Mastervolt Sunmaster XS4300/XS3200/XS2000 User and Installation Manual
This document provides comprehensive instructions for the installation, operation, and maintenance of the Mastervolt Sunmaster XS4300, XS3200, and XS2000 grid-connected solar inverters.
1 General Information
1.1 Product Description
The Mastervolt Sunmaster XS4300, XS3200, and XS2000, collectively referred to as "Sunmaster", are grid-connected solar inverters designed for feeding power generated by photovoltaic modules into the utility grid. They are not suitable for stand-alone use without a public grid connection.
1.2 Use of this Manual
This manual is intended for both qualified electricians (for installation, operation, and commissioning) and end-users (for operation, maintenance, and minor malfunction correction). All personnel working with the apparatus must be familiar with and follow the instructions herein. The manual should be stored in an accessible place.
1.3 Validity of this Manual
The specifications, provisions, and instructions apply to the standard versions of the Sunmaster delivered by Mastervolt.
1.4 Guarantee Specifications
Mastervolt provides a five-year product guarantee, conditional upon adherence to all installation and operation instructions and warnings provided in this manual. Installation must be performed by a qualified electrician, and maintenance must follow stated instructions. Unauthorized changes or repairs void the warranty. The warranty covers repair/replacement costs by Mastervolt; installation labor or shipping costs are not included.
1.5 Liability
Mastervolt accepts no liability for consequential damage due to the use of the Sunmaster or for errors within the manual and their results.
1.6 Changes to the Sunmaster
Any changes to the Sunmaster require prior written permission from Mastervolt.
1.7 Identification Label
An identification label, located as shown in Figure 1-1, contains important technical information for service and parts. ⚠️ CAUTION! Never remove the identification label.
2 Safety Guidelines and Warnings
Safety instructions and warnings are marked by pictograms:
- ⚠️ CAUTION! Special information, commands, and prohibitions to prevent damage.
- ⚠️ WARNING Refers to possible injury to the user/installer or significant material damage if procedures are not followed carefully.
2.2 Use for Intended Purpose
The Sunmaster is designed for permanent installations connected to a separate, grounded AC group, with no other electrical equipment connected. The electrical installation must meet applicable regulations and standards. ⚠️ WARNING! Never use the Sunmaster in situations with danger of gas or dust explosion or potentially flammable products.
2.3 Organisational Measures
The installer/user must have access to this manual and be familiar with its contents, especially Chapter 2.
2.4 Installation, Maintenance and Repair
These tasks must be performed only by qualified electricians due to lethal voltages. Connections and safety features must comply with local regulations. Use only original spare parts.
2.5 Warning of Special Dangers
- High DC voltages (up to 600V) are present.
- Voltages at the grid and solar side are not safe to touch and cannot be switched off at the solar side. An internal or external DC switch may be obligatory depending on local regulations.
- Do not work on the Sunmaster or electrical installation if it is connected to solar panels or AC grid.
- Only qualified electricians should make changes to your electrical system.
3 Before You Start
3.1 Unpacking
The delivery includes the Sunmaster, a mounting bracket, and this manual. After unpacking, check for damage. Do not use if damaged; contact your supplier.
3.2 Country Selection
The Sunmaster has an anti-islanding device (QNS/ENS) that must be configured at first installation according to local regulations (see section 4.3.2). Some models include an internal DC switch. Table 1 lists part numbers and indicates if a DC switch is included.
3.3 Installation Environment
- Ambient temperature: -20°C to 60°C (derating above 45°C).
- Install indoors in a conditioned or unconditioned environment.
- Maintain 10 cm clearance around the Sunmaster.
- Ensure hot air is discharged by forced ventilation if installed in a closed space.
- Keep at least 50 cm clearance between multiple Sunmasters, or take measures to prevent heat transfer.
- The Sunmaster may produce a slight noise level.
- Mount vertically on a solid wall.
- Optimal display readability is achieved when viewed from an equal or lower position.
Installation Environment Diagrams:
- Weather: ⚠️ WARNING! Never expose the Sunmaster to direct weather conditions such as rain, snow, or wind. Install in a sheltered environment. (✅ for sheltered, ❌ for exposed).
