User Guide for SIEMENS models including: PXC4, PXC5, PXC7, PXC4 Desigo Automation Controls for High-Tech Buildings, PXC4, Desigo Automation Controls for High-Tech Buildings, Desigo Automation Controls, Automation Controls, Controls

011 A6V13054432 PXC4 PXC5 PXC7 Range en-- d

Desigo™ PXC4, PXC5 & PXC7 Automation controls for ...

Manual operation. User. Plant operation with Desigo Control Point – Embedded building operation. Designed to simplify building automation operation and ...

il y a 2 jours — Building operation and monitoring are enabled through intuitive touch ... documentation purposes. ... Overviews help the user to handle.

6 days ago — Manual operation. User. Plant operation with Desigo Control Point – Embedded building operation. Designed to simplify building automation operation and ...


File Info : application/pdf, 24 Pages, 18.18MB

PDF preview unavailable. Download the PDF instead.

A6V13202299 Desigo PXC4 PXC5 PXC7 Automation controls for en agVO63e
DesigoTM PXC4, PXC5 & PXC7 Automation controls for high-tech buildings Range Description

A6V13054432_en--_d 2022-08-30

Smart Infrastructure

Table of Contents
1 Desigo PXC Controllers ­ The flexible, reliable ... .............................. 3 2 ... and scalable automation and control system ................................. 4 3 Desigo Control Point ............................................................................. 5 4 ... Embedded building operations......................................................... 6 5 ... Portfolio............................................................................................... 8 6 Operation and monitoring ..................................................................... 9 7 A family of programmable automation stations.................................. 10 8 PXC4 automation stations..................................................................... 13 9 PXC5 system controllers ....................................................................... 15 10 PXC7 automation stations..................................................................... 16 11 TXM input/output modules for PXC7 and PXC4 .................................. 17 12 KNX PL-Link field bus for "plug-and-play" field device communic-
ation......................................................................................................... 18 13 ABT Site ... for flexible and intuitive... ................................................. 20 14 ... set-up, programming, and commissioning...................................... 21 15 Can be extended in stages at any time ................................................ 22

2 | 24

A6V13054432_en--_d

Desigo PXC Controllers ­ The flexible, reliable ...

1

1 Desigo PXC Controllers ­ The flexible, reliable ...

The Desigo PXC automation and control system is optimized for control and monitoring of heating, ventilation, air conditioning plants and other technical plants in buildings. Scalability, energy efficiency, openness, and user-friendly operation sets it apart.
Desigo Control Point ­ embedded building operations
Desigo Control Point is designed to meet the requirements of different users in a building. Building operation and monitoring are enabled through intuitive touch panels on the control panel or via PC in the office. Through smart devices, users can also access related information anytime from any location.
Automation stations ­ scalable and open
Its scalability and openness distinguish the freely programmable automation stations for primary plants and meets all expectations associated with the control and monitoring of building services. Modular in design, the system can be ideally adapted to specific requirements and needs, making cost-effective DDC technology a possibility even in smaller HVAC systems. This innovative system strategy can add the PXC controller range in stages to a building automation and control system as needed and when required. Desigo PXC consistently supports open communications, making it easy to connect a wide variety of building services equipment based on standard open data interfaces.
KNX PL-Link field devices - easy to connect
Connect and replace KNX PL-Link devices without using any additional tools. Compatible field devices can be wired by using standard KNX twisted-pair cables. Up to 5 devices can be powered directly from the automation station before adding an external KNX power supply to run in maximum 64 KNX PL-Link nodes per KNX network and automation station.

