Innovair SLIM4 Heat Pump Series Submittal Data Sheets
Model: SOV18H2BA / SWV18BDA (18K)
Series: SLIM4 Heat Pump Series
Indoor Specifications
ESP (inWG) | 0~0.8 |
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 618.0 / 576.8 / 529.7 / 488.5 / / |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | 48.0 / 47 / 45 / 39 / N/A |
Dimension (W×D×H) | 20.28 x 15.71 x 36.54 in (515 x 399 x 928 mm) |
Package (W×D×H) | 22.83 x 19.49 x 42.91 in (580 x 495 x 1090 mm) |
Net/Gross Weight | 111.33 / 91.49 lbs (50.5 / 41.5 kg) |
Outdoor Specifications
Compressor Type | ROTARY |
Compressor Model | KSN140D58UFZ |
Refrigerant | R454B |
Refrigerant Oil Charge (mL) | 440 |
Refrigerant Oil | VG74 |
Outdoor Air Flow (Max) (CFM) | 1450.9 |
Outdoor Noise Level (dBA) | 55.5 |
Dimension (W×D×H) | 31.69 x 12.99 x 21.81 in (805 x 330 x 554 mm) |
Package (W×D×H) | 36.02 x 14.57 x 24.21 in (915 x 370 x 615 mm) |
Net/Gross Weight | 77.16 / 83.77 lbs (35 / 38 kg) |
Efficiency
Cooling | Heating | |
---|---|---|
SEER2 | 18.5 | HSPF2-4: 9.4 |
EER2 | 11.5 | COP: 3.55 |
Performance of Cooling
Rated Capacity (Btu/hr) | 18000 |
Min/Max Capacity (Btu/hr) | 5900~20600 |
Moisture Removal (L/h) | 1.87 |
Standard Operating Range (°F/°C) | -25~50 (-25~50) |
Rated Cooling Conditions | Indoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB |
Performance of Heating
1. @ 47°F Rated (Btu/hr) | 18000 |
2. @ 47°F Min/Max Capacity (Btu/hr) | 3900~19600 |
3. @ 17°F Rated (Btu/hr) | 12600 |
4. @ 5°F Rated: Capacity / COP | 11400 / 2.1 |
5. @ 5°F Max: Capacity (Btu/hr) | 11400 |
Standard Operating Range (°F/°C) | -25~24 (-25~24) |
Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB |
2. Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB |
3. Heating Conditions, Compressor Operating at Max. Frequency | Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB |
Electrical
Indoor Power Supply | 115/208/230V, 60Hz, 1Ph |
Indoor MCA (115V/(208/230V)) | 4A |
Indoor MOP | 15A |
Outdoor Power Supply | 208/230V, 60Hz, 1Ph |
Outdoor MCA | 16A |
Outdoor MOP | 20A |
Communication Wiring | AWG 20-2 |
Compressor RLA | 10A |
Outdoor Fan Motor RLA | 0.8A |
Outdoor Fan Motor W | / |
Indoor Fan Motor RLA | 3A |
Indoor Fan Motor W | 250W |
System Power Input @ Cooling (W) | 1565 (360~1820) |
System Power Input @ Heating (W) | 1485 (275~1610) |
MCA: Min. circuit amps (A) | |
MOCP: Max. over current protection (A) | |
RLA: Rated load amps (A) | |
W: Fan motor rated output (W) |
Piping
Throttle type (Indoor) | EXV |
Throttle type (Outdoor) | EXV |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 19mm (3/4in) |
Max. Piping Length (ft/m) | 98.40 (30) |
Max. Height Difference (ft/m) | 65.60 (20) |
Max. Pre-charged Length (ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/kg) | 51.15 (1.45) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)) | 0.7 (65) |
Connection Method | Flared* |
Indoor Unit Dimensions
Dimensions for 18K/24K models:
Dimension Label | Dimension (inch) | Dimension (mm) |
---|---|---|
A - Model Height | 36.5 | 928 |
B - Model Width | 20.3 | 515 |
C - Supply Air Opening Width | 17.4 | 442 |
D - Return Air Opening Width | 19.4 | 493.8 |
E - Model Depth | 15.7 | 399 |
F - Supply Air Opening Depth | 10.4 | 265.2 |
G - Return Air Opening Depth | 10.3 | 261 |
H - Supply Air Opening Clearance | 1.1 | 29.1 |
I - Return Air Opening Side Clearance | 0.42 | 10.6 |
J - Return Air Opening Front Clearance | 0.47 | 12 |
Outdoor Unit Dimensions
Key dimensions for the outdoor unit (refer to diagrams for specific views and labels):
- Width (W): 31.69 in (805 mm)
- Depth (D): 12.99 in (330 mm)
- Height (H): 21.81 in (554 mm)
- Package Width: 36.02 in (915 mm)
- Package Depth: 14.57 in (370 mm)
- Package Height: 24.21 in (615 mm)
Installation Instructions for Outdoor Unit
Clearance Requirements:
- 20 inches (500mm) or more on sides, front, and rear when any 2 sides are clear.
