoor coil to achieve specific pressures for charging when the outdoor temperature is below 65°F (18.3°C). It shows an outdoor unit with a cardboard or plastic sheet used to block one side of the coil.

Commercial Cooling Model(s) – Normal Operating Pressures and Temperatures

Note - Pressures at 80°F dry bulb and 67°F wet bulb entering indoor air temperatures.

ModelSubcooling Values (High Capacity) - at 95°F Ambient Temperature (°F (°C) ±1°F)Approach Values (High Capacity) - at 95°F Ambient Temperature (°F (°C))Air Temperature Entering Outside CoilLiquid Line Pressure / Vapor Line PressureSCFM
EL072KCSS - EL090KASD12 (6.7)6 (3.3)65 (18)235/1342750
75 (24)274/135
85 (29)317/137
95 (35)363/139
105 (41)413/141
115 (46)467/143
125 (52)525/145
EL090KCSS - EL120KASD12 (6.7)6 (3.3)65 (18)236/1242750
75 (24)273/126
85 (29)313/128
95 (35)358/130
105 (41)406/133
115 (46)458/135
125 (52)514/137
(2) EL090KCSS - EL180KASDCIR. 1: 12 (6.7)
CIR. 2: 12 (6.7)
CIR. 1: 4 (2.2)
CIR. 2: 4 (2.2)
65 (18)CIR. 1: 232/115
CIR. 2: 231/113
5200
75 (24)CIR. 1: 269/117
CIR. 2: 268/114
85 (29)CIR. 1: 309/119
CIR. 2: 309/117
95 (35)CIR. 1: 354/121
CIR. 2: 353/119
105 (41)CIR. 1: 401/123
CIR. 2: 401/122
115 (46)CIR. 1: 454/127
CIR. 2: 452/124
125 (52)CIR. 1: 510/129
CIR. 2: 509/128
(2) EL120KCSS - EL240KASDCIR. 1: 8 (4.4)
CIR. 2: 8 (4.4)
CIR. 1: 6 (3.3)
CIR. 2: 6 (3.3)
65 (18)CIR. 1: 224/122
CIR. 2: 224/122
7400
75 (24)CIR. 1: 260/123
CIR. 2: 260/123
85 (29)CIR. 1: 300/125
CIR. 2: 300/125
95 (35)CIR. 1: 344/128
CIR. 2: 344/128
105 (41)CIR. 1: 391/129
CIR. 2: 391/129
115 (46)CIR. 1: 443/131
CIR. 2: 443/131
125 (52)CIR. 1: 499/134
CIR. 2: 499/134
EL150KCSD - EL180KASDCIR. 1: 12 (6.7)
CIR. 2: 12 (6.7)
CIR. 1: 5 (2.8)
CIR. 2: 5 (2.8)
65 (18)CIR. 1: 239/127
CIR. 2: 237/124
5200
75 (24)CIR. 1: 276/130
CIR. 2: 274/125
85 (29)CIR. 1: 317/132
CIR. 2: 315/127
95 (35)CIR. 1: 361/133
CIR. 2: 359/130
105 (41)CIR. 1: 409/135
CIR. 2: 407/132
115 (46)CIR. 1: 462/138
CIR. 2: 459/134
125 (52)CIR. 1: 519/141
CIR. 2: 516/137
EL180KCSD - EL240KASDCIR. 1: 9 (5.0)
CIR. 2: 10 (5.6)
CIR. 1: 4 (2.2)
CIR. 2: 4 (2.2)
65 (18)CIR. 1: 217/130
CIR. 2: 219/131
7025
75 (24)CIR. 1: 255/133
CIR. 2: 256/133
85 (29)CIR. 1: 296/135
CIR. 2: 296/136
95 (35)CIR. 1: 340/137
CIR. 2: 341/138
105 (41)CIR. 1: 390/140
CIR. 2: 391/140
115 (46)CIR. 1: 443/142
CIR. 2: 445/142
125 (52)CIR. 1: 500/145
CIR. 2: 501/145
EL180KCSD - (2) EL090KASDCIR. 1: 9 (5.0)
CIR. 2: 10 (5.6)
CIR. 1: 4 (2.2)
CIR. 2: 3 (1.7)
65 (18)CIR. 1: 215/120
CIR. 2: 217/120
5200(2600 per unit)
75 (24)CIR. 1: 252/122
CIR. 2: 253/123
85 (29)CIR. 1: 293/125
CIR. 2: 294/125
95 (35)CIR. 1: 337/128
CIR. 2: 339/129
105 (41)CIR. 1: 385/130
CIR. 2: 388/131
115 (46)CIR. 1: 438/133
CIR. 2: 441/133
125 (52)CIR. 1: 497/137
CIR. 2: 498/137
EL240KCSD - (2) EL120KASDCIR. 1: 11 (6.1)
CIR. 2: 12 (6.7)
CIR. 1: 4 (2.2)
CIR. 2: 3 (1.7)
65 (18)CIR. 1: 226/120
CIR. 2: 226/120
7025(3513 per unit)
75 (24)CIR. 1: 263/122
CIR. 2: 265/122
85 (29)CIR. 1: 304/124
CIR. 2: 305/124
95 (35)CIR. 1: 348/127
CIR. 2: 349/126
105 (41)CIR. 1: 396/129
CIR. 2: 397/129
115 (46)CIR. 1: 448/131
CIR. 2: 449/131
125 (52)CIR. 1: 505/135
CIR. 2: 506/135