A6V13054432_en--_d

3 | 24

2

... and scalable automation and control system

2 ... and scalable automation and control system

4 | 24

Scalable solutions
Whether small buildings or large complexes, standard or advanced solutions ­ with the Desigo PXC family you get the optimal control for any type of high performing buildings.
Smart engineering
With our license-free Desigo Engineering Framework, you can intuitively engineer and commission a wide range of products leveraging the sophisticated applications and growing libraries.
Simple integration
Integrate different protocols with no additional hardware or software in a consistent and harmonized workflow saving additional costs and efforts.
Secured connectivity
Our Desigo PXC controllers with on-board WLAN and cloud remote access meet the highest security standards.
Tested quality BACnet® Testing Laboratories (BTL) is a registered trademark. Products that are successfully tested by the BACnet Testing Laboratories may bear the BTL label.
A6V13054432_en--_d

Desigo Control Point ...

3

3 Desigo Control Point ...
Desigo Control Point is a consistent concept designed to simplify operation and monitoring of heating, ventilation, air conditioning, lighting, and shading in small or medium-sized buildings. It facilitates building operation and monitoring by allowing you to access your buildings and plants via touch panels, PC, or mobile device ­ wherever you are. Whether it is for maximizing room comfort, monitoring and operating your primary plant, or displaying your building data, Desigo Control Point is the answer.

Efficient and intuitive remote plant operation ...
... that is Desigo Control Point

A6V13054432_en--_d

5 | 24

4

... Embedded building operations

4 ... Embedded building operations

Function overview

 Plant graphic: Fast and targeted monitoring and  operation of the system using animated and reallife plant images.

 Schedulers: Central programming of all time-



controlled building services.

 Alarm management: Detailed overview of alarms to quickly locate and eliminate errors.

 Trending: Comfortable analysis of trend data to

optimize operations and increase energy

efficiency.

 Reporting: Customized snapshots of values



displayed in a report form. Reports are used to

analyze plant operation and for evaluation and



documentation purposes.

 Generic operation: An efficient tool for navigation 

through the hierarchical structure to all the data

points in the system. The user can then read or

manipulate the data points with the appropriate

access rights.

Energy monitoring: Display and compare energy consumption based on a comprehensive library of graphics and configurable elements.
Haystack interface: Access by external IT systems for BACnet objects in a Desigo system via Haystack tagging or Haystack REST APL. Haystack is an initiative to simplify data access to the Internet of Things (IoT), optimized to the needs of building automation and control (http://project-haystack.org/).
Heating curve: Graphical display of the heating curve with the ability to modify parameters.
Engineering: Flexible and efficient creation of customized operation, based on graphic libraries.
User management: Enabling functions and access rights for different user roles.

Plant graphic Schedulers

6 | 24

Trending

Alarm management Reporting
Energy monitoring A6V13054432_en--_d

... Embedded building operations

4

Simplify your plant and room operation
Desigo Control Point has a user-friendly interface, designed to simplify tasks such as alarm management, scheduling, trending, report creation and consumption visualization. The use of native BACnet ensures that third party devices can be integrated and operated in the same intuitive way. Managing your plant and room anywhere, anytime has never been so easy!

Access your building whenever you want
With Desigo Control Point, you can remotely connect with your building from multiple devices. HTML 5.0 technology allows operation independent of mobile device type, size, or orientation.

Enhance your room comfort Desigo Control Point makes it easy to manage the operation of all kinds of rooms. Whether it is a meeting room, office space, conference room, or event room ­ you can easily control climate, lights, and blinds. The high resolution graphics can be customized to suit all floor plans and room layouts.
Monitor your energy usage for additional savings With Desigo Control Point you can display and compare energy consumption using standard dashboard templates or customize your views using comprehensive dashboard functions. Share your energy history in public areas to encourage even more savings!
Operate and monitor your plant easily Desigo Control Point makes your local plant monitoring easy. The high resolution capacitive displays provide the ultimate user experience and intuitive operation. Alarming, scheduling and trending, as well as navigation via graphics, are all at your fingertips.

A6V13054432_en--_d

7 | 24

5 ... Portfolio

5 ... Portfolio

BACnet touch panels (BACnet/IP)
The BACnet/IP touch panels enable direct connections to any BACnet network. Thanks to the embedded web server, it is possible to access the system using a standard web browser. For installation and operation, no extra tools are required.

