LHT Enlight Rooftop Units
High Efficiency | Lennox® CORE Controller | R-454B | 60Hz
COMMERCIAL PRODUCT SPECIFICATIONS (EHB)
Capacity Range: 13 to 20 Tons
Net Cooling Capacity: 156,000 to 228,000 Btuh
Net Heating Capacity: 150,000 to 226,000 Btuh
Optional Electric Heat: 15 to 90 kW
Featuring the Lennox® CORE Control System, MSAV™ Multi-Stage Air Volume, and SMART WIRE™ System. Compliant with ASHRAE Standard 90.1 and ENERGY STAR® certified.
Model Number Identification
The model number follows a structured format:
- Brand: L = Lennox®
- Unit Type: H = Heat Pump Unit
- Family: T = Enlight Series
- Nominal Cooling Capacity - Tons: 156 = 13 Tons, 180 = 15 Tons, 240 = 20 Tons
- Cooling Efficiency: H = High Efficiency
- Refrigerant Type: 5 = R-454B
- Voltage: Y = 208/230V-3 phase-60Hz, G = 460V-3 phase-60Hz, J = 575V-3 phase-60Hz
- Minor Design Sequence: 1 = 1st Revision
- Factory Installed Electric Heat: N = No Heat, E = 15 kW, J = 30 kW, K = 45 kW, L = 60 kW, P = 90 kW
- Blower Type: M = MSAV® Multi-Stage Air Volume, Belt Drive
Feature Highlights
Enlight rooftop units with the Lennox® CORE Control System offer high energy efficiency and an environmentally sustainable design, meeting a wide range of applications.
- 1. Scroll Compressors
- 2. Check/Thermal Expansion Valves
- 3. Filter/Driers
- 4. Reversing Valves
- 5. Copper Tube Outdoor Coil
- 6. Outdoor Coil Fan Motors
- 7. Heavy Gauge Steel Cabinet
- 8. Hinged Access Panels
- 9. MSAV® Multi-Stage Air Volume Blower
- 10. Disconnect Switch (option)
- 11. Electric Heat (option)
- 12. Air Filters
- 13. Lennox® CORE® Control System
- 14. Economizer (option)
- 15. Barometric Relief Dampers (option)
- 16. Power Exhaust (option)
Approvals and Warranty
Approvals
- AHRI Standard 340/360-2023 certified
- ETL and CSA listed
- Unit and components ETL, NEC and CEC bonded for grounding
- ASHRAE 90.1 energy efficiency compliant
- DOE 2023 energy efficiency standards
- UL 60335-2-40 Refrigerant Detector Requirements
- HCAI (OSHPD) OSP and Special Seismic Certification
- California Code of Regulations, Title 24 compliant
- ENERGY STAR® certified
- ISO 9001 Registered Manufacturing Quality System
Warranty
- Compressors: Limited five years
- Lennox® CORE® Unit Controller: Limited three years
- Variable Frequency Drive (VFD): Limited five years
- High Performance Economizers (optional): Limited five years
- All other covered components: Limited one year
Features and Benefits
Cooling/Heating System
- Designed for maximum sensible and latent cooling performance.
- Mechanical cooling operates from 0°F to 125°F.
- Mechanical heating operates above -15°F.
- Heating Operation Note: Below -4°F, the unit may switch to optional electric heat if mechanical heating is locked out.
- R-454B Refrigerant: Low GWP, Zero ODP, Low Toxicity/Lower Flammability (A2L). Factory pre-charged.
- Compressor System: Features two-stage and single-stage scroll compressors, resiliently mounted for quiet operation. Includes compressor crankcase heaters.
- Check/Thermal Expansion Valves: Ensure optimal performance across the application range.
- Filter/Driers: Protect the system from dirt and moisture.
- Reversing Valve: Enables rapid changeover between cooling and heating.
- High Pressure Switches: Protect compressors from overload conditions.
- Low Pressure Switches: Protect compressors from low pressure conditions.
- Indoor Coil Freeze Protection: Prevents ice build-up on the indoor coil.
- Coil Construction: Copper tube, enhanced aluminum fins, flared shoulder tubing, silver soldered, factory leak tested.
Cabinet
- Construction: Heavy-gauge steel panels, full perimeter galvanized steel base rail with rigging holes and fork slots. Raised edges protect duct and power entry openings.
- Airflow Choice: Shipped in downflow (vertical) configuration; field convertible to horizontal airflow.
- Power Entry: Electrical lines routed through unit base or horizontal knock-outs.
- Exterior Panels: Heavy-gauge galvanized steel with textured pre-paint polyurethane finish, tested for salt fog and UV exposure.
