Innovair SLIM4 Heat Pump Series Submittal Data Sheet

Innovair SLIM4 Heat Pump Series Submittal Data Sheet

Series Name: SLIM4 Heat Pump Series

Model Numbers: SOV18H2BA/SAV18BDA, SOV24H2BA/SAV24BDA, SOV30H2BA/SAV30BDA, SOV36H2BA/SAV36BDA, SOV48H2BA/SAV48BDA, SOV60H2BA/SAV60BDA

Indoor Specifications

Parameter18k/24k Models30k/36k Models48k/60k Models
Indoor Air Flow (CFM)618.03/576.83/529.74/488.54 (H/M/L/Si)988.85/894.67/806.38/712.21 (H/M/L/Si)1600.99/1471.50/1283.15/1094.80 (H/M/L/Si)
Indoor Noise Level (dBA)44/43/41/33 (H/M/L/Si)46/42/29 (H/M/L)53/50/44 (H/M/L)
Dimensions (W×D×H)21.02 x 17.52 x 45.00 in
534.0×445.0×1143.0 mm
21.02 x 21.02 x 49.02 in
534.0×534.0×1245.0 mm
21.02 x 24.49 x 52.99 in
534.0×622.0×1346.0 mm
Package Dimensions (W×D×H)26.57 x 20.87 x 48.62 in
675×530×1235 mm
26.57 x 24.41 x 52.56 in
675×620×1335 mm
27.95 x 26.77 x 56.50 in
710×680×1435 mm
Net/Gross Weight105.82/126.76 lbs
48/57.5 kg
128.97/153.44 lbs
58.5/69.6 kg
162.92/190.92 lbs
73.9/86.6 kg

Outdoor Specifications

Parameter18k/24k Models30k/36k Models48k/60k Models
Compressor TypeROTARYROTARYROTARY
Compressor ModelKSN140D58UFZKTF250D22UMTMTH550UKPC8FU
RefrigerantR454BR454BR454B
Refrigerant Oil Charge (mL)4406701800
Refrigerant OilVG74VG74HAF68D1C
Outdoor Air Flow (Max) (CFM)1450.93001.83037.1
Outdoor Noise Level (dBA)556065
Dimensions (W×D×H)31.69 x 12.99 x 21.81 in
805.0×330.0×554.0 mm
37.24 x 16.14 x 31.89 in
946.0×410.0×810.0 mm
38.58 x 16.34 x 38.39 in
980.0×415.0×975.0 mm
Package Dimensions (W×D×H)36.02 x 14.57 x 24.21 in
915×370×615 mm
42.91 x 19.68 x 34.84 in
1090×500×885 mm
45.08 x 19.68 x 42.52 in
1145×500×1080 mm
Net/Gross Weight77.16/83.77 lbs
35/38 kg
141.76/152.34 lbs
64.3/69.1 kg
192.90/224.21 lbs
87.5/101.7 kg

Efficiency Ratings

Rating18k/24k Models30k/36k Models48k/60k Models
Cooling SEER218.817.0 / 16.116.0 / 15.2
Cooling EER211.010.7 / 10.010.0 / 8.6
Heating HSPF2-49.18.5 / 8.78.5 / 8.4
Heating COP3.153.50 / 3.403.45 / 3.37

Performance Data

Performance of Cooling

Parameter18k Model24k Model30k Model36k Model48k Model60k Model
Rated Capacity (Btu/hr)180002400030000360004800054000
Min/Max Capacity (Btu/hr)5350~200007200~2700010400~340008300~3890016600~4990021000~55000
Moisture Removal (L/h)1.712.383.573.625.295.82
Standard Operating Range (°F/°C)-13~122 (-25~50)
Rated Cooling ConditionsIndoor: 80°F DB / 67°F WB; Outdoor: 95°F DB / 75°F WB