Product range overview
BACnet touch panels with integrated data management and web sever functionality
7.0 ", 10.1 ", 15.6 "

Type
PXM30.E PXM40.E PXM50.E

Data sheet A6V11664137

Client touch panels (TCP/IP)
When your project requires operation of the same system via multiple control panels, the TCP/IP touch panels are the right solution. Various web browser sessions and touch panels can connect to a centralized web server. This way, you can reduce the complexity and costs of larger installations.

Product range overview
Touch panel clients (TCP/IP) 7.0 ", 10.1 ", 15.6 "

Type
PXM30-1 PXM40-1 PXM50-1

Data sheet A6V11664139

BACnet web servers (BACnet/IP)
Desigo primary and room automation stations as well as third-party BACnet devices can be operated via BACnet/IP web servers ­ from the same network or remotely via an Internet connection to see what really matters.

Product range overview
BACnet web servers with standard and extended control point functionality

Type
PXG3.W100-2 PXG3.W200-2

Data sheet A6V12304192

8 | 24

A6V13054432_en--_d

Operation and monitoring

6

Location Office remotely

6 Operation and monitoring
Comfortable operation tailored at the right place
Intuitive operations provide excellent coverage of various requirements at the right place: On the panel, in the technical plant rooms or using a web browser from anywhere at any time. It permits inexpensive monitoring and operating of small to mid-sized plants.

Products

Application
Operate and monitor

User
Building operator

Panel doors

Office Touch panels

Remotely via web clients

On-site operation

Technical services manager

Panel

TXM

Field/Room

QMX

Manual

Service

intervention technician

Manual operation

User

Plant operation with Desigo Control Point ­ Embedded building operation
Designed to simplify building automation operation and monitoring tasks: Anytime from anywhere using a standard web browser.
Manual operation on the panel
The Desigo I/O modules include facilities for manual/emergency operation of plants and display operating states.

A6V13054432_en--_d

9 | 24

7

A family of programmable automation stations

7 A family of programmable automation stations

PXC4

PXC5

PXC7

The Desigo PXC range offers flexibility and ease of use in controlling and monitoring of building automation and control systems.
The modern system approach includes cloud connection to all PXC controllers as well as user-friendly operation via Desigo Control Point.
Comprehensive system functions such as alarm management, time scheduling, and trend data storage cover all the requirements associated with building operations.
Decentralized automation stations operate autonomously via networked BACnet communication, guaranteeing a high level of operational reliability. The automation stations also support BACnet Secure Connect (BACnet/SC) to protect communication between devices.
Integration of third-party devices via Modbus rounds out the list of feature for optimized controllers.
The ABT Site tool provides efficient engineering and commissioning via WLAN, Ethernet, or the cloud.

Alarm management
One of the most important functions of any building automation and control system is automatic alarm notification plant alarms. Alarm management (generation, display, and handling) must be simple, efficient, and consistent at all system levels. Desigo takes advantage of BACnet alarm functions and supports the following three types of alarms with up to 256 alarm priority levels:
 Basic alarms (no user interaction required)
 Simple alarms (acknowledgment required)
 Extended alarms (acknowledgement and alarm reset required)

Alarm messages
An alarm is automatically recorded, registered, and forwarded to a Desigo Control Point or to a Desigo management station. Meaningful alarm messages are also sent to remote devices.
Alarm lists provide an easy-to-read view of all pending and time-stamped alarms for straightforward processing.
Pop-up windows and optical/acoustic signals notify the operators.

10 | 24

A6V13054432_en--_d

A family of programmable automation stations

7

Alarm routing
Alarms are routed based on time and priority. This guarantees uninterrupted routing, even if the operator is unavailable. Overviews help the user to handle alarm situations quickly and correctly.

