Siemens Desigo™ PX BACnet Router

Models: PXG3.L, PXG3.M

A versatile BACnet router designed for seamless integration between BACnet/IP, BACnet/LonTalk, and BACnet MS/TP networks.

Key Features

Product Overview and Use

The PXG3... BACnet router connects a BACnet/IP network to a BACnet/LonTalk network (PXG3.L only), and/or a BACnet MS/TP channel. BACnet objects are transmitted simultaneously throughout any and all networks.

Diagram Description: A network diagram illustrates the router's connectivity, showing how it links BACnet/IPv4, BACnet/IPv6, BACnet/LonTalk (PXG3.L only), and BACnet MS/TP networks, with connections to Desigo Insight and third-party devices.

Router Functions

Four-way routing

The PXG3... BACnet router transmits BACnet protocol between a BACnet/IPv4 network, a BACnet/IPv6 network, a BACnet/LonTalk network (PXG3.L only), and a BACnet MS/TP channel. BACnet objects are simultaneously transmitted throughout any and all networks.

BBMD (Broadcast Management Device)

Used to distribute BACnet Broadcast messages across IP Routers.

Web server

The BACnet router includes a Device Object and can be operated by a BACnet Client. The present operating state, date and time, as well as statistics on sent packages can be viewed via the web server.

MS/TP Slave Proxy

The BACnet router can serve as a Slave Proxy for slaves connected to its MSTP port. It responds to Who-Is messages on the slaves' behalf by sending an I-Am message.

SNMP v2

Simple Network Management Protocol MIB-2, used for monitoring and diagnosing the BACnet router network interface.

BACnet NAT

Supports the setup of a BACnet network over a NAT device. Additionally, remote access from a public network to BACnet devices is possible on a private network. Important: The public IP address must be static. For security reasons, VPN tunneling is recommended with BACnet NAT.

BACnet/IP to BACnet/IP

When routing between BACnet/IP on the same IP network, the BACnet router address must be the same on both BACnet networks. The difference lies in the use of different BACnet UDP ports on the BACnet network.

Communication and Connectivity

Type Summary

Type (ASN) Product number (SSN) Name Ethernet ports LONWORKS MS/TP
PXG3.L S55842-Z105-A100 BACnet Router Ethernet/IP-LonTalk-MS/TP 2
PXG3.M S55842-Z106-A101 BACnet Router Ethernet/IP-MS/TP 2

Mechanical Design

Diagram Description: A schematic illustrates the physical layout of the router with numbered components:

  1. Plastic housing
  2. Plug-in terminal block (operating voltage)
  3. 2-port Ethernet switch (with 2 LEDs each for display purposes)
  4. LEDs for device and system status indication
  5. RJ45 interface for PXM20 (PXG3.L only)
  6. Tool interface (USB Device)
  7. Service button for identification on network (Ethernet, LONWORKS)
  8. LONWORKS terminal block (PXG3.L only)
  9. MS/TP terminal block
  10. Slider for mounting on DIN rail

LED Indicators

Diagram Description: Visual representation of the HMI/Tool LEDs (RUN, FLT, INF, COM1, COM2, SVC) and Ethernet port LEDs.

LED Color Activity Function
RUN Green Continuously ON Device ready.
Continuously OFF At least one internal power supply out of range.
Flashing Start-up of device.
FLT Red Continuously OFF OK
Continuously ON HW fault or program fault.
Flashing Incorrect or corrupt FW.
INF Yellow Flashing (Not used)
COM1 Yellow Flashing Sends MS/TP packages.
COM2 Yellow Flashing Sends LONWORKS packages (PXG3.L only).
SVC Red Continuously OFF Unconfigured.
Continuously ON Configured.
Flashing Defective Hardware.
Flashing per wink command *) Physical identification of the router.
Ethernet 1/2 Green Continuously ON Link active
Continuously OFF Link inactive
Flashing Network activity
Yellow Continuously ON Link 100 Mbps
Continuously OFF Link 10 Mbps

*) Wink command pattern: A visual representation shows a flashing pattern with durations (2s, 1s) and frequencies (5 Hz).

Service Button

Diagram Description: Location of the service button (labeled '1') on the device.

Factory Reset Procedure:

  1. Power off the device.
  2. Power on the device.
  3. Wait for all LEDs to light up and turn off, then push the SVC button.
  4. Keep the SVC button pressed until all LEDs light up, then release. (For Desigo V6_SP and earlier: Keep pressed until the green RUN LED flashes, then release).
  5. Wait for the device to fully start up unconfigured (RUN LED on, SVC LED flashes).

Note: Any device passwords and other settings are lost.

