LG LMU243HV Multi F Inverter Heat Pump Outdoor Unit

Performance Specifications

ParameterCooling Capacity (Btu/h)Heating Capacity (Btu/h)
Min.-Rated-Max.8,400~24,000~25,00010,080~24,600~29,000
Max. Heating Capacity at 5°F18,400
Max. Heating Capacity at 0°F16,730
Max. Heating Capacity at -4°F15,400
EER212.5
SEER222.5
COP4.2
HSPF29.4

Cooling Nominal Test Conditions: Indoor: 80°F DB / 67°F WB, Outdoor: 95°F DB / 75°F WB

Heating Nominal Test Conditions: Indoor: 70°F DB / 60°F WB, Outdoor: 47°F DB / 43°F WB

Electrical Specifications

ParameterValue
Power Supply208-230V, 60Hz, 1Ø
MOP (A)20
MCA (A)16.0
Recommended Fuse Size (A)20
Cooling Rated Amps (A)13.0
Heating Rated Amps (A)13.0
Compressor (A)12.0
Fan Motor (A)0.40
Locked Rotor Amps (A)16.0

Piping Specifications

ParameterValue
Refrigerant Charge (lbs.)3.97
Liquid Line Connection (in., O.D.)1/4 x 3
Vapor Line Connection (in., O.D.)3/8 x 3
Maximum Total Piping² (ft.)230.0
Min. / Max. ODU to IDU Piping (ft.)9.8 / 82.0
Piping Length (no add'l refrigerant, ft.)98.4
Maximum Elevation between ODU and IDU (ft.)49.2
Maximum Elevation between IDU and IDU (ft.)24.6

ODU = Outdoor Unit, IDU = Indoor Unit

Features

Operating Range

Unit Data

Compressor

Fan

Notes

  1. Acceptable operating voltage: 187V - 253V.
  2. Piping lengths are equivalent.
  3. Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
  4. All power / communication cable to be minimum 14 AWG, 4-conductor, stranded, shielded or unshielded wire, and must comply with applicable local and national codes. If shielded, the wire must be grounded to the chassis at the outdoor unit only.
  5. Power wiring size must comply with the applicable local and national codes.
  6. This data is rated 0 ft. above sea level, with 0 ft. level difference between outdoor and indoor units, and the following refrigerant pipe lengths: LMU183HV: 16.4 ft. x 2 = 32.8 ft.; LMU243HV: 16.4 ft. x 3 = 49.2 ft.; LMU303HV: 16.4 ft. x 4 = 65.6 ft.; LMU363HV: 16.4 ft. x 4 = 65.6 ft. All capacities are net with a combination ratio between 95 - 105%.
  7. Must follow installation instructions in the applicable LG installation manual.
  8. Refer to the Combination Data Manual for combination capacity tables.
  9. See the Performance Data Manual for sensible and latent capacities.

Optional Accessories

Related Indoor Units

The LMU243HV outdoor unit is compatible with various indoor units, including the PT-QAGW0 2'x2' Cassette Panel and the LCN128HV4 Multi F Ceiling Cassette Indoor Unit. Refer to specific product literature for detailed matching system information.

PT-QAGW0 2' x 2' Cassette Panel Specifications

Unit Data

LCN128HV4 Multi F Ceiling Cassette Indoor Unit Specifications

Performance

Electrical

Piping

Controls Features

Included Accessories

Required Accessories

Optional Accessories

Unit Data

Fan

Notes

  1. Acceptable operating voltage: 187V-253V.
  2. Sound Pressure levels are tested in an anechoic chamber under ISO Standard 3745.
  3. Removable Washable Filter size: 14" x 14" x 1".
  4. See Engineering Manual for sensible and latent capacities.
  5. All communication / connection (power) cable from the outdoor unit to the indoor unit is field supplied and must be a minimum of four-conductor, 18 AWG, stranded, shielded or unshielded (if shielded, it must be grounded to the chassis of the outdoor unit only), and must comply with applicable local and national codes.
  6. Power wiring cable size must comply with the applicable local and national code.
  7. The indoor unit comes with a dry helium charge.
  8. Corresponding refrigerant piping length is in accordance with standard length of each outdoor unit and the level difference is 0 ft. All capacities are net with a combination ratio between 95 - 105%.
  9. Must follow installation instructions in the applicable LG installation manual.

General Information

For a complete list of available accessories, contact your LG representative. For continual product development, LG reserves the right to change specifications without notice.

© LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG Life's Good" is a registered trademark of LG Corp. /www.lghvac.com

PDF preview unavailable. Download the PDF instead.

lg-l2h24c12120000-specification-sheet PyPDF2

Related Documents

PreviewLG LMU243HV Multi F Inverter Heat Pump Outdoor Unit Specifications
Detailed technical specifications, performance data, electrical requirements, and piping details for the LG LMU243HV Multi F Inverter Heat Pump Outdoor Unit, suitable for multi-zone HVAC applications.
PreviewLG LMU24CHV Multi F Inverter Heat Pump Outdoor Unit Specifications
Technical specifications for the LG LMU24CHV Multi F Inverter Heat Pump Outdoor Unit, including performance, electrical, piping, features, and operating range data.
PreviewLG KUMXA301A R32 Multi F LGRED Outdoor Unit Specifications
Technical specifications and performance data for the LG KUMXA301A R32 Multi F LGRED Outdoor Unit, including cooling and heating capacities, electrical requirements, piping details, and operational features.
PreviewLG Multi F / Multi F MAX Outdoor Unit Installation Manual
Comprehensive installation manual for LG Multi F and Multi F MAX outdoor units, covering safety instructions, general data, nomenclature, and detailed installation procedures for multi-zone heat pump systems.
PreviewLG ARUN060GSS4 Multi V S Heat Pump 5.0 Ton Outdoor Unit Specifications
Detailed specifications and AHRI certified data for the LG ARUN060GSS4 Multi V S Heat Pump 5.0 Ton Outdoor Unit, including performance, electrical, compressor, fan, piping, and dimensional information.
PreviewLG KUMXB241A R32 Multi F Outdoor Unit Technical Specifications
Comprehensive technical datasheet for the LG KUMXB241A R32 Multi F Outdoor Unit, detailing performance, electrical, piping, features, and operating parameters for HVAC installations.
PreviewLG KUMXA361A R32 Multi F MAX Outdoor Unit Technical Specifications
Detailed technical specifications for the LG KUMXA361A R32 Multi F MAX outdoor unit, including performance data, electrical requirements, piping limitations, and dimensions. Suitable for HVAC professionals and system designers.
PreviewLG Multi F & Multi F MAX Heat Pump Systems Engineering Manual
Comprehensive engineering manual detailing LG's Multi F and Multi F MAX multi-zone heat pump systems, covering design, selection, installation, technical specifications, and electrical connections for HVAC professionals.