- Insulation: Fully insulated with non-hygroscopic fiberglass in conditioned areas. Unit base is insulated for air sealing.
- Hinged Access Panels: For filter, heating/blower, and compressor/controls sections, with seals and quarter-turn latches for tight air/water seal.
Blower
- Motor: Overload protected, ball bearings. Motors 5 hp and above meet EISA 2007 standards.
- Supply Air Blower: Features forward curved blades, double inlet, statically and dynamically balanced. MSAV® system stages airflow using a Variable Frequency Drive (VFD) for controlled blower speed.
- VFD Operation: Alters frequency and voltage to control blower speed; adjustable for various airflow stages. Operational range: -40 to 125°F ambient.
Indoor Air Quality
- Air Filters: Standard disposable 2-inch MERV 4 filters. Optional Healthy Climate® High Efficiency filters (MERV 8, 13, 16) available.
- Healthy Climate® UVC Germicidal Light Kit: Uses UV-C energy to reduce microbes on illuminated surfaces; field installed in blower/evaporator coil section.
- Needlepoint Bipolar Ionization (NPBI) Kit: Integrates with system controls to reduce pathogens, pollutants, and odors using bipolar ions.
- Indoor Air Quality (CO2) Sensors: Monitor CO2 levels to adjust economizer dampers.
- Replacement Filter Media Kit: Includes washable metal mesh screen and frame.
Control System
- Lennox® CORE Control System: Microprocessor-based controller for flexible unit function control, designed for easy installation and service.
- CORE Mobile Service App: Provides guided setup, enhanced test functionality, and parameter configuration.
- Additional Features: 7-segment display for unit status/alarms, test buttons, SmartWire™ system, BACnet® and LonTalk® interoperability, Ethernet switch for daisy-chaining, USB port for service data.
- Configurable Functions: Discharge air cooling/heating control, economizer options, exhaust fan control, morning warm-up, night setback, fresh air tempering, demand control ventilation, low ambient controls, defrost methods.
- Component Protection/Safeguards: Includes compressor time-off delay, blower on/off delay, temperature limit controls, safety switch inputs, thermostat bounce delay, smoke alarm mode, "Strike Three" protection, minimum compressor run time.
- Control Methods/Interfaces: DDC and 24V thermostats, BACnet MS/TP and IP, LonTalk, Lennox S-BUS, zone sensors, humidity sensors, indoor air quality inputs.
Options / Accessories
A wide range of factory or field-installed options and accessories are available to customize unit performance and application suitability.
Cooling System
- Condensate Drain Trap (PVC or Copper)
- Drain Pan Overflow Switch
Blower - Supply Air
- MSAV® Multi-Stage Air Volume options (with or without VFD Bypass Control)
- Motors (3, 5, 7.5, 10 HP)
- Drive Kits (various RPM ranges)
- Blower Belt Auto-Tensioner
Cabinet
- Burglar Bars (US and CA)
- Combination Coil/Hail Guards
- Corrosion Protection
Controls
- Commercial Controls (LonTalk® Module, Novar® LSE)
- Dirty Filter Switch
- Fresh Air Tempering
- Smoke Detector (Supply or Return, Supply and Return)
Indoor Air Quality
- Healthy Climate® High Efficiency Air Filters (MERV 8, 13, 16)
- Replacement Filter Media Kit
- Indoor Air Quality (CO2) Sensors (various types)
- Needlepoint Bipolar Ionization (NPBI) Kit
- Healthy Climate® UVC Light Kit
- Step-Down Transformers (for 460V/575V units)
Electrical
- Voltage Options (208/230V, 460V, 575V - 3 Phase)
- Disconnect Switch (80, 150, 250 Amp)
- HACR Circuit Breakers
- Short-Circuit Current Rating (SCCR) up to 100kA
- GFI Service Outlets (15 Amp, 20 Amp)
- Weatherproof Cover for GFI
Electric Heat
- Available in 15 kW, 30 kW, 45 kW, 60 kW, and 90 kW configurations.
Economizer
- High Performance Economizer (California Title 24 / AMCA Class 1A Certified)
- Economizer Controls (Differential Enthalpy, Sensible Control, Single Enthalpy, Global Control, Building Pressure Control, Outdoor Air CFM Control)
- Barometric Relief Dampers (Downflow and Horizontal)
Outdoor Air
- Motorized Outdoor Air Dampers (0-25% adjustable)
- Manual Outdoor Air Damper
Roof Curbs
- Hybrid Roof Curbs (Downflow, various heights)
- Adjustable Pitch Curb (Downflow)
- Standard Roof Curbs (Horizontal, requires Horizontal Return Air Panel Kit)
- Insulation Kit for Standard Horizontal Roof Curbs
- Horizontal Return Air Panel Kit
Ceiling Diffusers
- Step-Down Ceiling Diffusers
- Flush Ceiling Diffusers
- Transitions (Supply and Return)
Power Exhaust
- Standard Static, SCCR Rated (for downflow applications, requires Economizer with Outdoor Air Hood and Downflow Barometric Relief Dampers).
