Installation Instructions

Accessory Fan/Filter Status Switch

For Small Rooftop Units: Gas Heating/Electric Cooling, Electric Cooling and Heat Pump Units (50/60 Hz)

Part No. CRSTATUS001A00

Package Contents

Description QTY
Pressure Switch1
Control Tube (16 in.)1
Control Tube (32 in.)1
Plastic Cap1
Screw - 10AB X 5/8 in.1

Package Usage

NOTE: Not all unit sizes may be available at this time.

Compatibility Charts

Table 1 - Carrier Usage Chart

MODEL NUMBER SIZES
48/50FC04-16
48/50GC04-14
48/50HC04-14
48/50JC04-06
48/50KC04-06
48/50LC04-12
48/50TC07-16
50FCQ04-14
50GCQ04-12
50HCQ04-12
50KCQ04-06
50TCQ07-14

Table 2 - Bryant Usage Table

MODEL NUMBER SIZES
580J/558J07-16
582J/559J04-06
582K/559K04-16
581K/551K04-14
581J/551J04-14
547K04-14
549K04-12
549J04-12
547J04-06
548J07-14

Table 3 - ICP Usage Table

MODEL NUMBER SIZES
RGV/RAV036-180
RGW/RAW036-150
RGH/RAH036-150
RGX/RAX036-060
RGS/RAS072-180
RHV036-150
RHW036-120
RHH036-120
RHX036-060
RHS072-150

Important Information

IMPORTANT: Read these instructions completely before attempting to install the accessory fan/filter status switch.

Safety Considerations

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguisher available for all brazing operations.

It is important to recognize safety information. This is the safety-alert symbol . When you see this symbol on the unit and in instructions or manuals, be alert to the potential for personal injury.

Understand the signal words DANGER, WARNING, CAUTION, and NOTE. These words are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices, which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.

Installation

NOTE: The fan/filter status switch can be installed to monitor indoor fan status (ON/OFF) or filter status (CLEAN/DIRTY). Follow the procedure as detailed in this document to perform the steps necessary to install the pressure switch for the desired application (as either a fan status switch or a filter status switch, but not both).

WARNING: ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury or death. Disconnect power supply and install lockout tag before attempting to install accessory.

CAUTION: EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in damage to equipment. When removing panels from the unit, be careful not to damage the roof or other surfaces with the panels.

  1. Turn off power to the unit and install lock-out tag per the WARNING above.
  2. Remove the filter access panel; no tools are required. Reserve the panel for replacement in Step 12.
  3. Remove the pressure switch assembly from the carton. Attach the 32 in. plastic control tube to the pressure switch on the port nearest to the electrical connections. (See Figure 1.)
  4. Depending on the intended use:
    • Filter Switch: Attach the 16 in. plastic control tube to the pressure switch on the port nearest to the mounting bracket. (See Figure 1.)
    • Fan Switch: Attach the plastic cap to the pressure switch on the port nearest to the mounting bracket. (See Figure 1.)
  5. Attach the pressure switch assembly to the uppermost portion of the inner flange of the corner post with the 2 screws provided. (See Figure 1.)
  6. Route the 32 in. control tube through the slot in the coil baffle next to the harness assembly. The end of the control tube should be loose in the indoor fan area. (See Figure 1.)
  7. Filter Switch: Suspend the 16 in. control tube over the return air opening. (See Figure 1.)
  8. For units without DDC controls, route and connect the digital indicator wires coming from the thermostat to the terminals on the pressure switch. (See Figure 1 and 2.)
  9. For units with DDC controls, refer to the installation instructions for the DDC controls for proper wiring connection points for the Fan/Filter status switch.
  10. Return power to the unit.
  11. Depending on the intended use, configure the switch as follows:
    • Filter Switch: Place the unit in Fan Only mode. The unit return air filter should be clean or new. Using a flat head screwdriver, rotate the adjustment knob until the pressure switch closes. (See Figure 1.) After the pressure switch closes, rotate the adjustment knob 1/4 turn in the same direction.
    • Fan Switch: Rotate the adjustment knob two full turns.
  12. Reinstall the filter access panel reserved in Step 2.