- 20 inches (500mm) or more when front and sides are clear.
- 4 inches (100mm) or more on all sides.
- 14 inches (350mm) or more on the front.
The unit meets all spatial requirements shown in Installation Clearance Requirements.
Fan Performance for Indoor Unit (18K)
This section presents a chart illustrating the relationship between external static pressure (in.w.c.) and air flow rate (CFM) for the 18K indoor unit. The chart displays distinct lines for different fan speeds: Turbo, M (Medium), H (High), and L (Low).
Model: SOV24H2BA / SWV24BDA (24K)
Series: SLIM4 Heat Pump Series
Indoor Specifications
ESP (inWG) | 0~0.8 |
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 824.0 / 759.3 / 694.5 / 629.8 / / |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | 53.0 / 51 / 48 / 37.5 / N/A |
Dimension (W×D×H) | 20.28 x 15.71 x 36.54 in (515 x 399 x 928 mm) |
Package (W×D×H) | 22.83 x 19.49 x 42.91 in (580 x 495 x 1090 mm) |
Net/Gross Weight | 91.49 / 111.33 lbs (41.5 / 50.5 kg) |
Outdoor Specifications
Compressor Type | ROTARY |
Compressor Model | KTM240D46UKT2 |
Refrigerant | R454B |
Refrigerant Oil Charge (mL) | 620 |
Refrigerant Oil | VG74 |
Outdoor Air Flow (Max) (CFM) | 1765.8 |
Outdoor Noise Level (dBA) | 59 |
Dimension (W×D×H) | 35.04 x 13.46 x 26.50 in (890 x 342 x 673 mm) |
Package (W×D×H) | 39.17 x 15.67 x 29.13 in (995 x 398 x 740 mm) |
Net/Gross Weight | 101.41 / 109.13 lbs (46 / 49.5 kg) |
Efficiency
Cooling | Heating | |
---|---|---|
SEER2 | 17.4 | HSPF2-4: 10.4 |
EER2 | 10.8 | COP: 3.80 |
Performance of Cooling
Rated Capacity (Btu/hr) | 24000 |
Min/Max Capacity (Btu/hr) | 10100~27500 |
Moisture Removal (L/h) | 2.5 |
Standard Operating Range (°F/°C) | -25~50 (-25~50) |
Rated Cooling Conditions | Indoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB |
Performance of Heating
1. @ 47°F Rated (Btu/hr) | 25000 |
2. @ 47°F Min/Max Capacity (Btu/hr) | 7000~32200 |
3. @ 17°F Rated (Btu/hr) | 20800 |
4. @ 5°F Rated: Capacity / COP | 19400 / 1.96 |
5. @ 5°F Max: Capacity (Btu/hr) | 19400 |
Standard Operating Range (°F/°C) | -25~24 (-25~24) |
Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB |
2. Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB |
3. Heating Conditions, Compressor Operating at Max. Frequency | Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB |
Electrical
Indoor Power Supply | 115/208/230V, 60Hz, 1Ph |
Indoor MCA (115V/(208/230V)) | 4A |
Indoor MOP | 15A |
Outdoor Power Supply | 208/230V, 60Hz, 1Ph |
Outdoor MCA | 19A |
Outdoor MOP | 20A |
Communication Wiring | AWG 20-2 |
Compressor RLA | 14A |
Outdoor Fan Motor RLA | 1A |
Outdoor Fan Motor W | / |
Indoor Fan Motor RLA | 3A |
Indoor Fan Motor W | 250W |
System Power Input @ Cooling (W) | 2222 (830 ~ 2850) |
System Power Input @ Heating (W) | 1980 (455 ~ 2590) |
MCA: Min. circuit amps (A) | |
MOCP: Max. over current protection (A) | |
RLA: Rated load amps (A) | |
W: Fan motor rated output (W) |
Piping
Throttle type (Indoor) | EXV |
Throttle type (Outdoor) | EXV |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 19mm (3/4in) |
Max. Piping Length (ft/m) | 164 (50) |
Max. Height Difference (ft/m) | 82 (25) |
Max. Pre-charged Length (ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/kg) | 74.08 (2.1) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)) | 0.7 (65) |
Connection Method | Flared |
Indoor Unit Dimensions
Dimensions for 18K/24K models:
Dimension Label | Dimension (inch) | Dimension (mm) |
---|---|---|
A - Model Height | 36.5 | 928 |
B - Model Width | 20.3 | 515 |
C - Supply Air Opening Width | 17.4 | 442 |
D - Return Air Opening Width | 19.4 | 493.8 |
E - Model Depth | 15.7 | 399 |
F - Supply Air Opening Depth | 10.4 | 265.2 |
G - Return Air Opening Depth | 10.3 | 261 |
H - Supply Air Opening Clearance | 1.1 | 29.1 |
I - Return Air Opening Side Clearance | 0.42 | 10.6 |
J - Return Air Opening Front Clearance | 0.47 | 12 |
Outdoor Unit Dimensions
Key dimensions for the outdoor unit (refer to diagrams for specific views and labels):
- Width (W): 35.04 in (890 mm)
- Depth (D): 13.46 in (342 mm)
- Height (H): 26.50 in (673 mm)
- Package Width: 39.17 in (995 mm)
- Package Depth: 15.67 in (398 mm)
- Package Height: 29.13 in (740 mm)
Installation Instructions for Outdoor Unit
Clearance Requirements:
- 20 inches (500mm) or more on sides, front, and rear when any 2 sides are clear.