Scheduler/calendar
Schedulers control workflows and processes on basic building automation and control functions on a day-to-day basis. Ventilation, heating, and air conditioning are controlled based on office and operation hours in offices, banks, restaurants and schools.
Schedulers ensure that the temperature setpoints are lowered at night in the building. They also ensure that certain rooms are not air-conditioned during vacations and that holidays and plants are only operated as needed.
Scheduler programs are saved and processed directly in a decentralized manner on the automation level. The primary plants continue to operate autonomously in the event the network failures.

A6V13054432_en--_d

11 | 24

7

A family of programmable automation stations

Trend data storage
Fully integrated trend data stores real-time (online) and historical (offline) data. The trend functions allow the operator to monitor and fine tune plants.
The Desigo system uses trend log objects per BACnet standard; the objects are accessible by any other client. Gathering options: Query, change of value (COV) Trend options: Continuously, one-time pass, defined timeframe.

Trend graphics can also be displayed on the PXM30/40/50 touch panels and Desigo Control Point web clients.
Access rights to data
Access rights are comfort functions to filter information by the individual needs of the customer. In other words, resident engineers or service engineers, for example, only have access to the information on a strict-need-to-know basis. Only authorized personnel can access operator units and requires a name and password. The access rights can also be assigned in detail, down to individual data points. Desigo uses the following access levels:  Internal, extended service, and basic service  Administrator, extended operation, and basic operation
Handing certificates and IT security
Digital certificates ensure the IT security of the control system. This applies for both the built-in web-server and https communication while encrypting BACnet traffic using the BACnet/SC option. Handling of the appropriate certificates is an integral part of the engineering process; the ABT tool allows for easy handling of these tasks without special know how.

12 | 24

A6V13054432_en--_d

PXC4 automation stations

8

8 PXC4 automation stations
For the control of primary plants.  Compact automation station for HVAC and building control systems, freely
programmable  System functions such as alarming, schedulers, trend functions, and access
security  Stand-alone application or for use within a building automation and control
system  Direct connection of field devices  Extensions possible with TXM I/O modules  The following functions are available with KNX PL-Link bus:
­ Communication with room operator units and sensors. ­ Plug-and-play connection of Siemens field devices with KNX PL-Link.  Integration of communicative field devices, e.g. variable speed drives via Modbus  Engineering and commissioning with the user-friendly ABT Site tool  BTL tested BACnet communication on IP (BACnet/IP and BACnet/SC) or BACnet MS/TP, in compliance with the BACnet standard including B-BC profile (Rev. 1.15)  WLAN interface for engineering and commissioning  BACnet/SC support (as BACnet/SC node only)

PXC4.E16 variants Order number Number of inputs/outputs (Onboard)
Number of universal inputs/outputs (UIO) Number of relay outputs (DO) Number of inputs/outputs (Onboard + TXM) Number of integration data points (Modbus TCP and/or RTU) Total number TXM-I/Os and integration DPs Number of KNX PL-Link devices Number of configurable RS485 interfaces for Modbus RTU integration Number of BACnet/SC nodes connected to PXC4.E16/ PXC4.E16S acting as hub

PXC4.E16S 1) S55375-C108 2) 16 12 4 up to 40 0
40 3) 0 0
0 (node only)

PXC4.E16 1) S55375-C100 2) 16 12 4 up to 40 up to 40
80 3) up to 64 1
0 (node only)

1) Communication BACnet/IP, BACnet/SC: PXC4.E16 and PXC4.E16S. Communication BACnet MS/TP: PXC4.M16 and PXC4.M16S. 2) For details on engineering, see PXC4, PXC5 & PXC7 Planning overview, A6V13054435. 3) KNX PL-Link DPs do not count as integration points. For KNX PL-Link, only the limitation of BACnet objects have to be considered.
For more information about PXC4 automation stations, refer to the data sheets A6V11646018 and A6V11937668.