Performance of Heating

Parameter18k Model24k Model30k Model36k Model48k Model60k Model
Heating Capacity @ 47°F (Btu/hr)180002600031000360004800054000
Min/Max Capacity @ 47°F (Btu/hr)5600~190007100~300006400~320006700~4130015300~4950026000~55000
Rated Capacity @ 17°F (Btu/hr)126002000018500256003240033000
Capacity / COP @ 5°F11200 / 221600 / 1.8719100 / 227000 / 238000 / 1.8538000 / 1.8
Max. Capacity @ 5°F112002160019100270003800038000
Standard Operating Range (°F/°C)-13~75 (-25~24)
Rated Heating ConditionsIndoor: 70°F DB / 60°F WB; Outdoor: 47°F DB / 43°F WB
2nd Rated Heating ConditionsIndoor: 70°F DB / 60°F WB; Outdoor: 17°F DB / 15°F WB
3rd Heating Cond. (Compressor Max Freq.)Indoor: 70°F DB / 60°F WB; Outdoor: 5°F DB / 5°F WB

Electrical Specifications

Parameter115V Option208/230V Option
Indoor Power Supply115V, 60Hz, 1Ph208/230V, 60Hz, 1Ph
Indoor MCA (A)5.54.0
Indoor MOP (A)1515
Outdoor Power Supply208/230V, 60Hz, 1Ph
Outdoor MCA (A)16 (18k) / 19 (24k) / 22.5 (30k) / 24 (36k) / 36 (48k) / 39 (60k)20 (18k) / 20 (24k) / 25 (30k) / 30 (36k) / 40 (48k) / 40 (60k)
Outdoor MOP (A)2020
Communication WiringAWG 20-2
Compressor RLA (A)10 (18k) / 14 (24k) / 17 (30k) / 17.5 (36k) / 27 (48k) / 30 (60k)10 (18k) / 14 (24k) / 17 (30k) / 17.5 (36k) / 27 (48k) / 30 (60k)
Outdoor Fan Motor RLA (A)0.8 (18k) / 1 (24k) / 1.1 (30k) / 1.5 (36k) / 2 (48k) / 1.2 (60k)0.8 (18k) / 1 (24k) / 1.1 (30k) / 1.5 (36k) / 2 (48k) / 1.2 (60k)
Outdoor Fan Motor W34 (18k) / 80 (24k) / 120 (30k) / 120 (36k) / 250 (48k) / 250 (60k)34 (18k) / 80 (24k) / 120 (30k) / 120 (36k) / 250 (48k) / 250 (60k)
Indoor Fan Motor RLA (A)2 (18k/24k) / 4.5 (30k/36k) / 7.8 (48k) / 8.3 (60k)2 (18k/24k) / 4.5 (30k/36k) / 7.8 (48k) / 8.3 (60k)
Indoor Fan Motor W250 (18k/24k) / 375 (30k/36k) / 750 (48k/60k)250 (18k/24k) / 375 (30k/36k) / 750 (48k/60k)
System Power Input @ Cooling (W)1635 (400~1900) (18k) / 2181 (530~2870) (24k) / 2778 (735~3230) (30k) / 3600 (710~4500) (36k) / 4800 (1400~5350) (48k) / 6200 (1800~6410) (60k)1635 (400~1900) (18k) / 2181 (530~2870) (24k) / 2778 (735~3230) (30k) / 3600 (710~4500) (36k) / 4800 (1400~5350) (48k) / 6200 (1800~6410) (60k)
System Power Input @ Heating (W)1675 (340~1650) (18k) / 2396 (440~2730) (24k) / 2595 (455~2550) (30k) / 3100 (460~3550) (36k) / 4085 (1025~4650) (48k) / 4650 (975~4810) (60k)1675 (340~1650) (18k) / 2396 (440~2730) (24k) / 2595 (455~2550) (30k) / 3100 (460~3550) (36k) / 4085 (1025~4650) (48k) / 4650 (975~4810) (60k)
MCA: Min. circuit amps (A)5.5/8.0/8.0/8.0/14.5/14.54.0/6.0/6.0/6.0/11.0/11.0
RLA: Rated load amps (A)10/14/17/17.5/27/3010/14/17/17.5/27/30
MOCP: Max. over current protection (A)15/15/15/15/15/1515/15/15/15/15/15
W: Fan motor rated output (W)250/250/375/375/750/750250/250/375/375/750/750