- 20 inches (500mm) or more when front and sides are clear.
- 4 inches (100mm) or more on all sides.
- 14 inches (350mm) or more on the front.
The unit meets all spatial requirements shown in Installation Clearance Requirements.
Fan Performance for Indoor Unit (24K)
This section presents a chart illustrating the relationship between external static pressure (in.w.c.) and air flow rate (CFM) for the 24K indoor unit. The chart displays distinct lines for different fan speeds: Turbo, H (High), M (Medium), and L (Low).
Model: SOV30H2BA / SWV30BDA (30K)
Series: SLIM4 Heat Pump Series
Indoor Specifications
ESP (inWG) | 0~0.8 |
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 988.8 / 894.7 / 806.4 / 712.2 / N/A |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | 50.5 / 50 / 48 / 36 / N/A |
Dimension (W×D×H) | 22.01 x 19.02 x 40.04 in (559 x 483 x 1017 mm) |
Package (W×D×H) | 24.61 x 22.83 x 46.97 in (625 x 580 x 1193 mm) |
Net/Gross Weight | 110.23 / 131.39 lbs (50 / 59.6 kg) |
Outdoor Specifications
Compressor Type | ROTARY |
Compressor Model | KTF250D22UMT |
Refrigerant | R454B |
Refrigerant Oil Charge (mL) | 670 |
Refrigerant Oil | VG74 |
Outdoor Air Flow (Max) (CFM) | 3001.9 |
Outdoor Noise Level (dBA) | 61 |
Dimension (W×D×H) | 37.24 x 16.14 x 31.89 in (946 x 410 x 810 mm) |
Package (W×D×H) | 42.91 x 19.69 x 34.84 in (1090 x 500 x 885 mm) |
Net/Gross Weight | 141.76 / 152.34 lbs (64.3 / 69.1 kg) |
Efficiency
Cooling | Heating | |
---|---|---|
SEER2 | 18.6 | HSPF2-4: 8.7 |
EER2 | 11 | COP: 3.5 |
Performance of Cooling
Rated Capacity (Btu/hr) | 30000 |
Min/Max Capacity (Btu/hr) | 10100~34400 |
Moisture Removal (L/h) | 2.99 |
Standard Operating Range (°F/°C) | -25~50 (-25~50) |
Rated Cooling Conditions | Indoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB |
Performance of Heating
1. @ 47°F Rated (Btu/hr) | 31000 |
2. @ 47°F Min/Max Capacity (Btu/hr) | 6500~31900 |
3. @ 17°F Rated (Btu/hr) | 18200 |
4. @ 5°F Rated: Capacity / COP | 18700 / 1.99 |
5. @ 5°F Max: Capacity (Btu/hr) | 18700 |
Standard Operating Range (°F/°C) | -25~24 (-25~24) |
Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB |
2. Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB |
3. Heating Conditions, Compressor Operating at Max. Frequency | Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB |
Electrical
Indoor Power Supply | 115/208/230V, 60Hz, 1Ph |
Indoor MCA (115V/(208/230V)) | 6A |
Indoor MOP | 15A |
Outdoor Power Supply | 208/230V, 60Hz, 1Ph |
Outdoor MCA | 22.5A |
Outdoor MOP | 25A |
Communication Wiring | AWG 20-2 |
Compressor RLA | 17A |
Outdoor Fan Motor RLA | 1.1A |
Outdoor Fan Motor W | / |
Indoor Fan Motor RLA | 4.5A |
Indoor Fan Motor W | 375W |
System Power Input @ Cooling (W) | 2727 (670 ~ 3130) |
System Power Input @ Heating (W) | 2596 (400 ~ 2550) |
MCA: Min. circuit amps (A) | |
MOCP: Max. over current protection (A) | |
RLA: Rated load amps (A) | |
W: Fan motor rated output (W) |
Piping
Throttle type (Indoor) | EXV |
Throttle type (Outdoor) | EXV |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 19mm (3/4in) |
Max. Piping Length (ft/m) | 164 (50) |
Max. Height Difference (ft/m) | 82 (25) |
Max. Pre-charged Length (ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/kg) | 91.71 (2.6) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)) | 0.7 (65) |
Connection Method | Flared |
Indoor Unit Dimensions
Dimensions for 30K/36K models:
Dimension Label | Dimension (inch) | Dimension (mm) |
---|---|---|
A - Model Height | 49 | 1017 |
B - Model Width | 21 | 559 |
C - Supply Air Opening Width | 18.8 | 478.6 |
D - Return Air Opening Width | 21.2 | 537.8 |
E - Model Depth | 21 | 483 |
F - Supply Air Opening Depth | 9.3 | 235.4 |
G - Return Air Opening Depth | 13.1 | 332.5 |
H - Supply Air Opening Clearance | 1.6 | 41 |
I - Return Air Opening Side Clearance | 0.42 | 10.6 |
J - Return Air Opening Front Clearance | 0.63 | 16 |
Outdoor Unit Dimensions
Key dimensions for the outdoor unit (refer to diagrams for specific views and labels):
- Width (W): 37.24 in (946 mm)
- Depth (D): 16.14 in (410 mm)
- Height (H): 31.89 in (810 mm)
- Package Width: 42.91 in (1090 mm)
- Package Depth: 19.69 in (500 mm)
- Package Height: 34.84 in (885 mm)
Installation Instructions for Outdoor Unit
Clearance Requirements:
- 20 inches (500mm) or more on sides, front, and rear when any 2 sides are clear.
