The GoodWe GT Series string inverter is an ideal choice for commercial and industrial (C&I) applications, designed to enhance productivity and realize high power density. With multiple MPPTs and a high input current of 21A per DC string, these inverters increase the overall yield, especially when paired with high-power PV modules. The optional PID (Potential Induced Degradation) recovery function is also supported for improved module performance. Safety is paramount, with both the DC and AC sides equipped with Type II surge protection to safeguard the inverter from lightning strikes, ensuring upgraded safety and reliability for the PV system. The GT Series inverters are engineered with an unrivaled set of features to deliver increased return on investment (ROI) for C&I PV projects.
Key Features
-
Optimal Generation for Higher Return
- 21A DC input current per string
- 8/10 MPPTs, max. Efficiency 99.0%
- 150% DC input oversizing & 110% AC output overloading
- No derating at 45°C
-
Smart Control & Monitoring
- String level monitoring
- Remote or onsite upgrade supported
-
Superb Safety & Reliability
- Type II SPD on AC & DC sides
- IP66 and optional C5 protection¹
- Optional AFCI protection
-
Friendly & Thought Design
- Lightweight design and high power density for easy installation
- Easy & quick replacement of fan
- Fuse free design
Technical Data
Parameter | GW75K-GT-LV-G10 | GW100K-GT | GW110K-GT | GW125K-GT |
---|---|---|---|---|
Input | ||||
Max. Input Voltage (V) | 800 | 1100 | 1100 | 1100 |
MPPT Operating Voltage Range (V) | 180 ~ 800 | 180~1000 | 180~1000 | 180~1000 |
Start-up Voltage (V) | 200 | 370 | 600 | 600 |
Nominal Input Voltage (V) | 600 | 600 | 600 | 600 |
Max. Input Current per MPPT (A) | 42 | 52.5 | 52.5 | 52.5 |
Max. Short Circuit Current per MPPT (A) | 45 | 55.5 | 55.5 | 55.5 |
Number of MPP Trackers | 8 | 8 | 10 | 10 |
Number of Strings per MPPT | 2 | 2 | 2 | 2 |
Output | ||||
Nominal Output Power (kW) | 75 | 100 | 110 | 125 |
Nominal Output Apparent Power (kVA) | 75 | 100 | 110 | 125 |
Max. AC Active Power (kW)*3 | 75*6 | 100*1 | 110.0*1 | 121.04 |
Max. AC Apparent Power (kVA)*3 | 75 | 100 | 110.0 | 121.04 |
Nominal Output Voltage (V) | 127/220, 3L/N/PE or 3L/PE | 220/380, 230/400, 3L / N / PE or 3L / PE | 220/380, 230/400, 3L / N / PE or 3L / PE | 220/380, 230/400, 3L / N / PE or 3L / PE |
Output Voltage Range (V) | 176~245 | 304~460 | 304~460 | 304~460 |
Nominal AC Grid Frequency (Hz) | 50/60 | 50/60 | 50/60 | 50/60 |
AC Grid Frequency Range (Hz) | 45~55/55~65 | 45~55/55~65 | 45~55/55~65 | 45~55/55~65 |
Max. Output Current (A)5 | 167.1 | 183.4 | 199.4 | 199.4 |
Power Factor | ~1 (Adjustable from 0.8 leading to 0.8 lagging) | ~1 (Adjustable from 0.8 leading to 0.8 lagging) | ~1 (Adjustable from 0.8 leading to 0.8 lagging) | ~1 (Adjustable from 0.8 leading to 0.8 lagging) |
Max. Total Harmonic Distortion | <3% | <3% | <3% | <3% |
Efficiency | ||||
Max. Efficiency | 98.8% | 98.8% | 98.8% | 98.8% |
European Efficiency | 98.3% | 98.4% | 98.4% | 98.5% |
Protection | ||||
PV String Current Monitoring | Integrated | |||
PV Insulation Resistance Detection | Integrated | |||
Residual Current Monitoring | Integrated | |||
PV Reverse Polarity Protection | Integrated | |||
Anti-islanding Protection | Integrated | |||
AC Overcurrent Protection | Integrated | |||
AC Short Circuit Protection | Integrated | |||
AC Overvoltage Protection | Integrated | |||
DC Switch | Integrated | Integrated | Integrated | Integrated |
DC Surge Protection | Type II | Type II (Type I + II Optional) | Type II (Type I + II Optional) | Type II (Type I + II Optional) |
AC Surge Protection | Type II | Type II | Type II | Type II |
AFCI | Optional*8 | Optional | Optional | Optional |
Emergency Power Off | Optional | Optional | Optional | Optional |
Rapid Shutdown | Optional | Optional | Optional | Optional |
Remote Shutdown | Integrated | Optional | Optional | Optional |
PID Recovery | Optional | Optional | Optional | Optional |
Reactive Power Compensation at Night | Optional | Optional | Optional | Optional |
Power Supply at Night | Optional | Optional | Optional | Optional |
General Data | ||||
Operating Temperature Range (°C) | -30~+60 | |||
Relative Humidity | 0~100% | |||
Max. Operating Altitude (m) | 4000 | |||
Cooling Method | Smart Fan Cooling | |||
User Interface | LED, LCD (Optional), WLAN + APP | LED, LCD (Optional), WLAN + APP | LED, LCD (Optional), WLAN + APP | LED, LCD (Optional), WLAN + APP |
Communication | RS485, WiFi + LAN | RS485, WiFi + LAN or 4G or PLC (Optional) | RS485, WiFi + LAN or 4G or PLC (Optional) | RS485, WiFi + LAN or 4G or PLC (Optional) |
Communication Protocols | Modbus-RTU (SunSpec Compliant) | |||
Weight (kg) | 88 | 88 | 88 | 930 x 650 x 300 |
Dimension (W x H x D mm) | 930 x 650 x 300 | 930 x 650 x 300 | 930 x 650 x 300 | 930 x 650 x 300 |
Topology | Non-isolated | |||
Self-consumption at Night (W) | <1 | <2 | <2 | <2 |
Ingress Protection Rating | IP66 | |||
DC Connector | MC4 (4~6mm²) | |||
AC Connector | OT/DT terminal (Max. 240mm²) |
¹ Optional functions or devices are purchased separately.
*1: For Australia is 99.99kW/KVA.
*2: For VDE4105 Max. AC Active Power (kW) and Max. AC Apparent Power (kVA): GW125K-GT is 134.9.
*3: For Chile and Brazil Max. AC Active Power (kW) and Max. AC Apparent Power (kVA): GW100K-GT is 100; GW110K-GT is 110; GW125K-GT is 125.
*4: For Australia is 110kW / kVA.
*5: For Australia Max. Output Current (A): GW100K-GT is 145, GW110K-GT is 159.5.
*6: For Colombia Max. AC Active Power (kW): GW75K-GT-LV-G10 is 70.9@208V.
*7: For Colombia Nominal Output Voltage (V): GW75K-GT-LV-G10 is 120 / 208, 3L/N/PE or 3L / PE.
*8: For Brazil and Colombia is Integrated.
* Please visit GoodWe website for the latest certificates.
* All pictures shown are for reference only. Actual appearance may vary.
Contact Information - India
Service: +91 93558 86166 | Service.in@goodwe.com
Sales: Sales.india@goodwe.com
Landing page: https://en.goodwe.com/india