- Mounting: Mount the Sunmaster vertically on a solid wall. (✅ for vertical on solid wall, ❌ for other).
- Sunlight/Heat: Do not expose the Sunmaster to direct sunlight or other heat sources. (❌ for direct sun/heat).
- Environment: Do not expose the Sunmaster to humid or dusty environments. (❌ for humid/dusty).
- Clearance: Keep 10 cm clearance around the Sunmaster. When installed next to each other, keep at least 50 cm clearance. If this is not possible, take measures to avoid one inverter heating up the other. (✅ for correct clearance, ❌ for insufficient).
Table 1: Sunmaster Models and DC Switch
Part number | Description | DC switch |
---|---|---|
131004300 | XS4300 IP44 ENS | No |
131014300 | XS4300 IP44 ENS SW | Yes |
131003200 | XS3200 IP44 ENS | No |
131013200 | XS3200 IP44 ENS SW | Yes |
131002000 | XS2000 IP44 ENS | No |
131012000 | XS2000 IP44 ENS SW | Yes |
3.4 AC Wiring
The Sunmaster must be used in a permanent installation connected to a separate AC distribution group. Cabling must be double insulated. Use appropriate AC wire diameter to ensure single wire resistance does not exceed 0.25 Ohm (e.g., 3x4mm² for up to 25 meters).
3.5 Grounding
An equipment-grounding conductor must be connected to the AC-output ground terminal. Grounding must comply with local codes. The solar array does not require grounding due to galvanic isolation.
3.6 Specifications of the Solar System
The solar system must meet the following specifications:
- Maximum open circuit string voltage at lowest possible temperature of PV modules and maximum PV power connected to the inverter.
Solar System Specifications Table:
Model Sunmaster | Max voltage | Max power |
---|---|---|
XS4300 | 550Vdc max | 4600Wp |
XS3200 | 600Vdc max | 3500Wp |
XS2000 | 450Vdc max | 2100Wp |
- Double insulated PV-wiring is required.
- All string cables must be double insulated and fitted with pre-assembled MultiContact connectors (Ø4mm).
- If two or more strings are connected, their lengths must be equal.
⚠️ CAUTION! Do not install the Sunmaster if the solar system does not comply with these stipulations.
3.7 DC Switch
A DC switch between PV modules and the inverter may be mandatory per local regulations (e.g., IEC60364-7-712). Mastervolt offers models with integrated DC switches. An external DC switch can also be used.
3.8 PV Modules and Strings
PV modules are connected in series to form a "string". String voltage should equal the open circuit voltage (Voc) per PV module multiplied by the number of modules per string. This value should be 70-95% of the calculated string voltage, depending on irradiation and temperature. The Sunmaster has a single MPP tracker and two parallel string connections (Figure 3-1).
3.8.1 Connection of two strings (standard)
Two strings can be connected directly to the Sunmaster's Solar inputs. The total input power should be distributed equally over both inputs as much as possible (Figure 3-2).
3.8.2 Connection of more than two strings (option)
For more than two strings, Multicontact Y-adapters may be used to combine strings (Figure 3-3, Figure 3-4). Strings connected to the same Solar input must have an equal number of identical PV-modules.
3.9 General Safety and Installation Precautions
- ⚠️ WARNING! Be sure that all wiring is disconnected from any power source during the entire installation.
- ⚠️ CAUTION! Short circuiting or reversing polarity may damage the Sunmaster, cabling, and terminal connections. Follow all installation instructions in order. The DC switch, if installed, must remain in the OFF position during installation.
3.10 Things You Need for Installation
Ensure you have the following items:
- Sunmaster + mounting bracket (included).
- Four screws (with plugs) for mounting (max. 5 mm diameter). Use mounting materials suitable for the Sunmaster's weight.
- Hexagonal socket wrench #4 for the connection compartment.
- Flat blade screwdriver.
- Masterbus communication cables.
- RS485 communication cables.
4 Installation
4.1 Installation Step by Step
⚠️ CAUTION! Read chapters 2 and 3 prior to installation.
