Enviro-Tech INSTALLATION INSTRUCTIONS URINAL FLUSH VALVE
ET3-R
Diagrams showing the Enviro-Tech ET3-R urinal flush valve components and water rating.
Thank you for purchasing this Enviro-Tech product.
INSTALLATION INSTRUCTIONS ET-3R URINAL FLUSH VALVE
Enviro-Tech strongly recommends using a qualified and registered plumber and electrician for installation. Ensure all pipework is flushed adequately, especially in new builds or where lines have been disrupted. Components of sensor products are particularly susceptible to debris and require more thorough flushing than standard plumbing fixtures. IMPORTANT: Flush pipe must be DN20 copper pipe or equivalent. Installation must comply with AS/NZS3500. Incorrect installation is NOT covered by your warranty.
TECHNICAL SPECIFICATIONS
Function | ET3-R |
---|---|
Power Input | AC: 220-240V 50/60Hz |
Power Consumption | 900 mA |
Water Pressure | 100 kPa - 500 kPa (recommended 350 kPa) |
Inlet/Outlet Diameter | 15 mm (1/2 G) |
Detection Zone | 1600 x 1000 mm (adjustable) |
Inductive Confirmation Time | 6 times within 5 seconds |
Confirmation Time After Use | 5 seconds |
Flush Time | 4 seconds (adjustable) |
Reset Time After Flush | 20 seconds |
Trap Seal Protection | Automatic flush every 6 hours if not used |
Flush Delay Time | After user leaves: 30 seconds |
COMPONENTS
Diagrams illustrating the main components: Solenoid Valve, Sensor, Transformer, and Bracket.
- Solenoid Valve
- Sensor
- Transformer
- Bracket
SOLENOID VALVE INSTALLATION
- Flush pipework thoroughly. Failure to do so will result in the solenoid sticking soon after installation, which is NOT covered by your product warranty.
- Attach the bracket, then insert the solenoid valve.
- Connect the water feed to the inlet valve.
- Connect the outlet to the urinal.
Illustrations showing correct and incorrect cable connections for the solenoid valve, and the mounting of the solenoid valve with screws.
SENSOR INSTALLATION
Note: Ceiling must be level. If the ceiling is sloping/pitched, the detection zone will be altered.
For Single Urinals:
- Drill a 70 mm hole in the ceiling, centered on the urinal and 100 mm from the wall/back of the urinal to the center of the sensor.
- Remove the screws from the sensor plate and install the flush box into the ceiling using the screw clips. Ensure the screw holes are aligned as shown.
- Make any required changes to flush time or pre-flush settings (refer to pages 4 & 5). Refix the sensor plate using the 2 screws. Ensure sensor plate screws are parallel to the wall for a single urinal.
Diagrams illustrating the sensor installation for a single urinal, including hole size, placement relative to the wall, and screw alignment.
For Twin or Trough Urinals:
- Drill a 70 mm hole in the ceiling, centered on the trough or the 2 individual urinals, and 300 mm from the wall/back of the urinal to the center of the sensor.
- Remove the screws from the sensor plate and install the flush box into the ceiling using the screw clips. Ensure the screw holes are aligned as shown.
- Make any required changes to flush time or pre-flush settings (refer to pages 4 & 5). Refix the sensor plate using the 2 screws. Ensure sensor plate screws are aligned facing the wall for twin or trough urinals.
Diagrams illustrating the sensor installation for twin or trough urinals, including hole size, placement relative to the wall, and screw alignment.
CABLE CONNECTIONS OF ET3-R
- Insert and connect the male-to-male connection cable between the sensor and the solenoid (Fig 1).
- Connect the sensor to the transformer using WAGO connectors. Ensure marked taped ends go together in one connector, and unmarked ends go into the other (Fig 1).
- Lock the WAGO connectors and then connect the transformer to mains power (Fig 2). The system will run a test and be ready to use.
Diagrams showing the cable connections between the solenoid valve, sensor, and transformer, including WAGO connector usage and mains power connection.
DISTANCE
Turn the potentiometer clockwise to increase the sensing distance and anti-clockwise to decrease it.
FACTORY SETTINGS
- Pre-flush is "ON".
- Time is "4".
- "1-10 Jumper Right" is set at 350 kPa, giving a flush volume of 0.8 L for a single urinal.
PRE-FLUSH ON/OFF
- Factory setting is 'ON' with the jumper set to the 'Right'.
- To turn pre-flush 'OFF', set the jumper to the 'Left'.
FULL FLUSH TIME
- Set the jumper to the 'Left' to choose 11-20s (where 20s = 0s).
- Set the jumper to the 'Right' to choose 1-10s (where 10s = 0s).
- Set the coding wheel to the required flush time. Refer to the table on the next page for full details of flush volumes and time setting options for different urinal types.