A6V13054432_en--_d

13 | 24

8

PXC4 automation stations

UIO Universal inputs/outputs support the following signal types:  Passive sensors LG-Ni 1000, 2x LG-Ni1000, Pt 1000 (375, 385), NTC 10k (Type II / Beta (0-50 °C) = 3892 K), NTC 100k
 Resistance sensors 1000 Ohm, 2500 Ohm, 1000...1175 Ohm (for setpoint shift)
 Voltage input analog DC 0...10 V.
 Binary potential-free contacts for signaling functions
 Counters to 25 Hz (electronic switch to 100 Hz)
 Analog outputs DC 0...10 V

DO

Relay outputs AC 250 V for binary controls, changeover contact (NO,

NC, pulse)

14 | 24

A6V13054432_en--_d

PXC5 system controllers

9

9 PXC5 system controllers
Freely programmable system controller that integrate Modbus and/or MS/TP devices or subsystems.
 BTL tested BACnet communication on IP (BACnet/IP and BACnet/SC) or BACnet MS/TP, in compliance with the BACnet standard including B-BC profile (Rev. 1.15)
 Modbus TCP/RTU and BACnet MS/TP  The following functions are available with KNX PL-Link bus:
­ Communication with room operator units and sensors. ­ Plug-and-play connection of Siemens field devices with KNX PL-Link.  IT security including HTTPS and BACnet/SC (as BACnet/SC hub)  WLAN interface for engineering and commissioning  System functions such as alarming, schedulers, trending, time sync, and life check  Grouping functionality e.g. common setpoints for room controls or energy demand  System and supervisory functionality  Integration of Modbus subsystems and devices via TCP and/or RTU: Data point mapping to BACnet/IP and supervisory functionality  Integration of BACnet MS/TP subsystems and devices: Supervisory functionality and routing to BACnet/IP

Type

PXC5.E003

Order number

S55375-C103 1)

Number of integration data points (Modbus TCP and/or RTU)

up to 500

Number of BACnet/MSTP devices per RS485 interface

up to 60 2)

Number of BACnet/SC devices as a BACnet/SC hub

up to 100

Number of KNX PL-Link devices

up to 64

Number of configurable RS485 interfaces either for integration of Modbus RTU or 2 BACnet MS/TP

1) For details on engineering, see PXC4, PXC5 & PXC7 Planning overview, A6V13054435. 2) Depending on the behavior of the third-party MS/TP devices
For more information about PXC5 system controllers, refer to the data sheet A6V11646020.

A6V13054432_en--_d

15 | 24

10 PXC7 automation stations

10 PXC7 automation stations
Freely programmable automation stations for HVAC, building services plants, and system controllers
 BTL tested BACnet communication on IP (BACnet/IP and BACnet/SC) or BACnet MS/TP, in compliance with the BACnet standard including B-BC profile (Rev. 1.15)
 Modbus TCP/RTU and BACnet MS/TP  The following functions are available with KNX PL-Link bus:
­ Communication with room operator units and sensors. ­ Plug-and-play connection of Siemens field devices with KNX PL-Link.  IT security including HTTPS and BACnet/SC (as BACnet/SC hub)  WLAN interface for engineering and commissioning  System functions such as alarming, schedulers, trending, time sync, and life check  Grouping functionality e.g. common setpoints for room controls or energy demand  System functionality for integrated subsystem and devices  Integration of Modbus subsystems and devices via TCP and/or RTU: Data point mapping to BACnet/IP and supervisory functionality  Integration of BACnet MS/TP subsystems and devices: Supervisory functionality and routing to BACnet/IP

PXC7 variants

E400S

E400M

E400L

Order number

S55375-C111 1) S55375-C110 1) S55375-C105 1)

Number of TXM inputs and outputs

up to 100

up to 200

up to 400

Number of integration data points (Modbus TCP and/or RTU)

up to 100

up to 200

up to 400

Total number TXM-I/Os and integration DPs 100 2)

250 2)

600 2)

