Product Overview
The nVent RAYCHEM S-20 Splice Kit is designed for creating reliable and safe splices for heating cables in various applications, including hazardous areas. It ensures proper electrical connection and environmental protection for the splice point.
Components and Tools
Hazardous Area Certifications
The BTV and QTVR cable types, when used with the S-20 splice kit, are certified for hazardous area applications according to various international standards.
Area Type | ATEX / UKEX | IECEx | North America (cCSAus) |
---|---|---|---|
BTV | SGS20ATEX0048X / BAS21UKEX0497X Ex II 2 G Ex 60079-30-1 eb IIC T6 Gb Ex II 2D Ex 60079-30-1 tb IIIC T80°C Db Ex II 2 G Ex 60079-30-1 eb mb IIC T6 Gb Ex II 2 D Ex 60079-30-1 mb tb IIIC T80°C Db Tmin -60°C | IECEx BAS.06.0043X Ex 60079-30-1 eb IIC T6 Gb Ex 60079-30-1 tb IIIC T80°C Db Ex 60079-30-1 eb mb IIC T6 Gb Ex 60079-30-1 mb tb IIIC T80°C Db Tmin -60°C | cCSAus Certificate 1333271 Class I Division 2 Group A,B,C,D Class II Division 2 Group E, F,G Class III T6 Zone when installed with S-20: US: Class I Zone 1 AEx eb IIC T6 Gb Zone 21 AEx tb IIIC T85°C Db Canada: Ex 60079-30-1 IIC T6 Gb Ex 60079-30-1 IIIC T85°C Db |
QTVR | SGS20ATEX0050X / BAS21UKEX0498X Ex II 2 G Ex 60079-30-1 eb IIC T4 Gb Ex II 2D Ex 60079-30-1 tb IIIC T130°C Db Ex II 2G Ex 60079-30-1 eb mb IIC T4 Gb Ex II 2D Ex 60079-30-1 mb tb IIIC T130°C Db Tmin -60°C | IECEx BAS.06.0045X Ex 60079-30-1 eb IIC T4 Gb Ex 60079-30-1 tb IIIC T130°C Db Ex 60079-30-1 eb mb IIC T4 Gb Ex 60079-30-1 mb tb IIIC T130°C Db Tmin -60°C | cCSAus Certificate 1333271 Class I Division 2 Group A,B,C,D Class II Division 2 Group E, F,G Class III T4 Um= 277 V max. Zone when installed with S-20: US: Class I Zone 1 AEx eb IIC T4 Gb Zone 21 AEx tb IIIC T135°C Db Canada: Ex 60079-30-1 IIC T4 Gb Ex 60079-30-1 IIIC T135°C Db |
EAC Ex: ООО Центр «ПрофЭкс» ЕАЭС RU C-BE.АЖ58.В.01728/21 1 Ex e IIC T* Gb X Ex tb IIIC T* Db X ТЕМП ОКР СРЕДЫ –60 to +56°C
* Hazardous area definitions in multiple languages are provided in the original document.
Specific Conditions of Use
- Maximum exposure temperature: 110°C (230°F)
- Minimum exposure temperature: -60°C (−76°F)
- Minimum installation temperature: -20°C (-4°F)
- Maximum current: 35A (for QTVR type)
- For use with heating cable types specified in the table.
Installation Instructions
⚠️ WARNING: Please ensure installation is performed in a clean, dry environment. All cable ends must be protected from moisture. Follow instructions carefully.
⚠️ WARNING: The purchaser must inform the manufacturer of any external effects or aggressive substances the equipment may be exposed to.
General Requirements:
- A ground fault circuit interrupter (GFCI) is required for each circuit.
- Ensure all circuits are de-energized before installation or servicing.
- Keep heating cable ends and kit components dry during installation.
- The electrically conductive covering (braid) of the heating cable must be connected to a suitable earthing terminal.
- The presence of heating cables must be clearly indicated by warning signs or markings at appropriate locations and intervals along the circuit.
- The insulation resistance of the heating cable must be measured and recorded after installation; it shall not be less than 20 MOhm.
- Personnel involved in the installation and testing of electric trace heating systems must be adequately trained in all required special techniques.
- Installation must be carried out under the supervision of a qualified person.
Step-by-Step Installation (Textual Description of Diagrams):
Preparation:
Right Side Preparation (for joining to another cable):
Joining the two prepared ends:
Contact Information
For sales and support, please contact nVent RAYCHEM in your region:
- Belgium/Luxembourg: Tel +32 16 21 35 02, Fax +32 16 21 36 04, salesbelux@nVent.com
- Bulgaria: Tel +359 5686 6886, Fax +359 5686 6886, salesee@nVent.com
- Czech Republic: Tel 420 602 232 969, czechinfo@nVent.com
- Denmark: Tel +45 70 11 04 00, salesdk@nVent.com
- Germany: Tel 0800 1818205, Fax 0800 1818204, salesde@nVent.com
- Spain: Tel +34 911 59 30 60, Fax +34 900 98 32 64, ntm-sales-es@nVent.com
- France: Tél 0800 906045, Fax 0800 906003, salesfr@nVent.com
- Croatia: Tel +385 1 605 01 88, Fax +385 1 605 01 88, salesee@nVent.com
- Italy: Tel +39 02 577 61 51, Fax +39 02 577 61 55 28, salesit@nVent.com
- Lithuania/Latvia/Estonia: Tel +370 5 2136633, Fax +370 5 2330084, info.baltic@nVent.com
- Hungary: Tel +36 1 253 7617, Fax +36 1 253 7618, saleshu@nVent.com
- Netherlands: Tel 0800 0224978, Fax 0800 0224993, salesnl@nVent.com
- Norway: Tel +47 66 81 79 90, salesno@nVent.com
- Austria: Tel 0800 29 74 10, Fax 0800 29 74 09, salesat@nVent.com
- Poland: Tel +48 22 331 29 50, Fax +48 22 331 29 51, salespl@nVent.com
- Republic of Kazakhstan: Tel +7 7122 32 09 68, Fax +7 7122 32 55 54, saleskz@nVent.com
- Russia: Тел +7 495 926 18 85, Факс +7 495 926 18 86, salesru@nVent.com
- Serbia and Montenegro: Tel +381 230 401 770, Fax +381 230 401 770, salesee@nVent.com
- Switzerland: Tel. 41 (41) 766 30 80, Fax 41 (41) 766 30 81, infoBaar@nVent.com
- Finland: Puh. 0800 11 67 99, salesfi@nVent.com
- Sweden: Tel +46 31 335 58 00, salesse@nVent.com
- Turkey: Tel +90 560 977 6467, Fax +32 16 21 36 04, salesee@nVent.com
- United Kingdom: Tel 0800 969 013, Fax 0800 968 624, salesthermalUK@nVent.com