Lennox R-454B Rooftop Units Comparison
Product Overview
This document provides a comprehensive comparison of Lennox R-454B rooftop units across different models: LTM, Lumière, Xion™, and Raider®. The comparison covers various aspects including electrical and gas/electric configurations, efficiency levels, control systems, accessibility, reliability, and indoor air quality features.
Model Specifications Comparison
Table A: Unit Specifications
Brand | Modèle LTM | Lumière | Xion™ | Raider® |
---|---|---|---|---|
Electricity/Electric | 3 to 25 tons (LCM) | 3 to 30 tons (LCT) | 2 to 25 tons (LCX) | 3 to 12.5 tons (ZCD) |
Gas/Electricity | 3 to 25 tons (LGM) | 3 to 30 tons (LGT) | 2 to 25 tons (LGX) | 3 to 12.5 tons (ZGD) |
Heat Pump | - | 3 to 25 tons (LHT) | 2 to 20 tons (LHX) | 3 to 10 tons (ZHD) |
Dual Fuel | - | 3 to 25 tons (LDT) | - | - |
Efficiency Levels | Ultra-high | Maxi | Standard | Standard |
Unit Controller | Lennox CORE® | Lennox® BASE | Lennox® CORE Lite | Base A2L Controller |
Humidity Control | Humiditrol+™ (HGRH Modulating), EDH | Humiditrol® (HGRH On/Off) | Humiditrol® (HGRH On/Off) | - |
Access Panels | Standard | Standard | Option (factory) | All models |
Independent Circuits | All models | All models | All models | Replacement support |
Footprint | Lennox | Lennox | Lennox | Raider® |
Control Types
Modèle LTM | Lumière | Xion™ | Raider® | |
---|---|---|---|---|
Thermostat 24 V | Standard | Standard | Standard | Standard |
Zone Sensor | Standard | Standard | Standard | - |
Humidity Control | 24V, 0-10VDC, CS8500, BAS | 24V, 0-10VDC, CS8500, BAS | 24V, 0-10VDC, CS8500, BAS | - |
BACnet® MS/TP | Standard | Standard | Standard | - |
IP BACnet® | Option (field/factory) | Option (field/factory) | Option (field) - Q3 2025 | 3rd party (field) |
LonTalk® | Option (factory) | Option (factory) | - | - |
LSE Novar® | Option (factory) | Option (factory) | - | - |
Return Air Control | Standard | MZVAV - Standard | Standard | - |
Box Size - A
3 to 6 tons | 3 to 6 tons | 2 to 6 tons | 3 to 6 tons | |
---|---|---|---|---|
Cooling Stages | Variable speed | 2 | 2-5 T (1) 6 T (2) | 3-5 T (1) 6 T (2) |
Gas Heating Stages | 2 | Up to 2 | Up to 2 | Up to 2 |
Fan Type | Direct drive | Direct drive, belt drive | Direct drive, belt drive | Direct drive, belt drive |
Fan Control | SZVAV, MZVAV | MSAV® | CAV, MSAV® | CAV, MSAV® |
SEER2/IEER (up to) | 21.2 / 23.1 | 17.5 / 17.3 | 14 / 15.5 | 13.4 / 15.5 |
EER (up to) | 14.3 | 13.5 | 11.5 | 11.0 |
Box Size - B
7.5 to 12.5 tons | 6.5 to 12.5 tons | 7.5 to 12.5 tons | 7.5 to 12.5 tons | |
---|---|---|---|---|
Cooling Stages | Variable speed | 3 | 3 | 3 |
Gas Heating Stages | 2 | 2 | 2 | 2 |
Fan Type | Direct drive | Belt drive | Belt drive, belt drive | Belt drive, belt drive |
Fan Control | SZVAV, MZVAV | MSAV®, MZVAV | VFD | VFD |
IEER (up to) | 21.0 | 17.0 | 15.0 | 15.0 |
EER (up to) | 12.7 | 12.7 | 11.2 | 11.2 |
Box Size - C/D
13 to 25 tons | 13 to 30 tons | 15 to 25 tons | S/O | |
---|---|---|---|---|
Cooling Stages | Variable speed | Up to 4 | Up to 4 | - |
Gas Heating Stages | Up to 4 | Up to 4 | - | |
Fan Type | Belt drive | Belt drive | Belt drive | Belt drive |
Fan Control | SZVAV, MZVAV | MSAV®, MZVAV | MSAV® | MSAV® |
IEER (up to) | 19.0 | 16.2 | 14.2 | - |
EER (up to) | 12.2 | 12.2 | 11.0 | - |
Exterior Air Features
Feature | Modèle LTM | Lumière | Xion™ | Raider® |
---|---|---|---|---|
ULL Economizer | Option (field/factory) | Option (field/factory) | Option (field/factory) | Option (field/factory) |
Standard Economizer | - | - | - | - |
Motorized OA | Option (factory) | Option (factory) | Option (factory) | Option (factory) |
Manual OA | Option (factory) | Option (factory) | Option (factory) | Option (factory) |
Exhaust Fan | Option (field/factory) | Option (field/factory) | Option (factory) | Option (factory) |
Reliability Features
Feature | Modèle LTM | Lumière | Xion™ | Raider® |
---|---|---|---|---|
Refrigerant Leak Detection System (SDR) | Standard | Standard | Standard | Standard |
High Pressure Switch | Standard | Standard | Standard | Standard |
Indoor Coil Protection (Freeze) | Standard | Standard | Standard | Standard |
Low Pressure Switch | Standard | Standard | Standard | Standard |
3-Strike Protection | Standard | Standard | Standard | Standard |
SCCR up to 100kA | Option (factory) | Option (factory) | Option (factory) | - |
Coil/Hail Protection | Option (field/factory) | Option (field/factory) | Option (factory) | Option (factory) |
Drain Pan Overflow Switch | Option (field/factory) | Option (field/factory) | Option (factory) | Option (factory) |
Dirty Filter Switch | Option (field/factory) | Option (field/factory) | Option (factory) | Option (factory) |
Fan Verification | Standard | Standard | Standard | Standard |
Standard Mechanical Cooling Range | 0-125 °F | 0-125 °F | 2-6T: 0-125 °F; 7.5-25 Ton: 45-125 °F | 45-125 °F |
Serviceability Features
Feature | Modèle LTM | Lumière | Xion™ | Raider® |
---|---|---|---|---|
Hinged Access Panels | Standard | Standard | Option (factory) | - |
Base Service Access | Standard | Standard | Standard | Standard |
Accessible Heating | Standard | Standard | Standard | Standard |
Slide-out Fan Motor | Standard | Standard | Standard | Standard (7.5-125 Ton) |
Tool-less Filter Access | Standard | Standard | Standard | Standard |
Fully Insulated Base | Standard | Standard | Standard | Standard |
Compressor Isolation Compartment | Standard | Standard | Standard | Standard |
Indoor Air Quality Features
Feature | Modèle LTM | Lumière | Xion™ | Raider® |
---|---|---|---|---|
Filters (up to MERV 16) | (Field/Factory) | (Field/Factory) | (Factory) | (Factory) |
Smoke Detector(s) | Option (field/factory) | Option (field/factory) | Option (factory) | Option (factory) |
NPBI - Ionizers | Option (factory) | Option (factory) | Option (factory) | Option (factory) |
UVC Lamps | Option (factory) | Option (factory) | Option (factory) | Option (factory) |
Fresh Air Conditioning | Option (field/factory) | Option (field/factory) | Option (factory) | Option (factory) |