Specifications
Model | LHT156H5M | LHT180H5M | LHT240H5M |
---|---|---|---|
Nominal Tonnage | 13 Ton | 15 Ton | 20 Ton |
Efficiency Type | High | High | High |
Blower Type | MSAV® Multi-Stage Air Volume | MSAV® Multi-Stage Air Volume | MSAV® Multi-Stage Air Volume |
Cooling Performance | |||
Gross Cooling Capacity (Btuh) | 160,000 | 182,000 | 237,000 |
Net Cooling Capacity (Btuh) | 156,000 | 176,000 | 228,000 |
AHRI Rated Air Flow (cfm) | 4500 | 5500 | 7000 |
IEER (Btuh/Watt) | 15.4 | 15.5 | 15.5 |
EER (Btuh/Watt) | 12.1 | 11.1 | 11.1 |
Total Unit Power (kW) | 12.9 | 15.8 | 20.5 |
Heating Performance | |||
Total High Heat Capacity (Btuh) | 150,000 | 176,000 | 226,000 |
COP | 3.4 | 3.4 | 3.4 |
Total Unit Power (kW) | 12.9 | 15.2 | 19.5 |
Total Low Heat Capacity (Btuh) | 86,000 | 104,000 | 128,000 |
COP | 2.1 | 2.1 | 2.1 |
Total Unit Power (kW) | 12.0 | 14.5 | 17.8 |
Electric Heat Available | See page 19 | See page 19 | See page 19 |
Sound Rating Number (dBA) | 94 | 94 | 94 |
Refrigerant Type | R-454B | R-454B | R-454B |
Compressor Type (number) | Two-Stage Scroll (1), Single-Stage Scroll (1) | Two-Stage Scroll (1), Single-Stage Scroll (1) | Two-Stage Scroll (1), Single-Stage Scroll (1) |
Outdoor Coil Net face area (ft²) | 55.1 | 55.1 | 55.1 |
Outdoor Coil Number of rows | 2 | 2 | 2 |
Outdoor Coil Fins (in.) | 20 | 20 | 20 |
Indoor Coil Net face area (ft²) | 21.4 | 21.4 | 21.4 |
Blower Motor HP (number and type) | 1/3 (6 PSC) | 1/3 (6 PSC) | 1/3 (6 PSC) |
Blower Motor RPM | 1075 | 1075 | 1075 |
Filters Type | MERV 4, Disposable | MERV 4, Disposable | MERV 4, Disposable |
Line voltage data (Volts-Phase-Hz) | 208/230-3-60, 460-3-60, 575-3-60 |
Unit Clearances
Clearances are specified for service and operation. For units with an economizer, specific clearances are provided.
Unit Clearance | A | B | C | D | Top Clearance | ||||
---|---|---|---|---|---|---|---|---|---|
in. | mm | in. | mm | in. | mm | in. | mm | ||
Service Clearance | 60 | 1524 | 36 | 914 | 36 | 934 | 66 | 1676 | Unobstructed |
Minimum Operation Clearance | 45 | 1143 | 36 | 914 | 36 | 914 | 41 | 1041 |
Outdoor Sound Data
Sound power levels are provided across various octave bands, with a Sound Rating Number (dBA) summarizing overall A-weighted sound power.
Size | 125 Hz | 250 Hz | 500 Hz | 1000 Hz | 2000 Hz | 4000 Hz | 8000 Hz | Sound Rating Number (dBA) |
---|---|---|---|---|---|---|---|---|
156, 180, 240 | 79 | 84 | 88 | 89 | 85 | 82 | 73 | 94 |
Weight Data
Unit weights (net and shipping) are provided for base and maximum configurations. Weights for factory/field installed options and accessories are also listed.