Engineering, Installation, and Maintenance

Engineering

The router does not require programming. Configuration is performed using Xworks Plus or the Desigo SSA-DNT via Ethernet, or using a USB device. For details, refer to SSA (Setup & Service Assistant) Commissioning, CA111050. Each device has a unique identification number on a removable barcode label and a unique MAC address. For more details, see document "Ethernet, TCP/IP, MS/TP and BACnet - Principles" (CM110666).

Installation

Ethernet: Refer to installation manual Desigo TRA, CM111043.

LONWORKS: Refer to installation manual Desigo RXC, CA110336.

Note: The HMI (RJ45 plug) only supports the PXM20. Connecting other devices may damage the PXG3.L or the connected device.

Mounting

The router is designed for mounting on a standard mounting rail or a wall. Power is supplied by connecting the plug-in screw terminal blocks.

Commissioning

To prevent equipment damage and/or personal injuries, adhere to local safety regulations and related safety standards.

Maintenance

No maintenance is required. A supercap supports the real-time clock for up to 3 days.

Disposal

These devices are considered electronic waste according to the European Directive 2012/19/EU (WEEE) and must not be disposed of as domestic waste. Dispose of the devices via the proper channels and observe all local and applicable laws.

Technical Data

Operating Voltage and Power

Parameter Specification
Operating voltage (24 V~, ⚡, ?) AC 24 V ± 20 % (SELV/PELV) or AC/DC 24 V class 2 (US), 48...63 Hz. Symmetric.
Power consumption Max. 9 VA (At AC 24 V)
Max. 4 W (At DC 24 V)
Max. permissible transit power AC/DC 24 V (RJ45 interface, HMI) Max. 0.5 A
Internal fuse With PTC

Hardware Information

Parameter Specification
Processor Series B: Atmel ARM9
Series C: Texas Instruments AM3352, 600MHz
Memory Series B: 256 MB Flash, 64 MB SDRAM
Series C: 512 MB Flash, 512 MB SDRAM (DDR3)
Response to power / communication failure Energy reserve (Supercap) to support real-time clock (3 days). Data available only if saved to flash memory.

Interface Specifications

Interface Type Details
Ethernet interface 2 x RJ45, screened 100BaseTX, IEEE 802.3 compatible, 10/100 Mbps, half / full duplex, auto-negotiation. Protocol: BACnet over UDP/IP.
HMI interface RJ45 (PXG3.L only)
USB interface Type B (USB device) Data rate: 12 Mbps. Galvanic isolation: No. Protective switch against surges and overcurrent: Yes.
LONWORKS interface (PXG3.L only) TP/FT-10 Transceiver: FT 5000 smart transceiver. Galvanic isolation: Yes. Bit rate: 78 kbps. Protocol: BACnet over LonTalk.
MS/TP interface RS485 Galvanic isolation: Yes. Baud rates: 9600, 19200, 38400, 76800, 115200. Protocol: BACnet over MS/TP.

Connection Terminals, Plug-in

Parameter Specification
Design type Plug-in screw terminals
Wire size Cu-wire or Cu-strand with wire end sleeve: 1 x 0.6 mm dia. to 2.5 mm² or 2 x 0.6 mm dia. to 1.0 mm²
Cu-strand without wire end sleeve: 1 x 0.6 mm dia. to 2.5 mm² or 2 x 0.6 mm dia. to 1.5 mm²
Screwdriver Slot screws, size 1 with shaft dia. ≤ 4.5 mm
Max. tightening torque 0.6 Nm

Standards, Approvals, and Environmental Data

Parameter Specification
Assignment as per EN 60730 Operation of automatic controller: Type 1
Degree of pollution: 2
Design type: Protection class III
Housing protection standard Protection type as per EN 60529: IP30
Front parts in the DIN section: IP30
Terminal part: IP20
Ambient conditions (Operation) Climatic: Class 3K5, -5 ... 50 °C, 5...95% r.h. (non-condensing)
Mechanical: Class 3M2
Ambient conditions (Transport) Climatic: Class 2K3, -25...70 °C, 5...95% r.h. (non-condensing)
Mechanical: Class 2M2
Standards, directives, and approvals Product standard: EN 60730-1 (Automatic electrical controls for household and similar use)
Product family standard: EN 50491-x (General requirements for Home and Building Electronic Systems (HBES) and Building Automation and Control Systems (BACS))
Electromagnetic compatibility (Applications) For use in residential, commerce, light-industrial and industrial environments.
EU conformity (CE): CM1T9270xx ¹)
UL certification (US): UL 916, http://ul.com/database
RCM-conformity (EMC): CM1T9222en_C1 ¹)
EAC conformity: Eurasia conformity
BTL Certificate: www.bacnetinternational.net/btl/search.php ²).
Environmental compatibility Product environmental declaration (contains data on RoHS compliance, materials composition, packaging, environmental benefit, disposal): CM1E9270 ¹).
Color Housing: RAL 7035 (light-gray)
Dimensions Housing as per DIN 43880, see dimensions.
Weight Without/with packaging: 286 g / 332 g

Footnotes:

1) The documents can be downloaded at http://siemens.com/bt/download.