Piping Specifications

ParameterValue
Throttle Type (Indoor)EXV
Throttle Type (Outdoor)EXV
Liquid Size9.52mm (3/8in)
Gas Size19mm (3/4in)
Max. Piping Length (ft/m)98.4 (30) / 164 (50) / 246 (75) [Varies by model capacity]
Max. Height Difference (ft/m)65.6 (20) / 82 (25) / 98.4 (30) [Varies by model capacity]
Max. Pre-charged Length (ft/m)24.6 (7.5)
Refrigerant Pre-charged Amount (oz/kg)51.15 (1.45) / 74.08 (2.1) / 91.71 (2.6) / 116.4 (3.3) / 134.04 (3.8) [Varies by model capacity]
Additional Charge of Refrigerant ((oz/ft)/(g/m))0.7 (65)
Connection MethodFlared

Dimensions

Indoor Unit Dimensions

Dimension18k/24k Models30k/36k Models48k/60k Models
A: Model Height (inch/mm)45 / 114349 / 124553 / 1346
B: Model Width (inch/mm)17-1/2 / 44521 / 53424-1/2 / 622
C: Supply Air Opening Width (inch/mm)15-5/8 / 39719-1/8 / 48622-5/8 / 575
D: Return Air Opening Width (inch/mm)15-1/8 / 38418-5/8 / 47322-1/8 / 562
E: Model Depth (inch/mm)21 / 53421 / 53421 / 534
F: Supply Air Opening Depth (inch/mm)10-1/4 / 26010-1/4 / 26010-1/4 / 260
G: Return Air Opening Depth (inch/mm)18-3/4 / 47618-3/4 / 47618-3/4 / 476
H: Supply Air Opening Clearance (inch/mm)15/16 / 2415/16 / 2415/16 / 24
I: Return Air Opening Side Clearance (inch/mm)1-1/4 / 321-1/4 / 321-1/8 / 28
J: Return Air Opening Front Clearance (inch/mm)1-1/2 / 381-5/8 / 411-5/8 / 41
K: Return Air Opening Back Clearance (inch/mm)5/8 / 163/4 / 163/4 / 19

Outdoor Unit Dimensions

Dimensional drawings of the outdoor unit are provided, showing front, side, and top views with key measurements labeled in inches and millimeters. These diagrams illustrate the unit's overall width, depth, and height, as well as the placement of service panels, pipe connections (liquid and gas refrigerant), and mounting bolt positions.

Installation Instructions for Outdoor Unit

Clearance requirements for the outdoor unit installation are specified to ensure proper operation and airflow. The unit requires:

  • A minimum of 20 inches (500mm) clearance at the front and sides when the unit is operating.
  • A minimum of 4 inches (100mm) clearance on the sides.
  • A minimum of 14 inches (350mm) clearance at the rear.
  • A minimum of 20 inches (500mm) clearance on any two sides (left, right, rear) if the unit is clear on those sides.

✔️ Meets all spatial requirements shown in Installation Clearance Requirements above.

Fan Performance for Indoor Unit

A line graph illustrates the fan performance for the indoor unit. The x-axis represents external static pressure in inches of water gauge (in.w.c.), ranging from 0 to 0.8. The y-axis represents air flow rate in cubic feet per minute (CFM), ranging from 0 to 1000 (for 18k/24k models) or up to 1600 (for larger models). Three lines, labeled H (High), M (Medium), and L (Low), show the consistent air flow rate achieved at different fan speeds across the tested static pressure range.