Figure Descriptions:

Figure 1 - Fan/Filter Status Switch Installation (Top View of Typical Rooftop Unit Shown): This diagram illustrates the physical placement and routing of the fan/filter status switch, pressure switch, and control tubes within a rooftop unit. It shows the 32-inch control tube connected to the pressure switch and routed through a slot in the coil baffle towards the indoor fan area. The 16-inch control tube (for filter switch) is shown suspended over the return air opening. It also indicates routing of thermostat wires through a U-slot in the coil baffle for R-410A units.

Figure 2 - Mounting Fan/Filter Status Switch: This diagram provides a closer view of the pressure switch mounting. It shows the pressure switch with its adjustment knob, ports for control tubes, and terminals for thermostat wiring (labeled GRA for Ground, From Thermostat, and To Thermostat). It indicates the switch is mounted to the corner post of the unit.

Operation

Filter Switch Operation

When the pressure switch is set up as a filter switch, the digital indicator light on the thermostat lights up when the filter is dirty and needs to be replaced. If direct digital controls are used, the filter status (CLEAN/DIRTY) is sent over the communications bus.

Fan Switch Operation

When the pressure switch is set up as a fan switch, the digital indicator light on the thermostat is lit when the indoor fan is operating. If the indoor fan is being told to operate by the thermostat and the indicator light is not lit, service the unit immediately. If direct digital controls are used, the indoor fan operation status (ON/OFF) is sent over the communications bus.

Models: CRSTATUS001A00, Gas Heating Electric Cooling, CRSTATUS001A00 Gas Heating Electric Cooling, Heating Electric Cooling, Electric Cooling, Cooling

PDF preview unavailable. Download the PDF instead.

IIK-CRSTATUS01-02 Acrobat Distiller 22.0 (Windows)

Related Documents

Preview Carrier Variable Frequency Drive (VFD) Installation & Service Manual for Rooftop Units
Comprehensive installation, start-up, and service instructions for Carrier Variable Frequency Drive (VFD) factory-installed options in 48/50TC, 50TCQ, 48/50HC, 50HCQ, and 40RU 2-Stage cooling rooftop units (sizes 07-30). Includes troubleshooting, maintenance, and VFD parameter details for ABB ACH580, ACH550, and ACS320 models.
Preview Carrier Horizontal Roof Curb Adapter Installation Guide for 48/50FC, HC Units
Official installation instructions from Carrier for the Horizontal Roof Curb Adapter Accessory, compatible with 48/50FC and 48/50HC Single Package Rooftop Units (Sizes 17-30). Includes safety, features, and step-by-step installation guidance.
Preview Carrier 48/50PD Series Rooftop Units: Controls, Operation, and Service Guide
Comprehensive guide for Carrier 48/50PD series rooftop units, detailing controls, start-up, operation, service, and troubleshooting for electric cooling and gas heating systems with COMFORTLink™ controls.
Preview Carrier Small Rooftop Units Accessory Electric Heater and Single Point Box Installation Instructions
Installation instructions for Carrier Accessory Electric Heaters and Single Point Boxes for Small Rooftop Units (3-6 Tons), covering safety, package contents, general installation, wiring, and troubleshooting.
Preview Carrier 48/50K, 48/50V Ultraviolet Lamp Accessory Installation Instructions
Installation instructions for Carrier's 48/50K and 48/50V Series Ultraviolet (UV-C) Lamp Accessory, designed to neutralize mold and fungus in HVAC cooling coil sections. Includes safety precautions, installation steps, maintenance, operation, and troubleshooting.
Preview Carrier 48/50HC Rooftop Units Controls, Start-Up, Operation, and Troubleshooting Guide
Comprehensive guide for Carrier 48/50HC Series Single Package Rooftop Units with ComfortLink Controls Version 2.X and PURON® (R-410A) Refrigerant. Covers controls, start-up procedures, operation, and troubleshooting.
Preview Carrier 48/50LC Rooftop Units: SystemVu Controls Manual
Comprehensive guide for Carrier 48/50LC Series Single Package Rooftop Units, detailing SystemVu™ Controls (Version 4.X) for start-up, operation, and troubleshooting.
Preview Carrier 48/50V Package Rooftop Unit Accessory Roof Curb Installation Guide
Installation instructions for Carrier 48/50V Package Rooftop Units Accessory Roof Curbs. Includes safety considerations, part numbers, package contents, curb usage, and detailed assembly diagrams described textually.