Unit Weights
Size | Net | Shipping | ||
---|---|---|---|---|
lbs. | kg | lbs. | kg | |
156 Base Unit | 2198 | 997 | 2398 | 1088 |
156 Max. Unit | 2488 | 1129 | 2688 | 1219 |
180 Base Unit | 2226 | 1010 | 2426 | 1100 |
180 Max. Unit | 2516 | 1141 | 2716 | 1232 |
240 Base Unit | 2268 | 1029 | 2468 | 1119 |
240 Max. Unit | 2558 | 1160 | 2758 | 1251 |
Factory / Field Installed Options and Accessories - Net Weights
Description | lbs. | kg |
---|---|---|
ECONOMIZER / OUTDOOR AIR / EXHAUST | ||
Economizer Dampers (with Outdoor Air Hood) | 167 | 76 |
Barometric Relief Dampers (downflow) | 30 | 14 |
Barometric Relief Dampers (horizontal) | 20 | 9 |
Outdoor Air Dampers with Hood (downflow) - Motorized | 39 | 18 |
Outdoor Air Dampers with Hood (downflow) - Manual | 22 | 10 |
Power Exhaust | 62 | 28 |
ELECTRIC HEAT | ||
15 kW | 59 | 27 |
30 kW | 59 | 27 |
45 kW | 76 | 34 |
60 kW | 76 | 34 |
90 kW | 84 | 38 |
COMBINATION COIL/HAIL GUARDS | ||
All models | 36 | 16 |
ROOF CURBS | ||
Hybrid Roof Curbs, Downflow (8 in. height) | 136 | 62 |
Hybrid Roof Curbs, Downflow (14 in. height) | 169 | 77 |
Hybrid Roof Curbs, Downflow (18 in. height) | 191 | 87 |
Hybrid Roof Curbs, Downflow (24 in. height) | 224 | 102 |
Adjustable Pitch Curb, Downflow (14 in. height) | 224 | 102 |
Standard Roof Curbs, Horizontal (26 in. height) | 450 | 204 |
Standard Roof Curbs, Horizontal (37 in. height) | 540 | 245 |
CEILING DIFFUSERS | ||
Step-Down (RTD11-185S) | 168 | 76 |
Step-Down (RTD11-275S) | 238 | 108 |
Flush (FD11-185S) | 168 | 76 |
Flush (FD11-275S) | 238 | 108 |
Transitions (C1DIFF33C-1) | 80 | 36 |
Transitions (C1DIFF34C-1) | 75 | 34 |
Dimensions
Detailed dimensional drawings and measurements are provided for unit configuration, installation, and accessory placement.
Corner Weights and Center of Gravity
Model | AA | BB | CC | DD | EE | FF | ||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
lbs. | kg | lbs. | kg | lbs. | kg | lbs. | kg | in. | mm | in. | mm | |
LHT156 Base Unit | 411 | 187 | 485 | 220 | 705 | 321 | 598 | 272 | 58-3/8 | 1481 | 37-1/8 | 943 |
LHT156 Max. Unit | 509 | 231 | 575 | 261 | 745 | 338 | 659 | 300 | 57-1/8 | 1452 | 39-3/4 | 1010 |
LHT180 Base Unit | 412 | 187 | 486 | 221 | 719 | 327 | 610 | 277 | 58-3/8 | 1482 | 36-3/4 | 934 |
LHT180 Max. Unit | 511 | 232 | 577 | 262 | 758 | 345 | 671 | 305 | 57-1/8 | 1452 | 39-3/8 | 1000 |
LHT240 Base Unit | 415 | 189 | 488 | 222 | 738 | 336 | 628 | 285 | 58-1/4 | 1479 | 36-1/4 | 921 |
LHT240 Max. Unit | 513 | 233 | 578 | 263 | 777 | 353 | 690 | 314 | 57 | 1448 | 38-7/8 | 987 |
Views and Details
End View: Shows dimensions for base, side electrical inlets, and condensate drain location.
Top View: Illustrates bottom supply air openings, bottom return air opening, and center of gravity points (EE, FF).
Side View: Depicts optional disconnect and 115 Volt outlet locations, lifting holes, and forklift slots.
Outdoor Air Hood Detail: Shows dimensions and mounting for the hood, furnished with Economizer or Outdoor Air Damper.
Optional Horizontal Barometric Relief Dampers with Hood: Details front and side views for field installation in horizontal return air duct.
Roof Curb Details: Includes diagrams for Hybrid Roof Curbs (double duct opening) with typical flashing details and dimensions, Adjustable Pitch Curb, and Standard Roof Curbs for horizontal applications.
Ceiling Diffuser Details: Provides diagrams for Combination Ceiling Supply and Return Diffusers (Step-Down and Flush types) with dimensional callouts.
Revisions
Options / Accessories: Added Burglar Bars.
For the latest technical information, visit www.Lennox.com or www.LennoxCommercial.com. Contact Lennox at 1-800-4-LENNOX.
Note: Lennox is committed to quality; specifications are subject to change without notice. Improper installation, adjustment, alteration, service, or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer.