ABB ESB20-20N-06 Installation Contactor
Model: ESB20-20N-06
Description: Installation Contactor (NO) 20 A - 2 NO - 0 NC - 230 V - Control Circuit DC
Product Details
The ESB20..N installation contactors are designed to control single loads up to 20 A and can be operated by AC or DC. They are suitable for both household and industrial applications, offering hum-free operation, low power consumption, and integrated overvoltage protection. Various contact combinations and accessories are available.
Product Image: A compact, white electrical component with a clear front panel showing the ABB logo, product name (ESB20-20N-06), and terminal markings (A1, A2). It has a single pole with a visible lever for manual operation.
Summary Information
Product Model | ESB20-20N-06 |
---|---|
Product ID | 1SBE121111R0620 |
European Article Number (EAN) | 3471523007505 |
Catalog Description | ESB20-20N-06 Installation Contactor (NO) 20 A - 2 NO - 0 NC - 230 V - Control Circuit DC |
Ordering Information
1-level packaging EAN | 3471523004641 |
---|---|
Minimum order quantity | 1 piece |
Customs tariff number | 85365080 |
Dimensions
Product Net Width | 18 mm |
---|---|
Product Net Height | 85 mm |
Product Net Depth | 65 mm |
Product Net Weight | 0.14 kg |
Technical Parameters
Parameter | Value |
---|---|
Rated operational voltage | Main Circuit 220 V DC, Main Circuit 250 V AC |
Rated control circuit voltage (Uc) | 230 V (Control Circuit DC, Control Circuit 50 Hz, Control Circuit 60 Hz, Control Circuit 400 Hz) |
Rated frequency (f) | Main Circuit DC, Main Circuit 50 Hz, Main Circuit 60 Hz |
Rated operational current AC-1 (Ie) | (NO) 20 A |
Rated operational current AC-3 (Ie) | (230 V) Single Phase, NO 9 A |
Rated operational power AC-1 (Pe) | (230 V) Single Phase, NO 4.6 kW |
Rated operational power AC-3 (Pe) | (230 V) Single Phase, NO 1.3 kW |
Rated operational current AC-7a (Ie) | (NO) 20 A |
Rated operational power AC-7a (Pe) | (230 V) Single Phase, NO 4.6 kW |
Rated operational current AC-7b (Ie) | (230 V) Single Phase, NO 9 A |
Rated operational power AC-7b (Pe) | (230 V) Single Phase, NO 1.3 kW |
Recommended screwdriver | Control Circuit Pozidriv 1, Main Circuit Pozidriv 1 |
Rated impulse withstand voltage (Uimp) | 6 kV |
Rated insulation voltage (Ui) | 400 V |
Main circuit connection capacity | Flexible with Ferrule 1x 1 ... 6 mm, Flexible with Ferrule 2x 1 ... 2.5 mm, Flexible with Insulated Ferrule 1x 1 ... 6 mm, Flexible with Insulated Ferrule 2x 1 ... 1.5 mm, Flexible 1x 1 ... 6 mm, Flexible 2x 1 ... 4 mm, Rigid 1x 1 ... 10 mm, Rigid 2x 1 ... 4 mm |
Control circuit connection capacity | Flexible with Ferrule 1x 1 ... 2.5 mm, Flexible with Ferrule 2x 0.75 ... 1.5 mm, Flexible with Insulated Ferrule 1x 1 ... 2.5 mm, Flexible with Insulated Ferrule 2x 0.75 ... 1 mm, Flexible 1x 1 ... 2.5 mm, Flexible 2x 1 ... 1.5 mm, Rigid 1x 0.5 ... 4 mm, Rigid 2x 0.75 ... 2.5 mm |
Tightening torque | Control Circuit 0.9 N·m, Main Circuit 1.2 N·m |
Stripping length | Control Circuit 7 mm |
Main circuit connection capacity (continued) | Main Circuit 10 mm |
Degree of protection | IP20 |
Electrical endurance (AC-1, NO) | 150000 cycles |
Electrical endurance (AC-3, NO) | 150000 cycles |
Electrical endurance (AC-7a, NO) | 150000 cycles |
Electrical endurance (AC-7b, NO) | 150000 cycles |
Mechanical endurance | 1000000 cycles |
Number of poles | 2P |
Number of NC auxiliary contacts | 0 |
Number of NO auxiliary contacts | 0 |