2) Filter list of results for 'BTL-31001'.

Connection Terminals and Interfaces

Diagram Description: A view of the router's front panel showing numbered connection points and interface labels.

Connection Point Interface Details
1, 2 Ethernet 2 x RJ45 interface
3 Operating Voltage AC/DC 24 V
5 LONWORKS (PXG3.L only)
MS/TP MS/TP interface
HMI RJ45 RJ45 interface for HMI (PXG3.L only)
USB USB Tool Interface USB tool interface
Service Service Button Service button

RJ45 Pin Assignment for HMI

Pin Name Description Pin Name Description
1 CLA LONWORKS A 5 nc Not connected
2 CLB LONWORKS B 6 nc Not connected
3 AC24V_N AC24V Neutral 7 nc Not connected
4 AC24V_L AC24V Line max. 500mA 8 nc Not connected

Operating Voltage Pin Assignment

Pin Name Description
1 24 V ~ AC 24 V
2 System neutral
3 Technical ground

LONWORKS Pin Assignment

Pin Name Description
4 CLA LONWORKS A
5 CLB LONWORKS B

MS/TP Pin Assignment

Pin Name Description
+ Data +
- Data –
Reference wire

Dimensions

All dimensions in mm.

Diagram Description: Orthographic views (front, side, top) of the router with dimensions indicated in millimeters. Key dimensions include overall width (162 mm), height (approx. 110 mm), and depth (approx. 90 mm), with detailed measurements provided for various features.

Models: PXG3.L, PXG3.M, PXG3.L BACnet Router, BACnet Router, Router

File Info : application/pdf, 10 Pages, 298.24KB

A6V10366162

References

PDF-XChange Standard (10.0 build 0.370) [GDI] [Windows 10 Enterprise x64 (Build 19044)]

Related Documents

Preview BACnet Conformance Certificate for Siemens VAV Compact Controller GxB181.1E/BA
Official BACnet Conformance Certificate (BTL) for the Siemens VAV Compact Controller, Model GxB181.1E/BA, confirming compliance with ISO 16484-5 protocol revision 1.10.
Preview BACnet Conformance Certificate for Siemens PXC3.E - BTL-30059
Official BACnet conformance certificate (BTL-30059) for the Siemens PXC3.E product, confirming compliance with ISO 16484-5. Details include models PXC3.E72, PXC3.E72A, PXC3.E75, PXC3.E75A, software version, vendor information, and certification validity.
Preview BACnet Conformance Certificate - Siemens DXR2
This certificate attests the BACnet conformance of Siemens DXR2 models to the BACnet standard ISO 16484-5, revision 1.13, as verified by WSPCert. Includes product details, software version, vendor information, and certification dates.
Preview Desigo Building Automation System 6.3: Technical Principles
This document details the technical principles of the Desigo Building Automation System 6.3, covering system overview, control concepts, technical views, data management, network architecture, and compatibility.
Preview Siemens Desigo PXC5.E003 System Controller: Technical Specifications and Features
Comprehensive technical specifications, functions, and integration details for the Siemens Desigo PXC5.E003 system controller, designed for BACnet/MSTP, Modbus, and KNX PL-Link device integration in building automation systems.
Preview Siemens Desigo DXR2.M18 Room Automation Station Datasheet
Technical datasheet for the Siemens Desigo DXR2.M18 Room Automation Station, detailing its features, applications, technical specifications, and compliance for HVAC, lighting, and shading control in building automation systems.
Preview Siemens TXB3 Bus Interface Module - BACnet Testing Laboratories Product Listing
Official BACnet Testing Laboratories (BTL) product listing for the Siemens TXB3 Bus Interface Module, detailing its compliance, device profiles, supported BIBBs, and technical specifications.
Preview Siemens Desigo PXC4, PXC5, PXC7 Automation Controls for High-Tech Buildings
Discover the Siemens Desigo PXC family of automation controllers (PXC4, PXC5, PXC7) designed for high-tech buildings. Learn about their scalable solutions, smart engineering capabilities, simple integration, and secure connectivity for building automation and control systems.