Residential Cooling Model(s) – Normal Operating Pressures and Temperatures

Note - Pressures at 80°F dry bulb and 67°F wet bulb entering indoor air temperatures.

ModelSubcooling Values (High Capacity) - at 95°F Ambient Temperature (°F (°C) ±1°F)Approach Values (High Capacity) - at 95°F Ambient Temperature (°F (°C))Air Temperature Entering Outside CoilLiquid Line Pressure / Vapor Line PressureSCFM
EL090KCSS + (2) CK40CT-60D-71 + (2) EL296UH135XE60D12 (6.7)6 (3.3)65 (18)238/1303545(1771 per unit)
75 (24)276/132
85 (29)316/134
95 (35)360/135
105 (41)408/137
115 (46)460/140
125 (52)516/143
EL090KCSS + (2) CK40CT-60C-71 + (2) EL280UH110E48C12 (6.7)6 (3.3)65 (18)239/1323210(1604 per unit)
75 (24)276/133
85 (29)317/135
95 (35)361/137
105 (41)409/139
115 (46)461/141
125 (52)516/144
EL090KCSS + (2) CK40CT-60C-71 + (2) EL296UH110XE60C12 (6.7)6 (3.3)65 (18)239/1333285(1641 per unit)
75 (24)276/134
85 (29)317/135
95 (35)361/138
105 (41)409/140
115 (46)461/142
125 (52)517/145
EL090KCSS + (2) CK40CT-60C-71 + (2) EL280UH110E60C12 (6.7)6 (3.3)65 (18)239/1313115(1556 per unit)
75 (24)276/132
85 (29)317/134
95 (35)361/136
105 (41)409/138
115 (46)460/141
125 (52)516/143
EL120KCSS + (2) CK40CT-60C-71 + (2) EL280UH110E60C9 (5.0)6 (3.3)65 (18)223/1203115(1556 per unit)
75 (24)261/122
85 (29)302/124
95 (35)347/126
105 (41)398/128
115 (46)451/131
125 (52)509/133
EL120KCSS + (2) CK40CT-60C-71 + (2) EL280UH110XE60C9 (5.0)7 (3.9)65 (18)223/1223285(1641 per unit)
75 (24)261/124
85 (29)302/125
95 (35)347/127
105 (41)398/130
115 (46)451/132
125 (52)510/135
EL120KCSS + (2) CK40CT-60D-71 + (2) EL296UH135XE60D9 (5.0)6 (3.3)65 (18)223/1193545(1771 per unit)
75 (24)260/121
85 (29)302/123
95 (35)347/125
105 (41)397/127
115 (46)451/131
125 (52)509/133

Commercial Heat Pump Model(s) – Normal Operating Pressures and Temperatures

ModelSubcooling Values - Cooling (High Capacity) - at 95°F Ambient Temperature (°F (°C) ±1°F (0.5°C))Approach Values - (High Capacity) - at 95°F Ambient Temperature (°F (°C) ± 1°F (0.5°C))Air Temperature Entering Outside CoilLiquid Line Pressure / Vapor Line Pressure (CIR. 1)Liquid Line Pressure / Vapor Line Pressure (CIR. 2)SCFM
(2) EL090KPSS + EL240KASD6 (3.3)8 (4.4)65 (18)224/126224/1266000
75 (24)260/129260/129
85 (29)300/130300/130
95 (35)344/133344/133
105 (41)391/135391/135
115 (46)442/138442/138
125 (52)497/141497/141
Normal Operating Pressures - Heating (Liquid ±10 & Suction ±5 psig)
Air Temperature Entering Outside CoilLiquid Line Pressure / Vapor Line Pressure (CIR. 1)Liquid Line Pressure / Vapor Line Pressure (CIR. 2)
60 (15)340/111340/111
50 (10)321/94321/94
40 (4)304/79304/79
30 (-1)288/65288/65
20 (-6)276/53276/53
10 (-12)264/43264/43

Interconnected Wiring Diagrams and Thermostat Operations

The purpose of the interconnect diagrams is to enable AHRI testing agencies to wire up 2-1 and 1-2 Commercial Elite Splits matchups for performance (ratings) testing. All multiple unit interconnection diagrams require field provided thermostat, relay(s), transformer(s). For non-AHRI testing applications, engineering strongly suggests consulting with Lennox technical support before attempting to apply these diagrams in the field.