- Mark the position of the four mounting spots using the mounting bracket (Figure 4-1).
- Fix the mounting bracket to the wall (Figure 4-2).
- Place the Sunmaster over the mounting bracket and move it downwards until it locks (Figure 4-3).
- Loosen the two hexagonal screws (a) at the bottom of the cabinet (Figure 4-4).
- Insert a flat blade screwdriver into the indicated slots (b) and remove the bottom plate of the Sunmaster (Figure 4-5).
- Feed the AC wiring through the left cable gland of the bottom plate and connect the wiring to the screw terminals (Figure 4-6).
- Connect the MasterBus cables to the MasterBus connectors and the QS-Databus wiring to the RJ-45 connectors for monitoring (option) (Figure 4-7).
- Close the connection compartment: Tighten the two hexagonal screws (a) and the cable glands (b) (Figure 4-8).
- Ensure the DC-Switch is in the OFF position. Then connect the string cabling to the Sunmaster (Figure 4-9).
4.2 Use in Italy
In Italy, ENEL may require sealing parts of the AC wiring. All Sunmasters are equipped with a wire seal facility (Figure 4-10).
4.3 Commissioning After Installation
Commissioning should be carried out during daytime only to check correct operation.
4.3.1 Switching on
- Check that the DC-switch of the solar array is in the OFF position.
- Switch on the AC grid.
- Move the DC-switch of the solar array to the ON position.
- The Sunmaster will switch on automatically if connection is correct and solar irradiation is sufficient. This may take a few seconds.
- At first commissioning, the country code must be selected (see section 4.3.2).
4.3.2 Country Code Selection
Follow these steps to configure the Sunmaster for local grid connection regulations:
- After commissioning, a message is displayed. Press S4 to scroll through the country codes.
Country code | Norm | Use Allowed in |
---|---|---|
GERMANY 1P, limited to 4.600 W | ENS | Germany, Austria, Belgium |
GERMANY 3P | ENS | Germany, Austria, Belgium |
SPAIN | QNS | Spain |
ITALY | ENS | Italy |
UK | QNS | United Kingdom |
FRANCE | ENS | France |
AUSTRALIA | QNS | Australia |
GREECE | QNS | Greece |
HOLLAND | QNS | Netherlands, rest of Europe |
USA 240V | QNS | USA (Split Phase 240V) |
USA 208V | QNS | USA (ThreePhase 208V) |
KOREA | QNS | South Korea |
TAIWAN | QNS | Taiwan |
- Select the applicable country code from the table.
- Press S4 to scroll through the country codes.
- If the correct country code is shown, press S2 to select it.
- Confirm your selection by pressing S3 (or cancel by pressing S4).
- If a wrong country code was entered, press S2 and S4 simultaneously for 3 seconds to restart the procedure.
- The Sunmaster switches on. Refer to chapter 5 for operation instructions.
For GERMANY 3P, if three inverters are MasterBus connected, they switch on/off together. The 3-PH block function is important in this configuration (see section 5.3.5 and 5.3.8).
4.4 De-commissioning
⚠️ CAUTION! Follow instructions in order.
- Cut off the grid voltage by switching off the AC distribution switch.
- If applied, move the DC switch to the OFF position.
- Disconnect the MultiContact connectors from the Sunmaster.
- Remove the bottom plate of the Sunmaster and disconnect the AC wiring.
The Sunmaster can then be safely demounted.
5 Operation
5.1 General
The Sunmaster switches on automatically with sufficient solar irradiation. It operates automatically without user action. At night or insufficient irradiation, it switches off automatically. The display shows no information when off. There is no ON/OFF switch; refer to section 4.4 for decommissioning. ⚠️ CAUTION! Never disconnect the MultiContact plugs during operation, as this may cause a spark or electric arc.
5.2 Forced Cooling
An internal cooling fan ensures optimum temperature control. The fan speed increases with internal temperature, contributing to efficiency and lifetime.
5.3 LCD Display
The integrated LCD display shows system performance, including daily energy revenues, actual solar/AC power, voltage, current, frequency, inverter temperature, total energy revenue, working hours, and status/diagnostics. The display is operated by four keys: S1, S2, S3, and S4 (Figure 5-1).