Number of BACnet/SC devices connected as up to 100 nodes

up to 100

up to 100

Number of BACnet MS/TP devices in a field level network

up to 60 3)

up to 120 3) (2 x 60)

up to 240 3) (4 x 60)

Number of KNX PL-Link devices

up to 64

up to 64

up to 64

Number of configurable RS485 interfaces

1

2

4

either for integration of Modbus RTU or

BACnet MS/TP

1) For details on engineering, see PXC4, PXC5 & PXC7 Planning overview, A6V13054435. 2) KNX PL-Link DPs do not count as integration points. For KNX PL-Link, only the limitation of BACnet objects have to be considered. 3) Depending on the behavior of the third-party MS/TP devices.
For more information about PXC7 automation stations, refer to the data sheet A6V12505052.

16 | 24

A6V13054432_en--_d

11 TXM input/output modules for PXC7 and PXC4

11 TXM input/output modules for PXC7 and PXC4

Flexible input and output modules for sensors and actuators

Type TXM1.xxx Number of inputs/outputs Number of universal inputs/outputs (UIO) Number of universal inputs/outputs (XIO) Number of relay outputs (DO) Number of digital inputs (DI) Number of TRIAC Number of Inputs (P)

8D 16D 8U 8U-ML 8X 8X-ML 6R 6R-M 8P

8 16 8

8

8

8

6

6

8

8

8

8

8

6

6

8 16

8

8T 4D3R

8

7

3 4 6

Local override LCD indication 3 color I/O status LED Green I/O status LED

-

-

-



-



-



-

-

-

-

-

-



-



-

-

-

-

-



-

-

-

-

-

-



-

-



-













-





-

UIO
XIO
DO TRIAC DI P

Universal inputs/outputs support the following signal types:  Passive sensors LG-Ni 1000, 2x LG-Ni1000, Pt 1000 (375, 385), NTC 10k (Type II / Beta (0-50 °C) = 3892 K), NTC 100k  Resistance sensors 1000 Ohm, 2500 Ohm, 1000...1175 Ohm (for setpoint shift)  Voltage input analog DC 0...10 V.  Binary potential-free contacts for signaling functions  Counters to 25 Hz (electronic switch to 100 Hz)  Analog outputs DC 0...10 V
Universal inputs/outputs support the following signal types:  Same as UIO, and in addition  Current input 4...20 mA or 0...20 mA  Current output 4...20 mA on outputs 5 to 8
Relay outputs AC 250 V for binary controls, changeover contact (NO, NC, pulse)
TRIAC: Permanent contact, pulse width modulation
Binary output: Status signal (NO/NC), Signal pulse, Meter 10 Hz (DI 1-8)
Pt100 4 wire, 0...250 Ohm, Pt1000 / 0...2500 Ohm, LG-Ni1000

TXM I/O modules with local operation

TXM1.6R-M

TXM1.8U-ML and TXM1.8X-ML

Local override, three-colored LEDs

Local override, LCD

A6V13054432_en--_d

17 | 24

12 KNX PL-Link field bus for "plug-and-play" field device communication

12 KNX PL-Link field bus for "plug-and-play"
field device communication
KNX PL-Link complies fully with the KNX standard. Communication between the PXC4, PXC5, and PXC7 automation stations and peripheral devices with KNX PLLink has been optimized so that plug-and-play functionality is available offering automatic device recognition, device connection, and device configuration. KNX PL-Link devices are configured by using the Desigo standard tools. The KNX commissioning software (ETS) is not needed.

Increased engineering and commissioning efficiency
Using KNX PL-Link devices together with the Siemens automation stations saves engineering and commissioning time. In addition, in service cases no engineering tool is required. If more than one device needs to be assigned to the automation station, following mechanisms are supported:
 Offline engineering using the KNX device ID (barcode sticker delivered together with the device).
 Offline engineering and online commissioning using the service pin from the KNX device.