Diagram of the control board showing the Potentiometer (Distance sensitivity adjustment), Coding Wheel (Flush Time adjustment), Fuse, and Jumpers for Pre-flush and Time settings.
FLUSH VOLUME SETTINGS
Time settings for flush volumes without 'pre-flush':
Urinal Type | Dynamic Pressure | Time Setting | Flush Volume |
---|---|---|---|
Single Urinal | 350 kPa | 6 s | 0.8 L |
500 kPa | 5 s | ||
Twin Urinal | 350 kPa | 12 s | 1.6 L |
450 kPa | 11 s | ||
500 kPa | 10s (10=0) | ||
Slab/Trough Urinal | 350 kPa | 19s | 2.4 L |
400 kPa | 17s | ||
450 kPa | 16s | ||
500 kPa | 15s |
Time settings for flush volumes with 'pre-flush':
Urinal Type | Dynamic Pressure | Time Setting | Flush Volume |
---|---|---|---|
Single Urinal | 350 kPa | 4 s | 0.8 L |
500 kPa | 3 s | ||
Twin Urinal | 350 kPa | 8 s | 1.6 L |
450 kPa | 7 s | ||
550 kPa | 6 s | ||
Slab/Trough Urinal | 350 kPa | 12s | 2.4 L |
400 kPa | 11s | ||
500 kPa | 10s (10=0) |
DETECTION ZONE (GUIDE ONLY)
2.4 M Height Installation
Urinal Type | Side View | Front View | Top View |
---|---|---|---|
Single Urinal | Diagram showing side view of detection zone for a single urinal at 2.4m height. |
Diagram showing front view of detection zone for a single urinal at 2.4m height. |
Diagram showing top view of detection zone for a single urinal at 2.4m height. |
Twin Urinals | Diagram showing side view of detection zone for twin urinals at 2.4m height. |
Diagram showing front view of detection zone for twin urinals at 2.4m height. |
Diagram showing top view of detection zone for twin urinals at 2.4m height. |
Slab Urinal | Diagram showing side view of detection zone for a slab urinal at 2.4m height. |
Diagram showing front view of detection zone for a slab urinal at 2.4m height. |
Diagram showing top view of detection zone for a slab urinal at 2.4m height. |
3 M Height Installation
Urinal Type | Side View | Front View | Top View |
---|---|---|---|
Single Urinal | Diagram showing side view of detection zone for a single urinal at 3m height. |
Diagram showing front view of detection zone for a single urinal at 3m height. |
Diagram showing top view of detection zone for a single urinal at 3m height. |
Twin Urinals | Diagram showing side view of detection zone for twin urinals at 3m height. |
Diagram showing front view of detection zone for twin urinals at 3m height. |
Diagram showing top view of detection zone for twin urinals at 3m height. |
Slab Urinal | Diagram showing side view of detection zone for a slab urinal at 3m height. |
Diagram showing front view of detection zone for a slab urinal at 3m height. |
Diagram showing top view of detection zone for a slab urinal at 3m height. |
TROUBLESHOOTING
PROBLEM | POSSIBLE CAUSE | SOLUTION |
---|---|---|
No water out or will not stop running | Most common: Plugs not connected correctly. No water supply or No Power. | - Check water and power supply. - Unplug all cables, leave unplugged for 5 minutes, then reconnect everything carefully. Clean filter. Clean/replace solenoid. |
Too little water flow | Water pressure is low or turned down. | Adjust/raise the water pressure. |
Flow Valve needs adjusting. The filter or solenoid is blocked. | Adjust flow valve on solenoid. Clean the filter. Clean/replace the solenoid. |
|
Too much water flow | Water pressure is too high. Flow valve needs adjusting. | Adjust/lower the water pressure. Adjust flow valve on solenoid. |
Flush time or sensing distance is not adequate | Sensor requires adjustment. | See the 'Settings' section of this manual for instructions. |
For detailed troubleshooting advice, visit the Enviro-Tech websites enviro-tech.com.au or enviro-tech.co.nz or call the contact numbers provided.
Enviro-Tech WARRANTY
This Enviro-Tech product is guaranteed for 12 months from the date of purchase. This is a parts-only warranty, and Enviro-Tech is not liable for any associated costs incurred in the replacement or repair of any item. For full warranty conditions, see the Warranty page on the Enviro-Tech websites.
AFTERCARE
Ensure good water quality is maintained and the filter on the solenoid valve is cleaned regularly. Failure to do so could result in a blocked solenoid, impair product functionality, and may invalidate your product warranty. Surfaces should be maintained using a clean, damp cloth; no abrasive agents or materials should be used or come into contact with the surface finish, as this will invalidate your warranty.
This Enviro-Tech product is manufactured strictly to adhere to the ISO9001 standard, WaterMark certification, and WELS standards. Enviro-Tech reserves the right to update product technology at any time.