5.3.1 Actual Readings
When [ACTUAL] is highlighted, actual readings are shown (Figure 5-3). Press S2: Source to toggle between SOLAR 1 (DC input) and AC GRID (AC output). Press S4: Select to cycle through displayed data: [W] (Watts), [V] (Volts), [A] (Amps), [Hz] (Hertz), [Ω] (Ohms), [°C] (Celsius), and [kWh] (Kilowatt-hours).
The initial screen (Figure 5-2) shows a 0-100% bar for actual solar power and energy generated today.
Selected source = AC GRID | Selected source = SOLAR 1 |
---|---|
W: Power supplied to the AC grid | W: Solar power supplied to the Sunmaster by the PV-strings |
V: AC grid voltage | V: DC voltage from the PV-string |
A: AC current supplied to the AC grid | A: DC current from the PV-string |
Hz: AC grid frequency | Hz: n/a |
Ω: AC grid impedance* | Ω: n/a |
°C: Internal temperature of the inverter | °C: Internal temperature of the inverter |
kWh: Energy generated today | kWh: PV-string |
* ENS-models only (see chapter 3.2), else 0.00 is shown. |
5.3.2 Historical Data
When [DAY] is highlighted, daily performance for the last 30 days is shown (Figure 5-4). Press S4: Select to switch between [kWh] (total energy yield of the selected day) and [h] (operating hours of the selected day). Press S3: Info to select a day (short press for one day back, hold to scroll forward).
5.3.3 Total Energy Revenues
When [TOTAL] is highlighted, total performance since commissioning is displayed (Figure 5-5). Press S2: Source to toggle between SOLAR 1 (DC input total performance) and AC GRID (AC output total performance). Press S4: Select to switch between [kWh] (total energy yield) and [h] (total operating hours).
5.3.4 System Information
When [SYSTEM] is highlighted, system information is displayed (Figure 5-6). Press and hold S2 for 3 seconds to toggle Sleep mode (backlight off after 60s inactivity vs. always illuminated). Press S3: Info to cycle through [Model] (e.g., "XS4300"), [Serial] (serial number), [Firmw] (firmware version), and [Error] (cause of failure, see section 5.3.6).
5.3.5 Settings
Three settings can be adjusted: Backlight On/Off, Isolation detection On/Off, and 3 PH block On/Off (see section 5.3.8). Press S1 and S2 for 5 seconds to enter settings. S3 and S4 scroll through options, S2 confirms the selection.
5.3.6 Failures
The Sunmaster operates normally if the red ERROR LED is OFF. If the LED illuminates or blinks, a failure is detected. The display will show an error code (Figure 5-7). Refer to Chapter 6 for error code explanations. Normal shutdown occurs at night or with insufficient irradiation; this is not a failure.
5.3.7 Power Limitation
The power limitation function, if activated via a datalogger (e.g., DataControl Pro/Premium II), limits the inverter's output to a set percentage (e.g., "PM 80" means 80% of maximum power). The inverters return to normal operation after 10 minutes without a power limitation command.
5.3.8 3-Phase Block
This security measure, required by some grid operators for 3-phase configurations, ensures all inverters provide energy to the grid or none do. If one inverter fails, the others halt as well (Figure 5-8).
5.4 Maintenance
No specific maintenance is required. Examine the electrical installation annually for defects like loose connections or burnt wiring. Clean the cabinet with a soft, dry cloth only. Do not use liquids, acids, or scourers.
6 Trouble Shooting
Consult an installer if problems persist. The table below lists common errors and their solutions:
Error LED | Error Code | Meaning | What to do? |
---|---|---|---|
Off | NONE | No error | Inverter is working normally. |
Off | Insufficient irradiation | Normal at night. Consult installer if display shows no information during daytime. Check PV module wiring. | |
Off | WAIT 0:00 | Start-up | Inverter checks AC grid quality before operating. May take up to 5 minutes. |
Off | COUNTRY (or any name of a country) | Country code not selected | Select the correct country code (see section 4.3.2). |
On | TEMP HI | Internal temperature high | Check for airflow obstruction (see section 3.3). Consult installer if problem persists. |
On | SOL1 LOW | Solar input voltage low | Normal condition during sunrise/sunset. Consult installer if problem persists with sufficient irradiation. |
On | SOL1 HIGH | Solar input voltage high | Contact your supplier. |
On | NO GRID | No connection to AC-grid | Check AC-grid connection and fuse in meter cupboard. |
On | ENS OFF | ENS fault | Grid safety device error. Check grid connection (wiring too thin or too long). Consult installer. |
On | G83 OFF | G83 fault | Grid safety device error. Check grid connection. Consult installer. |
On | VAC LOW | AC voltage low | Consult installer. |
On | VAC HIGH | AC voltage high | Consult installer. |
On | FAC LOW | AC frequency low | Consult installer. |
On | FAC HIGH | AC frequency high | Consult installer. |
On | INSULATION | Insulation failure | Leak current between PV modules and grounding. Consult installer. |
Fast blinking | NTC FAIL, EF I2C FAIL, ENS FAIL, CB I2C FAIL, HW VAC FAC, HW RELAY, HW ERROR 1-9 | Defective device in Sunmaster | Write down the exact error text. Consult an installer for replacement. |
7 Specifications
7.1 Technical Specifications
General Specifications | Details |
---|---|
Article number | See chapter 3.2 |
Typical string length | 5-9 modules (72 cells), 7-12 modules (54 cells) or 10-18 modules (36 cells) |
Operating temperature | -20°C to 60°C (fully protected against over temperature) |
Storage temperature | -20°C to 70°C |
Relative humidity | max. 95%; PCB has anti-moisture coating |
Protection degree | IP44 for unconditioned indoor use |
Safety class | Class I / Class II |
Galvanic isolation | Class II transformer |
MTBF | 187.000 hours |
Dimensions | See chapter 7.2 |
Weight | 10 kg (22 lbs) |
Solar Input (DC)
Sunmaster XS4300 | Sunmaster XS3200 | Sunmaster XS2000 | |
---|---|---|---|
Nominal power at 45°C ambient* | 3488W DC | 2651W DC | 1590W DC |
Maximum power | 3663W DC | 2784W DC | 1670W DC |
Recommended PV power range | 2900 - 4350Wp | 2200 - 3300Wp | 1300 - 2000Wp |
# MPP trackers | 1 MPP tracker (dynamic) | 1 MPP tracker (dynamic) | 1 MPP tracker (dynamic) |
MPP voltage range at nominal power | 230-440V DC | 180-480V DC | 145-360V DC |
MPP efficiency | 99.9% (Fraunhofer algorithm) | 99.9% (Fraunhofer algorithm) | 99.9% (Fraunhofer algorithm) |
Operating voltage range | 100 - 550V DC | 100 - 600V DC | 100 - 450V DC |
Rated current | 15A | 15A | 11A |
Start-up power | 7W | 7W | 5W |
String connections | 2 parallel | 2 parallel | 2 parallel |
DC connectors | 2 sets of Multi Contact (4 mm) connectors | 2 sets of Multi Contact (4 mm) connectors | 2 sets of Multi Contact (4 mm) connectors |
Grid Output (AC)
Sunmaster XS4300 | Sunmaster XS3200 | Sunmaster XS2000 | |
---|---|---|---|
Nominal power at 45°C ambient* | 3300W | 2500W | 1500W |
Maximum power | 3465W ** | 2625W | 1575W |
Voltage* | 230V AC single phase (184-265V country dependent) | 230V AC single phase (184-265V country dependent) | 230V AC single phase (184-265V country dependent) |
Rated current | 15A | 11A | 7A |
Fuse | 6.3x32 mm, 250V/30A T (ceramic) | 6.3x32 mm, 250V/20A T (ceramic) | 6.3x32 mm, 250V/20A T (ceramic) |
Frequency* | 45 – 65Hz, country dependent | 45 – 65Hz, country dependent | 45 – 65Hz, country dependent |
Power factor | > 0.99 at full power | > 0.99 at full power | > 0.99 at full power |
Stand-by power | < 0.5W | < 0.5W | < 0.5W |
EU efficiency | 94.6% @ 370V | 94.3% @ 400V | 94.4% @ 300V |
Maximum efficiency | 95.6% | 95.4% | 95.7% |
AC connections | PG-13.5 gland and screw terminals 2.5 - 4 mm² | PG-13.5 gland and screw terminals 2.5 - 4 mm² | PG-13.5 gland and screw terminals 2.5 - 4 mm² |
* Depending on country settings, see section 4.3.2. ** Belgian version max 3330W.
