LG LMU243HV Multi F Inverter Heat Pump Outdoor Unit

Performance Specifications

ParameterValueConditions
Cooling Capacity (Min.-Rated-Max.)8,400~24,000~25,000 Btu/h
Heating Capacity (Min.-Rated-Max.)10,080~24,600~29,000 Btu/h
Max. Heating Capacity at 5°F18,400 Btu/h
Max. Heating Capacity at 0°F16,730 Btu/h
Max. Heating Capacity at -4°F15,400 Btu/h
EER212.5
SEER222.5
COP4.2
HSPF29.4
Cooling Nominal Test ConditionsIndoor: 80°F DB / 67°F WB
Outdoor: 95°F DB / 75°F WB
Heating Nominal Test ConditionsIndoor: 70°F DB / 60°F WB
Outdoor: 47°F DB / 43°F WB

Electrical Specifications

ParameterValue
Power Supply208-230V, 60Hz, 1Ø
MOP (A)20
MCA (A)16.0
Recommended Fuse Size (A)20
Cooling Rated Amps (A)13.0
Heating Rated Amps (A)13.0
Compressor (A)12.0
Fan Motor (A)0.40
Locked Rotor Amps (A)16.0

Piping Specifications

ParameterValue
Refrigerant Charge (lbs.)3.97
Liquid Line Connection (in., O.D.)1/4 x 3
Vapor Line Connection (in., O.D.)3/8 x 3
Maximum Total Piping² (ft.)230.0
Min. / Max. ODU to IDU Piping (ft.)9.8 / 82.0
Piping Length (no add'l refrigerant, ft.)98.4
Maximum Elevation between ODU and IDU (ft.)49.2
Maximum Elevation between IDU and IDU (ft.)24.6

Features

  • Auto operation
  • Auto restart
  • Inverter (variable speed compressor)
  • Defrost / Deicing
  • Restart delay (three [3] minutes)
  • Self diagnosis
  • Soft start
  • Low ambient cooling down to 14°F

Operating Range

ConditionRange
Cooling (°F DB)14 to 118
Heating (°F WB)-4 to +64

Unit Data

ParameterValue
Refrigerant TypeR410A
Refrigerant ControlEEV
Sound Pressure (Cool / Heat) ±1 dB(A)³50 / 54
Net / Shipping Weight (lbs.)101.4 / 110.2
Heat Exchanger CoatingGold Fin™
Minimum No. of Indoor Units2
Maximum No. of Indoor Units3

Compressor

ParameterValue
TypeTwin Rotary
Quantity1
Oil / TypeFVC68D

Fan

ParameterValue
TypePropeller
Quantity1
Motor / DriveBrushless Digitally Controlled/Direct
Max. Airflow Rate (CFM)1,766

Dimensional Drawings

The second page of the document contains detailed dimensional drawings of the LMU243HV unit. These include various views such as top, front, side, and rear perspectives, along with a 3D representation. All dimensions are provided in inches, illustrating the physical size and layout of the outdoor unit, including connection ports and fan placement.

Notes

  • Acceptable operating voltage: 187V - 253V.
  • Piping lengths are equivalent.
  • Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
  • All power / communication cable must be minimum 14 AWG, 4-conductor, stranded, shielded or unshielded wire, and must comply with applicable local and national codes. If shielded, the wire must be grounded to the chassis at the outdoor unit only.
  • Power wiring size must comply with the applicable local and national codes.
  • Capacity ratings are net at 0 ft. above sea level, with 0 ft. level difference between outdoor and indoor units, and specific refrigerant pipe lengths. All capacities are net with a combination ratio between 95 - 105%.
  • Installation must follow instructions in the applicable LG installation manual.
  • Refer to the Combination Data Manual for combination capacity tables.
  • See the Performance Data Manual for sensible and latent capacities.

Optional Accessories

  • PI-485 - PMNFP14A1 MultiSITE Comm. Mgr.
  • PBACNBTR0A AC Smart 5
  • PACP5A000 ACP 5
  • Power Distribution Indicator (PDI) Premium - PQNUD1S41
  • Mobile LGMV - PLGMVW100
  • Drain Pan Heater - PQSH1203
  • Low Ambient Baffle Kit (Cooling operation to -4°F) - ZLABGP03A
Models: LMU243HV 24k BTU Outdoor Condenser, LMU243HV 24k, BTU Outdoor Condenser, Outdoor Condenser, Condenser

File Info : application/pdf, 2 Pages, 2.58MB

PDF preview unavailable. Download the PDF instead.

6d62b904632d366816c2f39afb75fd10

References

Adobe InDesign 17.1 (Windows) Adobe PDF Library 16.0.5; modified using iTextSharp 4.1.6 by 1T3XT

Related Documents

Preview LG LMU30CHV Multi F Inverter Heat Pump Outdoor Unit Specifications
Technical specifications and performance data for the LG LMU30CHV Multi F Inverter Heat Pump Outdoor Unit, including operating ranges, electrical requirements, piping details, and features.
Preview LG LMU24CHV Multi F Inverter Heat Pump Outdoor Unit Specifications
Technical specifications for the LG LMU24CHV Multi F Inverter Heat Pump Outdoor Unit, including performance, electrical, piping, features, and operating range data.
Preview LG LMU243HV Multi F Inverter Heat Pump Outdoor Unit Specifications
Detailed specifications for the LG LMU243HV Multi F Inverter Heat Pump Outdoor Unit, including performance data, electrical requirements, piping information, operating ranges, and unit data.
Preview LG KUMXB481A R32 Multi F Max Outdoor Unit Technical Specifications
Detailed technical specifications, performance data, and installation guidelines for the LG KUMXB481A R32 Multi F Max outdoor unit, including capacity, electrical, piping, and features for HVAC systems.
Preview LG ARNU053TRD4 Multi V Four-Way Ceiling Cassette - Technical Specifications
Detailed technical specifications and features for the LG ARNU053TRD4 Multi V Four-Way 2' x 2' Ceiling Cassette indoor unit, including performance data, electrical requirements, piping, controls, unit data, and dimensional information.
Preview LG Multi F / Multi F MAX Outdoor Unit Installation Manual
Comprehensive installation manual for LG Multi F and Multi F MAX outdoor units, covering safety instructions, general data, nomenclature, and detailed installation procedures for multi-zone heat pump systems.
Preview LG KUMXA301A R32 Multi F LGRED Outdoor Unit Specifications
Technical specifications and performance data for the LG KUMXA301A R32 Multi F LGRED Outdoor Unit, including cooling and heating capacities, electrical requirements, piping details, and operational features.
Preview LG KUMXA361A R32 Multi F MAX Outdoor Unit Technical Specifications
Detailed technical specifications for the LG KUMXA361A R32 Multi F MAX outdoor unit, including performance data, electrical requirements, piping limitations, and dimensions. Suitable for HVAC professionals and system designers.