- 20 inches (500mm) or more when front and sides are clear.
- 4 inches (100mm) or more on all sides.
- 14 inches (350mm) or more on the front.
The unit meets all spatial requirements shown in Installation Clearance Requirements.
Fan Performance for Indoor Unit (30K)
This section presents a chart illustrating the relationship between external static pressure (in.w.c.) and air flow rate (CFM) for the 30K indoor unit. The chart displays distinct lines for different fan speeds: Turbo, H (High), M (Medium), and L (Low).
Model: SOV36H2BA / SWV36BDA (36K)
Series: SLIM4 Heat Pump Series
Indoor Specifications
ESP (inWG) | 0~0.8 |
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 1189.0 / 1083.0 / 971.2 / 865.2 / / |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | 50.5 / 48 / 36.5 / N/A |
Dimension (W×D×H) | 22.01 x 19.02 x 40.04 in (559 x 483 x 1017 mm) |
Package (W×D×H) | 24.61 x 22.83 x 46.97 in (625 x 580 x 1193 mm) |
Net/Gross Weight | 109.57 / 130.73 lbs (49.7 / 59.3 kg) |
Outdoor Specifications
Compressor Type | ROTARY |
Compressor Model | KTF310D43UMT |
Refrigerant | R454B |
Refrigerant Oil Charge (mL) | 1000 |
Refrigerant Oil | VG74 |
Outdoor Air Flow (Max) (CFM) | 2413.3 |
Outdoor Noise Level (dBA) | 62 |
Dimension (W×D×H) | 37.24 x 16.14 x 31.89 in (946 x 410 x 810 mm) |
Package (W×D×H) | 42.91 x 19.69 x 34.84 in (1090 x 500 x 885 mm) |
Net/Gross Weight | 153.22 / 163.58 lbs (69.5 / 74.2 kg) |
Efficiency
Cooling | Heating | |
---|---|---|
SEER2 | 16.7 | HSPF2-4: 9.3 |
EER2 | 10.2 | COP: 3.3 |
Performance of Cooling
Rated Capacity (Btu/hr) | 36000 |
Min/Max Capacity (Btu/hr) | 11800~39000 |
Moisture Removal (L/h) | 3.37 |
Standard Operating Range (°F/°C) | -25~50 (-25~50) |
Rated Cooling Conditions | Indoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB |
Performance of Heating
1. @ 47°F Rated (Btu/hr) | 37000 |
2. @ 47°F Min/Max Capacity (Btu/hr) | 6900~41000 |
3. @ 17°F Rated (Btu/hr) | 24800 |
4. @ 5°F Rated: Capacity / COP | 29200 / 1.99 |
5. @ 5°F Max: Capacity (Btu/hr) | 29200 |
Standard Operating Range (°F/°C) | -25~24 (-25~24) |
Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB |
2. Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB |
3. Heating Conditions, Compressor Operating at Max. Frequency | Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB |
Electrical
Indoor Power Supply | 115/208/230V, 60Hz, 1Ph |
Indoor MCA (115V/(208/230V)) | 6.5A |
Indoor MOP | 15A |
Outdoor Power Supply | 208/230V, 60Hz, 1Ph |
Outdoor MCA | 24A |
Outdoor MOP | 30A |
Communication Wiring | AWG 20-2 |
Compressor RLA | 17.5A |
Outdoor Fan Motor RLA | 1.5A |
Outdoor Fan Motor W | / |
Indoor Fan Motor RLA | 5A |
Indoor Fan Motor W | 375W |
System Power Input @ Cooling (W) | 3529 (760 ~ 4090) |
System Power Input @ Heating (W) | 3189 (490 ~ 3710) |
MCA: Min. circuit amps (A) | |
MOCP: Max. over current protection (A) | |
RLA: Rated load amps (A) | |
W: Fan motor rated output (W) |
Piping
Throttle type (Indoor) | EXV |
Throttle type (Outdoor) | EXV |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 19mm (3/4in) |
Max. Piping Length (ft/m) | 246 (75) |
Max. Height Difference (ft/m) | 98.40 (30) |
Max. Pre-charged Length (ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/kg) | 116.40 (3.3) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)) | 0.7 (65) |
Connection Method | Flared |
Indoor Unit Dimensions
Dimensions for 30K/36K models:
Dimension Label | Dimension (inch) | Dimension (mm) |
---|---|---|
A - Model Height | 49 | 1017 |
B - Model Width | 21 | 559 |
C - Supply Air Opening Width | 18.8 | 478.6 |
D - Return Air Opening Width | 21.2 | 537.8 |
E - Model Depth | 21 | 483 |
F - Supply Air Opening Depth | 9.3 | 235.4 |
G - Return Air Opening Depth | 13.1 | 332.5 |
H - Supply Air Opening Clearance | 1.6 | 41 |
I - Return Air Opening Side Clearance | 0.42 | 10.6 |
J - Return Air Opening Front Clearance | 0.63 | 16 |
Outdoor Unit Dimensions
Key dimensions for the outdoor unit (refer to diagrams for specific views and labels):
- Width (W): 37.24 in (946 mm)
- Depth (D): 16.14 in (410 mm)
- Height (H): 31.89 in (810 mm)
- Package Width: 42.91 in (1090 mm)
- Package Depth: 19.69 in (500 mm)
- Package Height: 34.84 in (885 mm)
Installation Instructions for Outdoor Unit
Clearance Requirements:
- 20 inches (500mm) or more on sides, front, and rear when any 2 sides are clear.
- 20 inches (500mm) or more when front and sides are clear.
- 4 inches (100mm) or more on all sides.
- 14 inches (350mm) or more on the front.
The unit meets all spatial requirements shown in Installation Clearance Requirements.
Fan Performance for Indoor Unit (30K)
This section presents a chart illustrating the relationship between external static pressure (in.w.c.) and air flow rate (CFM) for the 30K indoor unit. The chart displays distinct lines for different fan speeds: Turbo, H (High), M (Medium), and L (Low).
Model: SOV36H2BA / SWV36BDA (36K)
Series: SLIM4 Heat Pump Series
Indoor Specifications
ESP (inWG) | 0~0.8 |
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 1189.0 / 1083.0 / 971.2 / 865.2 / / |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | 50.5 / 48 / 36.5 / N/A |
Dimension (W×D×H) | 22.01 x 19.02 x 40.04 in (559 x 483 x 1017 mm) |
Package (W×D×H) | 24.61 x 22.83 x 46.97 in (625 x 580 x 1193 mm) |
Net/Gross Weight | 109.57 / 130.73 lbs (49.7 / 59.3 kg) |
Outdoor Specifications
Compressor Type | ROTARY |
Compressor Model | KTF310D43UMT |
Refrigerant | R454B |
Refrigerant Oil Charge (mL) | 1000 |
Refrigerant Oil | VG74 |
Outdoor Air Flow (Max) (CFM) | 2413.3 |
Outdoor Noise Level (dBA) | 62 |
Dimension (W×D×H) | 37.24 x 16.14 x 31.89 in (946 x 410 x 810 mm) |
Package (W×D×H) | 42.91 x 19.69 x 34.84 in (1090 x 500 x 885 mm) |
Net/Gross Weight | 153.22 / 163.58 lbs (69.5 / 74.2 kg) |
Efficiency
Cooling | Heating | |
---|---|---|
SEER2 | 16.7 | HSPF2-4: 9.3 |
EER2 | 10.2 | COP: 3.3 |
Performance of Cooling
Rated Capacity (Btu/hr) | 36000 |
Min/Max Capacity (Btu/hr) | 11800~39000 |
Moisture Removal (L/h) | 3.37 |
Standard Operating Range (°F/°C) | -25~50 (-25~50) |
Rated Cooling Conditions | Indoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB |
Performance of Heating
1. @ 47°F Rated (Btu/hr) | 37000 |
2. @ 47°F Min/Max Capacity (Btu/hr) | 6900~41000 |
3. @ 17°F Rated (Btu/hr) | 24800 |
4. @ 5°F Rated: Capacity / COP | 29200 / 1.99 |
5. @ 5°F Max: Capacity (Btu/hr) | 29200 |
Standard Operating Range (°F/°C) | -25~24 (-25~24) |
Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB |
2. Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB |
3. Heating Conditions, Compressor Operating at Max. Frequency | Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB |
Electrical
Indoor Power Supply | 115/208/230V, 60Hz, 1Ph |
Indoor MCA (115V/(208/230V)) | 6.5A |
Indoor MOP | 15A |