Safety Devices | Details |
---|---|
General | Galvanic separation between DC and AC side, by means of a class II transformer |
Island protection* | Mastervolt Digital ENS - VDE 0126 -1-1 compliant |
Reclosure time* | 10-300 sec |
Temperature protection | Power derating above 75°C internal temperature, switch off at 90°C |
DC side | Earth fault (switch off); over-voltage (switch off); polarity (short circuit); overcurrent (limiting by voltage shift-up); DC transients; (varistor and buffer capacitor); overload (temperature controlled power derating) |
AC side | Current limiting; over- and under-voltage (switch off); over- and under-frequency (switch off); short circuit (ceramic fuse); transients/surge (varistors) |
Monitoring | Details |
---|---|
Indicator | Backlit display with indication of power and diagnostic messages |
External communication | 2 galvanic isolated RS485 databus connections |
External communication | 2 galvanic isolated MasterBus connections |
Monitoring (optional) | Masterlog (PC Software). Free download from www.mastervolt.com |
Monitoring (optional) | PC-Link (connect the databus to the PC) |
Monitoring (optional) | Data Control Premium II: datalogger for up to 6 inverters with local, remote or internet monitoring |
Monitoring (optional) | Data Control Professional: PV system control over the Internet, for up to 20 inverters |
Regulations & Directives | Details |
---|---|
CE Conformity | Yes |
EMC Directive | EMC 89/336/EEG |
Emission | EN 55022 Class B |
Harmonics | EN 61000-3-2, EN 61000-4-11 and -3-3 |
Dips, variations, flicker | EN 55024 |
Immunity | EN 61000-4-2 and -3, EN 61000-4-4, -4-5 and -4-6 |
LV directive | 2006/95/EC |
Electrical safety | EN 60950-1 |
National grid interface req.* | VDE 0126-1-1 / DK5940 / RD1663-2000 / K SC 8536 / G83-1 compliant |
* Depending on country settings, see section 4.3.2 |
7.2 Outline Drawings
Dimensions of the Sunmaster XS4300, XS3200, XS2000 are provided in Figure 7-1 (Height: 540 mm [21.3 in], Width: 356 mm [14.0 in], Depth: 142 mm [5.59 in]).
8 Ordering Information
The following accessories and components are available:
- Part number 130362900: Set of two Multicontact Y-adapters PV-AZS4 (positive) and PV-AZB4 (negative).
- Part number 130360700: Adapter cable (from MC1 to MC2 positive).
- Part number 130360800: Adapter cable (from MC1 to MC2 negative).
- Part number 130394000: Masterlog - Free software package to monitor your photovoltaic (PV) system using your PC or notebook. PC Link is compulsory.
- Part number 130391010: PC Link, RS485/232 converter.
- Part number 130391020: PC Link Industrial, RS485/RS232 converter for more than 10 Sunmasters or cable lengths over 100 meters.
- Part number 130391040: PC Link Industrial, RS485/USB converter for more than 10 Sunmasters or cable lengths over 100 meters.
- Part number 130397000: Data Control 'Premium' II local – Datalogger for up to 6 Sunmaster inverters locally.
- Part number 130397100: Data Control 'Premium' II remote – Datalogger for up to 6 Sunmaster inverters over the Internet.
- Part number 130397200: Data Control 'Pro' Analogue – Datalogger for up to 20 Sunmaster inverters locally or over the Internet.
- Part number 130397210: Data Control 'Pro' ISDN – Datalogger for up to 20 Sunmaster inverters locally or over the Internet.