Unit operation tables based upon thermostat demands have been provided for each of the interconnect diagrams as a means of verifying proper wiring.

For FIGURE 4 wiring, if either indoor Air Handler detects a refrigerant leak and initiates the mitigation process, the non-leaking unit's blower will activate at the "G" demand speed until the leak is no longer detected. For FIGURE 5 wiring (using integrated furnace controller), if either Furnace detects refrigerant leak and initiates the leak mitigation process, the non-leaking furnace will activate its blower in high speed until the leak is no longer detected.

Figure 2: Two Air Conditioners (Outdoor) and One Indoor Air Handler (Indoor)

This wiring diagram illustrates the interconnect wiring for a split system configuration involving two outdoor Lennox air conditioners and one indoor air handler. It details the low voltage control wiring between these components and a thermostat.

Legend: A194 & TB14 - Terminal Strip-Class II Voltage (Factory Installed), 67K65 - Relay, DPDT, 24V Coil (Field Provided), 24 VAC / 70 VA (MIN) Transformer (Field Provided), A2 - Thermostat (Field Provided), Optional Field Installed Accessory (Not Used for AHRI), Class II Field Wiring, Optional Class II Field Wiring.

Figure 3: Two Heat Pumps (Outdoor) and One Indoor Air Handler (Indoor)

This wiring diagram illustrates the interconnect wiring for a split system configuration involving two outdoor Lennox heat pumps and one indoor air handler. It details the low voltage control wiring between these components and a thermostat.

Legend: A194 & TB14 - Terminal Strip-Class II Voltage (Factory Installed), 67K65 - Relay, DPDT, 24V Coil (Field Provided), 56L68 - Relay, SPDT, 24V Coil (Field Provided), 24 VAC / 70 VA (MIN) Transformer (Field Provided), A2 - Thermostat (Field Provided), Optional Field Installed Accessory (Not Used for AHRI), Class II Field Wiring, Optional Class II Field Wiring (Not Used for AHRI), Class II Factory Wiring.

Figure 4: One Air Conditioner (Outdoor) and Two Air Handlers (Indoor)

This wiring diagram illustrates the interconnect wiring for a split system configuration involving one outdoor Lennox air conditioner and two indoor air handlers. It details the low voltage control wiring between these components and a thermostat.

Legend: A194 & TB14 - Terminal Strip-Class II Voltage (Factory Installed), 56L68 - Relay, SPDT, 24V Coil (Field Provided), 67K65 - Relay, DPDT, 24V Coil (Field Provided), 24 VAC / 70 VA (MIN) Transformer (Field Provided), A2 - Thermostat (Field Provided), Optional ELEH Electric Heat Isolation Relays Shown for Reference (Not Used for AHRI), A194 Mitigation Activation on Either AHU Places the Other AHU Into Blower Only Operation, Class II Field Wiring, Optional Class II Field Wiring (Not Used for AHRI), Class II Factory Wiring.

Figure 5: One Air Conditioner (Outdoor) and Two Residential Furnaces (Indoor)

This wiring diagram illustrates the interconnect wiring for a split system configuration involving one outdoor Lennox air conditioner and two residential furnaces. It details the low voltage control wiring between these components and a thermostat.

Legend: TB14 - Terminal Strip-Class II Voltage (Factory Installed), See Elite Splits Engineering Handbook for Applicable Gas Furnace Models, 56L68 - Relay, SPDT, 24V Coil (Field Provided), Replace Factory 24 VAC Transformer with Field Provided 24 VAC / 70 VA MIN. Transformer, A2 - Thermostat (Field Provided), 67K66 - Relay, 3PDT, 24V Coil (Field Provided), Wiring for Furnace Control Board with R454B Leak System Integrated. Mitigation Activation on Either Furnace Places the Other Furnace Into High Speed Blower Operation, Class II Field Wiring, Class II Field Wiring (Not Used by AHRI).

TABLE 1: Cooling Operation - Two Air Conditioners and One Air Handler (wired per FIGURE 2)

Thermostat (Output Signal)AHU Blower SpeedAC #1AC #2ELEH Heater (Option)
Compressor SpeedFan(s)Compressor SpeedFan(s)
Y1LowLowOnLowOnOff
Y2HighHighOnHighOnOff
GLow or HighOffOffOffOffOff
W1*HighOffOffOffOffOn
W2*HighOffOffOffOffOn

*Consult instructions for specific ELEH model for staging details; ELEH not installed for AHRI testing.

