EP DROP 1-2: Electronic Control Panel for 1 or 2 Pumps in Rainwater Harvesting Tanks
The EP DROP 1-2 is a specialized electronic control panel designed for rainwater harvesting systems. It ensures the automatic emptying of the collection tank after a rainfall event. The integrated rain sensor initiates the pump's emptying cycle after a programmed time following the meteorological event.
This control panel is compact, economical, easy to install, and program, making it a suitable replacement for older control units.
Key Features
- Specific Design: Tailored for "first rain" systems.
- Intuitive: Offers maximum ease of configuration and use.
- Complete: Supplied with a rain sensor as standard.
- Maximum Control: Integrates the most comprehensive system protections.
Main Characteristics
- LEDs on the front panel indicate operating status and alarms.
- AUTOMATIC – 0 (standby) – MANUAL (fixed or impulse) operating buttons.
- Motor alternation for EP DROP 2 models.
- Dry-run protection with level sensors/float switches.
- Up to 4 control inputs: float switches.
- Inputs for thermal pads with automatic reset (excludable).
- Selectable overcurrent protection delay.
- Automatic reset for minimum current alarm (excludable).
- Delay for network return activation (excludable).
- Manual activation of buttons (fixed or momentary).
- Provision for start capacitors for single-phase versions (not included).
- System activation delay timer after meteorological phenomena (programmable).
- Rain sensor included.
Versions
- Single-phase: 100-240Vac 50/60Hz
- Three-phase: 310-450 Vca 50/60 Hz
Controls
- Electronic maximum current control with assisted calibration.
- Electronic minimum current control (dry-run operation) with assisted calibration.
- Phase failure or incorrect sequence control on power input (excludable).
Alarms
- Indicated alarms: voltage status, levels, motor overload, motor minimum current, motor thermal protection (clicson).
- General alarm output contacts.
Protections
- Auxiliary and motor protection fuses.
- Main interlocking switch (if provided).
- ABS casing, IP55 rated.
Functions Incorporated in EP DROP 2
- Motor alternation.
- Immediate motor changeover in case of failure.
Components
- Rain Sensor: Detects rainfall to initiate system operation.
- Modular Extension: For additional functionality.
- RS485 (Optional): For communication.
Dimensions [mm]
FIG. 1:
Height: 310 mm, Width: 240 mm, Depth: 185 mm
FIG. 2:
Height: 310 mm, Width: 230 mm, Depth: 240 mm
EP DROP 1 Specifications
Model | Voltage | Power (kW) | Power (HP) | Current Range | Max Current (A) | Fig. | Casing Material | Weight (kg) |
---|---|---|---|---|---|---|---|---|
EP DROP 1-Mono | 1~230 V | 2.2 | 3 | 2-18 A | 18A | 1 | Plastic | 1.5 |
EP DROP 1-Tri/7.5 | 3~400 V | 7.5 | 10 | 2-16 A | 16A | 1 | Plastic | 2.3 |
EP DROP 1-Tri/11 | 3~400 V | 11 | 15 | 16-25 A | 25A | 1 | Plastic | 2.5 |
EP DROP 1-Tri/15 | 3~400 V | 15 | 20 | 16-32 A | 32A | 1 | Plastic | 3 |
EP DROP 2 Specifications
Model | Voltage | Power (kW) | Power (HP) | Current Range | Max Current (A) | Fig. | Casing Material | Weight (kg) |
---|---|---|---|---|---|---|---|---|
EP DROP 2-Mono | 1~230 V | 2.2 | 3 | 2-18 A | 18A | 1 | Plastic | 1.5 |
EP DROP 2-Tri/7.5 | 3~400 V | 7.5 | 10 | 2-16 A | 16A | 1 | Plastic | 2.5 |
EP DROP 2-Tri/11 | 3~400 V | 11 | 15 | 16-25 A | 25A | 2 | Plastic | 3 |
EP DROP 2-Tri/15 | 3~400 V | 15 | 20 | 16-32 A | 32A | 2 | Plastic | 3.5 |
Connection Type 1 Diagrams
Diagrams illustrating the wiring for various inputs and outputs, including alarm signals, sensor connections, and power supply.
Optional Features (Available Upon Request)
- Acoustic alarm (90 dB, 12Vdc).
- Flashing alarm light (12V AC/DC).
- Analog timer with daily program.
- Digital timer with weekly program.
- Work pause timer.
- External 24 Vac control for supply connection/disconnection.
- External 230 Vac control for supply connection/disconnection.
Accessories
- PROXPS RS485 Modbus module.
- PRO-SL level sensor module.
- PRO-SL H20 oil chamber infiltration module.
- BMS PRO-6D0 dry contact module.
- PRO-DBT buffer battery module.
- Bluetooth module for PROXPS application.
- Pressure switch SQUARE D 4.6 IP20 F1/4 1.4-2.8 M NC.
- Pressure switch SQUARE D 7 IP20 F1/4 4.3-5.4 M NC.
- Pressure switch TELEMECANIQUE 6 IP54 F1/4 1.8-4.8 M NC.
- Pressure switch TELEMECANIQUE 6 IP54 F1/4 1.8-4.8 NA/NC.
- Pressure switch TELEMECANIQUE 6 IP54 F1/4 1.8-4.8 T NC.
- Pressure switch SQUARE D 10.5 IP20 F1/4 4.3-5.4 M NC.
- Pressure switch TELEMECANIQUE 12 IP54 F1/4 3.6-10.3 M NC.
- K3SL Kit of 3 wireless level probes.
- 5m PVC float switch with counterweight.
- 10m PVC float switch with counterweight.
- 20m PVC float switch with counterweight.
- Taurus float switch H07RNF 8.8 GTAH3x106GG01 6 m.
- Taurus float switch H07RNF 8.8 GTAH3x110GG01 10 m.
- Taurus float switch H07RNF 8.8 GTAH3x115GG01 15 m.
- Taurus float switch H07RNF 8.8 GTAH3x120GG01 20 m.
- EBARA RNC-1002 10 m float switch.
Special Executions (Available Upon Request)
- IP65 single-door fiberglass enclosure.
- IP65 blind double-door fiberglass enclosure.
- IP65 blind double-door metal enclosure.
- IP65 transparent double-door fiberglass enclosure.
- IP65 transparent double-door metal enclosure.
- Base for floor mounting (100 mm).
- Hollow column with floor fixing.