Outdoor Power Supply | 208/230V, 60Hz, 1Ph |
Outdoor MCA | 24A |
Outdoor MOP | 30A |
Communication Wiring | AWG 20-2 |
Compressor RLA | 17.5A |
Outdoor Fan Motor RLA | 1.5A |
Outdoor Fan Motor W | / |
Indoor Fan Motor RLA | 5A |
Indoor Fan Motor W | 375W |
System Power Input @ Cooling (W) | 3529 (760 ~ 4090) |
System Power Input @ Heating (W) | 3189 (490 ~ 3710) |
MCA: Min. circuit amps (A) | |
MOCP: Max. over current protection (A) | |
RLA: Rated load amps (A) | |
W: Fan motor rated output (W) |
Piping
Throttle type (Indoor) | EXV |
Throttle type (Outdoor) | EXV |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 19mm (3/4in) |
Max. Piping Length (ft/m) | 246 (75) |
Max. Height Difference (ft/m) | 98.40 (30) |
Max. Pre-charged Length (ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/kg) | 116.40 (3.3) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)) | 0.7 (65) |
Connection Method | Flared |
Indoor Unit Dimensions
Dimensions for 30K/36K models:
Dimension Label | Dimension (inch) | Dimension (mm) |
---|---|---|
A - Model Height | 49 | 1017 |
B - Model Width | 21 | 559 |
C - Supply Air Opening Width | 18.8 | 478.6 |
D - Return Air Opening Width | 21.2 | 537.8 |
E - Model Depth | 21 | 483 |
F - Supply Air Opening Depth | 9.3 | 235.4 |
G - Return Air Opening Depth | 13.1 | 332.5 |
H - Supply Air Opening Clearance | 1.6 | 41 |
I - Return Air Opening Side Clearance | 0.42 | 10.6 |
J - Return Air Opening Front Clearance | 0.63 | 16 |
Outdoor Unit Dimensions
Key dimensions for the outdoor unit (refer to diagrams for specific views and labels):
- Width (W): 37.24 in (946 mm)
- Depth (D): 16.14 in (410 mm)
- Height (H): 31.89 in (810 mm)
- Package Width: 42.91 in (1090 mm)
- Package Depth: 19.69 in (500 mm)
- Package Height: 34.84 in (885 mm)
Installation Instructions for Outdoor Unit
Clearance Requirements:
- 20 inches (500mm) or more on sides, front, and rear when any 2 sides are clear.
- 20 inches (500mm) or more when front and sides are clear.
- 4 inches (100mm) or more on all sides.
- 14 inches (350mm) or more on the front.
The unit meets all spatial requirements shown in Installation Clearance Requirements.
Fan Performance for Indoor Unit (30K)
This section presents a chart illustrating the relationship between external static pressure (in.w.c.) and air flow rate (CFM) for the 30K indoor unit. The chart displays distinct lines for different fan speeds: Turbo, H (High), M (Medium), and L (Low).
Model: SOV36H2BA / SWV36BDA (36K)
Series: SLIM4 Heat Pump Series
Indoor Specifications
ESP (inWG) | 0~0.8 |
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 1189.0 / 1083.0 / 971.2 / 865.2 / / |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | 50.5 / 48 / 36.5 / N/A |
Dimension (W×D×H) | 22.01 x 19.02 x 40.04 in (559 x 483 x 1017 mm) |
Package (W×D×H) | 24.61 x 22.83 x 46.97 in (625 x 580 x 1193 mm) |
Net/Gross Weight | 109.57 / 130.73 lbs (49.7 / 59.3 kg) |
Outdoor Specifications
Compressor Type | ROTARY |
Compressor Model | KTF310D43UMT |
Refrigerant | R454B |
Refrigerant Oil Charge (mL) | 1000 |
Refrigerant Oil | VG74 |
Outdoor Air Flow (Max) (CFM) | 2413.3 |
Outdoor Noise Level (dBA) | 62 |
Dimension (W×D×H) | 37.24 x 16.14 x 31.89 in (946 x 410 x 810 mm) |
Package (W×D×H) | 42.91 x 19.69 x 34.84 in (1090 x 500 x 885 mm) |
Net/Gross Weight | 153.22 / 163.58 lbs (69.5 / 74.2 kg) |
Efficiency
Cooling | Heating | |
---|---|---|