Key Features

  • Multi-position installation: horizontal (left or right), vertical (up or down).
  • Aluminum Coil construction.
  • Constantly Air Flow system capable of up to 0.80 In.W.G.
  • Optional 1-inch R4.2 fiberglass free insulation to reduce condensation and boost efficiency.
  • Optional Auxiliary heat kit available, up to 25kW.
  • Designed for easy maintenance.
  • Multiple control options are available, including:
    • Two-way communication wired controller (120N/X6).
    • Two-way communication wired controller with built-in WiFi (120N/X6W).
    • Wireless remote controller.
    • Third-Party 24V Thermostat compatibility.
  • Adaptive Control System.
  • High efficiency ratings: up to 18.8 SEER2, 11 EER2, and 9.7 HSPF2.
  • Chassis heater and crankcase heater are equipped as standard.

PDF preview unavailable. Download the PDF instead.

Innovair-R454B-SLIM4-Heat-Pump-AHU-Submittals Adobe PDF Library 24.3.212

Related Documents

Preview Innovair SLIM4 SAV Series Indoor Unit User Manual
Comprehensive user manual for the Innovair SLIM4 SAV Series indoor unit, detailing safety precautions, installation, operation, maintenance, and troubleshooting for split system cooling and heat pump applications.
Preview Innovair SLIM4 Hyper Heat Pump Series Submittal Data Sheet
Comprehensive submittal data sheet for the Innovair SLIM4 Hyper Heat Pump Series, detailing specifications, performance metrics, electrical requirements, piping details, and dimensional data for models SHV18H2BA/SAV18BDA through SHV60H2BA/SAV60BDA. Includes cooling and heating performance at various conditions, indoor and outdoor unit specifications, and installation clearance guidelines.
Preview Innovair SLIM4 Heat Pump Series Submittal Data Sheets
Comprehensive submittal data sheets for Innovair's SLIM4 Heat Pump Series, detailing specifications, efficiency ratings, performance data, electrical requirements, and dimensions for models SOV18H2BA, SWV18BDA, SOV24H2BA, SWV24BDA, SOV30H2BA, SWV30BDA, SOV36H2BA, and SWV36BDA.
Preview Innovair Slim 4+ Central Heat Pump System: Approval Drawings and Specifications
Comprehensive approval drawings and technical specifications for the Innovair Slim 4+ Central Heat Pump System. Details include performance metrics like SEER2 and HSPF2, features, model variations, dimensions, electrical heating element compatibility, and available options for residential and commercial applications.
Preview Innovair Split Horizontal-Vertical Duct Air Conditioner Owner's and Installation Manual
Comprehensive owner's and installation manual for Innovair Split Horizontal-Vertical Duct Air Conditioners. This guide provides essential safety precautions, operating instructions, maintenance tips, troubleshooting advice, and detailed installation procedures for Innovair air conditioning units.
Preview INNOVAIR DEV Series Heat Pump & Air Conditioner AHRI Certified Ratings
Comprehensive AHRI certified product ratings for INNOVAIR DEV Series split system heat pumps and air conditioners, detailing SEER, EER, HSPF, and model specifications for both 2017 and 2023 standards.
Preview INNOVAIR SHV and SOV Series Heat Pump Product Ratings and IRA Tax Credit Eligibility
This document provides detailed product ratings for INNOVAIR SHV and SOV Series Heat Pump systems, including cooling and heating capacities, SEER2, EER2, and HSPF2 ratings. It also notes potential eligibility for the U.S. federal tax credit.
Preview Innovair GAV Series Indoor Unit Installer's Guide - Safety, Installation, and Specifications
Comprehensive installer's guide for Innovair GAV Series indoor air handler units (GAV24B2A, GAV36B2A, GAV48B2A, GAV60B2A). Covers installation, safety precautions, electrical wiring, airflow performance, ductwork, refrigerant pipe connection, maintenance, and wiring diagrams for R454B refrigerant systems.