- Part number 130397220: Data Control 'Pro' GSM – Datalogger for up to 20 Sunmaster inverters locally or over the Internet.
- Part number 130397230: Data Control 'Pro' Ethernet – Datalogger for up to 20 Sunmaster inverters locally or over the Internet.
- Part number 130010905: Modular communication cable, cross wired, 8 pole, 1 meter / 3 ft.
- Part number 130010906: Modular communication cable, cross wired, 8 pole, 5 meter / 16 ft.
- Part number 130010910: Modular communication cable, cross wired, 8 pole, 10 meter / 33 ft.
- Part number 130010915: Modular communication cable, cross wired, 8 pole, 15 meter / 49 ft.
- Part number 120107000: Complete set to assemble modular communication cables (includes 100m cable, 100 modular jacks, crimping tool).
Mastervolt offers a wide range of products for grid-connected and independent autonomous electrical installations. Visit www.mastervolt.com for more information.
9 Italy Self Test
General
The Italy Self Test verifies the upper and lower limits of the AC voltage and AC frequency at which the inverter will disconnect from the grid. This test is performed by selecting the "System/Model" menu and, if the model is ITALY, pressing the lower two buttons for 3 seconds. "ITALY TEST" will blink; press the lower right button to confirm. The test sequence includes UH (high off limit AC voltage), UL (low off limit AC voltage), FH (high off limit AC frequency), and FL (low off limit AC frequency). After each test, confirm the result. The standard reclosure time of 300 seconds is reduced to 10 seconds for testing. Test accuracy is better than 1V/0.1Hz if grid voltage and frequency are stable.
UH-test
Starts by pressing "Start". The screen shows test time, measured grid voltage (UG), and the high voltage limit (UH). During the test, UH decreases until it reaches UG, causing the inverter to disconnect and the red error LED to illuminate. After the test, TIME, UG, and UT (measured UH) are displayed. Calculation: UT = UG + (TIME * 11.5).
UL-test
Starts by pressing "Start". The screen shows test time, measured grid voltage (UG), and the low voltage limit (UL). During the test, UL increases until it reaches UG, causing the inverter to disconnect and the red error LED to illuminate. After the test, TIME, UG, and UT (measured UL) are displayed. Calculation: UT = UG – (TIME * 11.5).
FH-test
Starts by pressing "Start". The screen shows test time, measured grid frequency (FG), and the high frequency limit (FH). During the test, FH decreases until it reaches FG, causing the inverter to disconnect and the red error LED to illuminate. After the test, TIME, FG, and FT (measured FH) are displayed. Calculation: FT = FG + (TIME * 0.05).
FL-test
Starts by pressing "Start". The screen shows test time, measured grid frequency (FG), and the low frequency limit (FL). During the test, FL increases until it reaches FG, causing the inverter to disconnect and the red error LED to illuminate. After the test, TIME, FG, and FT (measured FL) are displayed. Calculation: FT = FG – (TIME * 0.05).
10 Certificates
10.1 Certificate of VDE-0126 Conformity
A Certificate of Compliance from Bureau Veritas confirms that the Mastervolt Sunmaster XS4300, XS3200, XS2000, XL3301 (automatic disconnection device) meets the requirements of DIN V VDE V 0126-1-1:2006-02 and related standards for photovoltaic systems with single-phase parallel coupling.
10.2 EC Declaration of Conformity
Mastervolt declares that the Sunmaster XS4300, XS3200, and XS2000 are CE-marked and comply with relevant standards including EMC Directive, Emission, Harmonics, Immunity, LV directive, and Electrical safety. Dated 18-10-2011.
10.3 AS4777 Certificate of Compliance
A Certificate of Compliance from Bureau Veritas confirms that the Mastervolt XS 6500, XS 4300, XS 3200, XS 2000 (automatic disconnection device) meets the requirements of AS 4777.2:2005 and AS 4777.3:2005 for grid connection of energy systems via inverters.
Contact Information
Mastervolt
Snijdersbergweg 93, 1105 AN Amsterdam, The Netherlands
Tel: +31-20-3422100
Fax: +31-20-6971006
Email: info@mastervolt.com