SEER2 | 16.7 | HSPF2-4: 9.3 |
EER2 | 10.2 | COP: 3.3 |
Performance of Cooling
Rated Capacity (Btu/hr) | 36000 |
Min/Max Capacity (Btu/hr) | 11800~39000 |
Moisture Removal (L/h) | 3.37 |
Standard Operating Range (°F/°C) | -25~50 (-25~50) |
Rated Cooling Conditions | Indoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB |
Performance of Heating
1. @ 47°F Rated (Btu/hr) | 37000 |
2. @ 47°F Min/Max Capacity (Btu/hr) | 6900~41000 |
3. @ 17°F Rated (Btu/hr) | 24800 |
4. @ 5°F Rated: Capacity / COP | 29200 / 1.99 |
5. @ 5°F Max: Capacity (Btu/hr) | 29200 |
Standard Operating Range (°F/°C) | -25~24 (-25~24) |
Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB |
2. Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB |
3. Heating Conditions, Compressor Operating at Max. Frequency | Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB |
Electrical
Indoor Power Supply | 115/208/230V, 60Hz, 1Ph |
Indoor MCA (115V/(208/230V)) | 6.5A |
Indoor MOP | 15A |
Outdoor Power Supply | 208/230V, 60Hz, 1Ph |
Outdoor MCA | 24A |
Outdoor MOP | 30A |
Communication Wiring | AWG 20-2 |
Compressor RLA | 17.5A |
Outdoor Fan Motor RLA | 1.5A |
Outdoor Fan Motor W | / |
Indoor Fan Motor RLA | 5A |
Indoor Fan Motor W | 375W |
System Power Input @ Cooling (W) | 3529 (760 ~ 4090) |
System Power Input @ Heating (W) | 3189 (490 ~ 3710) |
MCA: Min. circuit amps (A) | |
MOCP: Max. over current protection (A) | |
RLA: Rated load amps (A) | |
W: Fan motor rated output (W) |
Piping
Throttle type (Indoor) | EXV |
Throttle type (Outdoor) | EXV |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 19mm (3/4in) |
Max. Piping Length (ft/m) | 246 (75) |
Max. Height Difference (ft/m) | 98.40 (30) |
Max. Pre-charged Length (ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/kg) | 116.40 (3.3) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)) | 0.7 (65) |
Connection Method | Flared |
Indoor Unit Dimensions
Dimensions for 30K/36K models:
Dimension Label | Dimension (inch) | Dimension (mm) |
---|---|---|
A - Model Height | 49 | 1017 |
B - Model Width | 21 | 559 |
C - Supply Air Opening Width | 18.8 | 478.6 |
D - Return Air Opening Width | 21.2 | 537.8 |
E - Model Depth | 21 | 483 |
F - Supply Air Opening Depth | 9.3 | 235.4 |
G - Return Air Opening Depth | 13.1 | 332.5 |
H - Supply Air Opening Clearance | 1.6 | 41 |
I - Return Air Opening Side Clearance | 0.42 | 10.6 |
J - Return Air Opening Front Clearance | 0.63 | 16 |
Outdoor Unit Dimensions
Key dimensions for the outdoor unit (refer to diagrams for specific views and labels):
- Width (W): 37.24 in (946 mm)
- Depth (D): 16.14 in (410 mm)
- Height (H): 31.89 in (810 mm)
- Package Width: 42.91 in (1090 mm)
- Package Depth: 19.69 in (500 mm)
- Package Height: 34.84 in (885 mm)
Installation Instructions for Outdoor Unit
Clearance Requirements:
- 20 inches (500mm) or more on sides, front, and rear when any 2 sides are clear.
- 20 inches (500mm) or more when front and sides are clear.
- 4 inches (100mm) or more on all sides.
- 14 inches (350mm) or more on the front.
The unit meets all spatial requirements shown in Installation Clearance Requirements.
Fan Performance for Indoor Unit (30K)
This section presents a chart illustrating the relationship between external static pressure (in.w.c.) and air flow rate (CFM) for the 30K indoor unit. The chart displays distinct lines for different fan speeds: Turbo, H (High), M (Medium), and L (Low).