Taking the maximum out of the automation stations
Per automation station up to 64 KNX PL-Link devices can be connected. KNX PLLink data points do not count as integration points. For KNX PL-Link, only the limitation of BACnet objects must be considered. The automation stations have an internal bus power supply for approximately 5 KNX PL-Link devices. If the integrated power supply is insufficient to cover the power demand, the internal bus power supply can be replaced by an external bus power supply unit.
Following KNX PL-Link devices are supported by the PXC4, PXC5 and PXC7 automation stations:

Device type Room sensors

Product No.
QMX3.P30 S55624-H103

Functions
Temperature sensor

QMX3.P40 S55624-H116

Multisensor for temperature and humidity

QMX3.P70 S55624-H104

 Multisensor for temperature, humidity, and CO2
 Air quality indicator with LED

18 | 24

A6V13054432_en--_d

12 KNX PL-Link field bus for "plug-and-play" field device communication

Device type
HVAC room operator units

Product No. QMX3.P34 S55624-H105
QMX3.P44 S55624-H143
QMX3.P74 S55624-H106

More device types are coming soon.

Functions
 Temperature sensor
 Segmented backlit display and touchkeys
 Multisensor for temperature and humidity
 Segmented backlit display and touchkeys
 Multisensor for temperature, humidity, and CO2
 Segmented backlit display and touchkeys

A6V13054432_en--_d

19 | 24

13 ABT Site ... for flexible and intuitive...
13 ABT Site ... for flexible and intuitive...
Professional software tools and a wide range of proven application function blocks are available for engineering automation stations.
ABT Site
The engineering tool ABT Site is a user-friendly software tool that is easy to use and geared toward technical processing of customer projects. This includes configuration, programming, commissioning, and final adjustments on the automation station with the associated program. A variety of report functions are available for documentation purposes. Thanks to the intuitive design, Desigo ABT Site makes it easy to begin working right away without time-consuming training. ABT Site supports certificate management for both secure communication between devices (BACnet/SC) and https communication (TLS certificate) with web servers embedded in the devices.
Efficient engineering with function blocks
The project-specific HVAC applications are configured, programmed, commissioned, and maintained using a programming editor with freely programmable graphical function charts, offering an intuitive and efficient engineering experience. A collection of over 250 predefined and tested function blocks are assembled to create the required controls applications. The programming editor can be used offline in the office or online in the plant room for fast and efficient commissioning thanks to actual process values displayed in the program structure.
ABT Go
ABT Go allows commissioning via an easy-to-use app from your mobile device. Functions such as I/O testing as well as reporting (including plant pictures) are included.

20 | 24

A6V13054432_en--_d

14 ... set-up, programming, and commissioning
14 ... set-up, programming, and commissioning

Set up system: Project settings/Building view

Set up data points: I/O configuration/Modbus editor

Program device: Graphical programming editor

Create graphics: Desigo Control Point offline engineering

Wiring test: Easy-to-use ABT Go mobile app to simplify commissioning. A6V13054432_en--_d

21 | 24

15 Can be extended in stages at any time
15 Can be extended in stages at any time
Improve operation, step-by-step
Desigo Control Point ­ embedded building operations - can be supplemented as needed in panels, rooms, or on a floor.
Increased ease of service
Remote operation via web solutions increases ease of service throughout the life of the building.
Desigo room automation
The unique and flexible solution for all room automation tasks to reduce energy consumption at a maximum level of comfort. Desigo room automation provides a product range of solutions with room operation for HVAC as well as lighting and shading.
Desigo CC ­ The integrated building management platform
The Desigo CC management platform offers comfortable, system-wide multistation operation of distributed building complexes, uniting innovative management of building comfort, security, and energy distribution.

22 | 24

A6V13054432_en--_d

A6V13054432_en--_d

23 | 24

Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies A6V13054432_en--_d

© Siemens Switzerland Ltd, 2022 Technical specifications and availability subject to change without notice.



References