Number of NC main contacts | 0 |
Number of NO main contacts | 2 |
Width in modular spacing units | 1.0 |
Pollution degree | 3 |
Standards | IEC/EN 60947-1, IEC/EN 60947-4-1, UL 60947-1, UL 60947-4-1, IEC/EN 61095, IEC 60335-2-40 A2L |
UL/CSA Applicable Technical Parameters
Parameter | Value |
---|---|
Max. service voltage UL/CSA | Main Circuit 240 V AC |
Rated power UL/CSA | (220 ... 240 V AC) Single Phase, NO 1 Hp |
Main circuit connection capacity UL/CSA | Solid 14-8 AWG, Stranded 14-8 AWG |
Control circuit connection capacity UL/CSA | Solid 16-10 AWG, Stranded 16-10 AWG |
Tightening torque UL/CSA | Control Circuit 8 in·lb, Main Circuit 11 in·lb |
Environmental Conditions
Ambient temperature | Operation -25 ... +55 °C, Storage -40 ... +80 °C |
---|---|
Maximum operating altitude | 2000 m |
Mechanical shock withstand (IEC 60068-2-27) | 11 ms Pulse 15g |
RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
Material Compliance
- Conflict Minerals Reporting Template (CMRT): 9AKK108467A5658
- REACH Declaration: 2CMT2021-006202
- RoHS: 2CMT2021-006277
- Toxic Substances Control Act - TSCA: 2CMT2023-006525
- WEEE B2C / B2B: Business To Consumer
- WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
Product Environmental Declaration (EPD): 1SAC200416H0001
Certificates and Declarations
Certificate/Declaration | Document Code |
---|---|
A2L Certificate - IEC | 1SAA920000-4601 |
ABS Certification | 1SAA920000-0101 |
CB Certification | 1SAA920007-2001 |
CQC Certification | CQC2018010304057353, CQC2018010304057344 |
Declaration of Conformity - CCC | 2020980304001370 |
Declaration of Conformity - CE | 2020980304001371 |
Declaration of Conformity - UKCA | 1SAD101100-3301 |
DNV Certification | 1SAD201100-3301 |
EAC Certification | 1SAA920000-0306 |
NF Certification | 1SAA920003-2701 |
RMRS Certification | 1SAA920002-1201 |
UL Certification | 1SAA920000-0705, E191658-19960301 |
Packaging Information
1-level packaging unit | box 1 piece |
---|---|
1-level packaging width | 88 mm |
1-level packaging height | 71 mm |
1-level packaging length | 20 mm |
1-level packaging gross weight | 0.14 kg |
Classification
Object classification code | Q |
---|---|
ETIM 5 | EC001653 - Installation contactor for distribution board |
ETIM 6 | EC001653 - Installation contactor for distribution board |
ETIM 7 | EC001653 - Installation contactor for distribution board |
eclass | V11.0: 27142308 |
UNSPSC | 39121529 |
IDEA granularity classification code (IGCC) | 4759 >> Installation contactor for distribution board |
E-Number (Finland) | 3707565 |
E-Number (Norway) | 4190231 |
E-Number (Sweden) | 3210556 |
ETIM 8 | EC001653 - Installation contactor for distribution board |
Classification Path: Low voltage products and systems → Contactors → Building contactors. Low voltage products and systems → Circuit protection products → Command and Signalling Devices → Building contactors.
Accessories
Identifier | Description | Type | Quantity | Unit Of Measure |
---|---|---|---|---|
1SAE901901R1011 | EH04-11N Auxiliary Contact - 0 NO - 0 NC - Auxiliary Circuit 50 Hz | EH04-11N | 1 | piece |
1SAE901901M1011 | EH04-11N Auxiliary Contact - 0 NO - 0 NC - Auxiliary Circuit 50 Hz | EH04-11N | 1 | piece |
1SAE901901R1020 | EH04-20N Auxiliary Contact - 0 NO - 0 NC - Auxiliary Circuit 50 Hz | EH04-20N | 1 | piece |
1SAE901901M1020 | EH04-20N Auxiliary Contact - 0 NO - 0 NC - Auxiliary Circuit 50 Hz | EH04-20N | 1 | piece |