Model: SOV36H2BA / SWV36BDA (36K)
Series: SLIM4 Heat Pump Series
Indoor Specifications
ESP (inWG) | 0~0.8 |
Indoor Air Flow (Turbo/H/M/L/Si) (CFM) | 1189.0 / 1083.0 / 971.2 / 865.2 / / |
Indoor Noise Level (Turbo/H/M/L/Si) (dBA) | 50.5 / 48 / 36.5 / N/A |
Dimension (W×D×H) | 22.01 x 19.02 x 40.04 in (559 x 483 x 1017 mm) |
Package (W×D×H) | 24.61 x 22.83 x 46.97 in (625 x 580 x 1193 mm) |
Net/Gross Weight | 109.57 / 130.73 lbs (49.7 / 59.3 kg) |
Outdoor Specifications
Compressor Type | ROTARY |
Compressor Model | KTF310D43UMT |
Refrigerant | R454B |
Refrigerant Oil Charge (mL) | 1000 |
Refrigerant Oil | VG74 |
Outdoor Air Flow (Max) (CFM) | 2413.3 |
Outdoor Noise Level (dBA) | 62 |
Dimension (W×D×H) | 37.24 x 16.14 x 31.89 in (946 x 410 x 810 mm) |
Package (W×D×H) | 42.91 x 19.69 x 34.84 in (1090 x 500 x 885 mm) |
Net/Gross Weight | 153.22 / 163.58 lbs (69.5 / 74.2 kg) |
Efficiency
Cooling | Heating | |
---|---|---|
SEER2 | 16.7 | HSPF2-4: 9.3 |
EER2 | 10.2 | COP: 3.3 |
Performance of Cooling
Rated Capacity (Btu/hr) | 36000 |
Min/Max Capacity (Btu/hr) | 11800~39000 |
Moisture Removal (L/h) | 3.37 |
Standard Operating Range (°F/°C) | -25~50 (-25~50) |
Rated Cooling Conditions | Indoor: 80°F DB/67°F WB, Outdoor: 95°F DB/75°F WB |
Performance of Heating
1. @ 47°F Rated (Btu/hr) | 37000 |
2. @ 47°F Min/Max Capacity (Btu/hr) | 6900~41000 |
3. @ 17°F Rated (Btu/hr) | 24800 |
4. @ 5°F Rated: Capacity / COP | 29200 / 1.99 |
5. @ 5°F Max: Capacity (Btu/hr) | 29200 |
Standard Operating Range (°F/°C) | -25~24 (-25~24) |
Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 47°F DB/43°F WB |
2. Rated Heating Conditions | Indoor: 70°F DB/60°F WB, Outdoor: 17°F DB/15°F WB |
3. Heating Conditions, Compressor Operating at Max. Frequency | Indoor: 70°F DB/60°F WB, Outdoor: 5°F DB/5°F WB |
Electrical
Indoor Power Supply | 115/208/230V, 60Hz, 1Ph |
Indoor MCA (115V/(208/230V)) | 6.5A |
Indoor MOP | 15A |
Outdoor Power Supply | 208/230V, 60Hz, 1Ph |
Outdoor MCA | 24A |
Outdoor MOP | 30A |
Communication Wiring | AWG 20-2 |
Compressor RLA | 17.5A |
Outdoor Fan Motor RLA | 1.5A |
Outdoor Fan Motor W | / |
Indoor Fan Motor RLA | 5A |
Indoor Fan Motor W | 375W |
System Power Input @ Cooling (W) | 3529 (760 ~ 4090) |
System Power Input @ Heating (W) | 3189 (490 ~ 3710) |
MCA: Min. circuit amps (A) | |
MOCP: Max. over current protection (A) | |
RLA: Rated load amps (A) | |
W: Fan motor rated output (W) |
Piping
Throttle type (Indoor) | EXV |
Throttle type (Outdoor) | EXV |
Liquid Size | 9.52mm (3/8in) |
Gas Size | 19mm (3/4in) |
Max. Piping Length (ft/m) | 246 (75) |
Max. Height Difference (ft/m) | 98.40 (30) |
Max. Pre-charged Length (ft/m) | 24.6 (7.5) |
Refrigerant Pre-charged Amount (oz/kg) | 116.40 (3.3) |
Additional Charge of Refrigerant ((oz/ft)/(g/m)) | 0.7 (65) |
Connection Method | Flared |
Indoor Unit Dimensions
Dimensions for 30K/36K models:
Dimension Label | Dimension (inch) | Dimension (mm) |
---|---|---|
A - Model Height | 49 | 1017 |
B - Model Width | 21 | 559 |
C - Supply Air Opening Width | 18.8 | 478.6 |
D - Return Air Opening Width | 21.2 | 537.8 |
E - Model Depth | 21 | 483 |
F - Supply Air Opening Depth | 9.3 | 235.4 |
G - Return Air Opening Depth | 13.1 | 332.5 |
H - Supply Air Opening Clearance | 1.6 | 41 |
I - Return Air Opening Side Clearance | 0.42 | 10.6 |
J - Return Air Opening Front Clearance | 0.63 | 16 |
Outdoor Unit Dimensions
Key dimensions for the outdoor unit (refer to diagrams for specific views and labels):
- Width (W): 37.24 in (946 mm)
- Depth (D): 16.14 in (410 mm)
- Height (H): 31.89 in (810 mm)
- Package Width: 42.91 in (1090 mm)
- Package Depth: 19.69 in (500 mm)
- Package Height: 34.84 in (885 mm)
Installation Instructions for Outdoor Unit
Clearance Requirements:
- 20 inches (500mm) or more on sides, front, and rear when any 2 sides are clear.
- 20 inches (500mm) or more when front and sides are clear.
- 4 inches (100mm) or more on all sides.
- 14 inches (350mm) or more on the front.
The unit meets all spatial requirements shown in Installation Clearance Requirements.
Fan Performance for Indoor Unit (36K)
This section presents a chart illustrating the relationship between external static pressure (in.w.c.) and air flow rate (CFM) for the 36K indoor unit. The chart displays distinct lines for different fan speeds: Turbo, H (High), M (Medium), and L (Low).