TABLE 2: Cooling & Heating Operation - Two Heat Pumps and One Air Handler (wired per FIGURE 3)

Thermostat (Output Signal)AHU Blower SpeedHP #1HP #2ELEH Heater (Option)
Compressor SpeedFan(s)Compressor SpeedFan(s)
Y1LowLowOnLowOnOff
Y2HighHighOnHighOnOff
GLow or HighOffOffOffOffOff
W1HighHighOnHighOnOff
W2+*HighOffOffOffOffOn

*Consult instructions for specific ELEH model for staging details; ELEH not installed for AHRI testing. +H2 Signal from Heat Pump is "On" (24V power) during defrost mode.

TABLE 3: Cooling Operation - One Air Conditioners and Two Air Handler (wired per FIGURE 4)

Thermostat (Output Signal)AHU #1 Blower SpeedAHU #2 Blower SpeedAir Conditioner4 Fan(s)ELEH Heater (Option)
Compressor #1 SpeedCompressor #2 Speed
Y1LowLowLowOff2 OnOff
Y2MediumMediumLowLow4 OnOff
Y3HighHighHighHigh4 OnOff
GLow or HighLow or HighOffOffOffOff
W1*HighHighOffOffOffOn
W2*HighHighOffOffOffOn

*Consult instructions for specific ELEH model for staging details; ELEH not installed for AHRI testing.

TABLE 4: Cooling Operation - One Air Conditioner and Two Residential Furnaces (wired per FIGURE 5)

Thermostat (Output Signal)Furnace #1 Blower SpeedFurnace #2 Blower SpeedAir Conditioner
Compressor SpeedFan(s)Compressor SpeedFan(s)Compressor SpeedFan(s)
Y1LowLowOnLowOnOff
Y2HighHighOnHighOnOff
G*OnOnOffOffOffOff
W1*OnOnOffOffOffOn
W2*OnOnOffOffOffOn

*Consult instructions for specific Furnace model for staging and airflow details.

Models: 10, 12, 15, 20, ELKP Outdoor Air Conditioners, ELKP, Outdoor Air Conditioners, Air Conditioners, Conditioners

File Info : application/pdf, 21 Pages, 2.50MB

PDF preview unavailable. Download the PDF instead.

508349-02a Adobe PDF Library 17.0

Related Documents

Preview Lennox Elite Series Large Split Systems Quick Reference Guide
Comprehensive quick reference guide for Lennox Elite Series large split system air conditioners and heat pumps, detailing specifications, features, and model comparisons.
Preview Lennox Elite Series 6-20 Ton Split Systems Quick Reference Guide
Quick reference guide detailing specifications, model numbers, and features for Lennox Elite Series 6 to 20-ton split system air conditioners and heat pumps, suitable for commercial HVAC applications.
Preview Lennox Elite Series EL18KSLV Heat Pump Installation Instructions
Comprehensive installation instructions for the Lennox Elite Series EL18KSLV Heat Pump units. Covers general information, operating range, safety warnings, installation procedures, refrigerant handling, electrical connections, and unit operation for residential and light commercial applications. Includes model variants and technical specifications.
Preview Lennox Heat Pump AHRI System Matches
Comprehensive guide to Lennox heat pump AHRI system matches, detailing model compatibility, cooling and heating performance ratings (SEER2, EER2, HSPF2, COP), and specifications for HVAC professionals and consumers.
Preview Lennox EL16KC1 Elite Series Residential Air Conditioner Product Specifications
Comprehensive product specifications for the Lennox EL16KC1 Elite Series residential air conditioner. Details include model identification, features, technical specifications, electrical data, dimensions, sound data, installation clearances, and warranty information for the R-454B refrigerant system.
Preview Lennox ML14KP1 Merit Series Heat Pump Installation Instructions
Comprehensive installation guide for the Lennox ML14KP1 Merit Series Heat Pump, covering unit setup, refrigerant piping, electrical connections, start-up procedures, charging, and maintenance.
Preview Lennox CK40CT | CK40UT Indoor Coils: Product Specifications
Detailed product specifications for Lennox CK40CT and CK40UT indoor coils, covering capacities from 1.5 to 5 tons. Includes model number identification, features, construction details, dimensions, and air resistance data.
Preview Lennox Elite Series EL16KC1 Air Conditioner Installation Instructions
Comprehensive installation guide for the Lennox Elite Series EL16KC1 Air Conditioner, covering safety precautions, unit placement, refrigerant piping, electrical wiring, and start-up procedures.