Introduction
The OneControl® Touch Panel (OCTP), formerly known as MyRV®, is a touchscreen device designed for controlling and monitoring various systems within a recreational vehicle. These systems include slide-outs, leveling systems, awnings, lighting, temperature, water tanks, tire pressure, and battery levels, provided they are installed and programmed into the OneControl system. Powering up the vehicle unit also powers the OneControl Touch Panel and associated controllers.
For additional support, visit: https://support.lci1.com/onecontrol-wireless-formerly-myrv.
NOTE: Images in this document are for reference only. Actual parts and assemblies may differ from those shown.
Compatibility
This thermostat control is compatible with the following appliances:
- Single-stage LP gas furnaces with self-contained fan control.
- Conventional air conditioning systems with one or two-speed fans.
- Combination air conditioning/heat pump systems with one or two-speed fans.
Specifications
Specification | Min | Typ | Max | Units |
---|---|---|---|---|
Operating Supply Voltage | 9 | 13.8 | 18 | Volts DC |
Operating Temperature Range | -10 (14) | N/A | +45 (113) | C (F) |
Quiescent Current | N/A | 30 | 45 | mA DC |
Sink Current (Generator) | N/A | 1.2 | 2.0 | A DC |
Focused Relay Drive Current | N/A | N/A | 1.5 | A DC |
HVAC Control System Capabilities Switch
The HVAC control system features a "capabilities" switch that must be set to match the attached equipment. The switch settings are as follows:
Switch Function | When "OFF" | When "ON" | Note |
---|---|---|---|
Dual-Speed Fan | Fan is high-speed only | Fan has a low-speed wire | N/A |
Heat Pump (HP) | System (if present) A/C only | Rooftop A/C System includes HP | Orange wire |
Air Conditioning | No A/C system in this zone | This zone has A/C | HP setting ignored |
LP Gas Heat | No gas furnace installed | Gas furnace installed | Furnace has own fan |
Safety
Read and understand all instructions before installing or operating this product. Adhere to all safety labels.
This manual provides general instructions. Many variables can affect installation complexity and operation. Failure to correctly follow the provided instructions may result in death, serious personal injury, severe product and/or property damage, including voiding of the Lippert limited warranty.
⚠️ WARNING: Ensure that power is properly disconnected at the supply (mains and/or battery). Failure to do so may result in damage to the product and personal injury or death.
⚠️ WARNING: Failure to follow the instructions provided in this manual may result in death, serious injury, unit damage, or voiding of the component warranty.
⚠️ WARNING: This thermostat control device requires 12V direct current (DC) and cannot operate from alternating current (AC) sources. Confirm that your furnace or air conditioning unit supplies 12V DC to the zone wiring harness before proceeding. Connecting the thermostat to AC will cause irreparable damage and void the warranty.
⚠️ CAUTION: Ground connections need to be tied together for ALL heating and cooling appliances in a zone.
NOTE: The thermostat module requires 12V DC power from two separate sources:
- Power from the house battery should be applied via the main power input connector (PWR).
- Each active climate zone HVAC unit will supply its own power to its corresponding thermostat zone connector.
Resources Required
- Cordless or electric drill or screw gun
- Appropriate drill bits
- Appropriate drive bits
- Tape measure
- Phillips head screwdriver
Preparation
Prior to Installation
NOTE: Ensure the control capabilities have been configured before the HVAC controller is mounted.
NOTE: The HVAC controller should be mounted in close proximity to any other OneControl controllers. All thermostat control leads should be run from the heating and cooling appliances to this centralized location.
Connections
1. Select configuration for each zone using the DIP switches in the top left corner of the controller (Fig. 1). Each zone has four switches:
- A. Dual-Speed Fan
- B. Heat Pump
- C. Air Conditioning
- D. LP Gas Heat
NOTE: All switches are in the "ON" position from the factory. Move the switch to the left for any function not used in each zone. For example, a zone with an air conditioner, dual speed fan, and LP gas heat would be:
- A. Dual-Speed Fan "ON"
- B. Heat Pump "OFF"
- C. Air Conditioning "ON"
- D. LP Gas Heat "ON"
Installation
The HVAC controller is a CAN bus network enabled module that integrates up to three zones of HVAC, plus a generator with hour meter and auto-start, with the OneControl system. Each zone can control one A/C or heat pump, one gas furnace, and one fan (single or dual speed). Each zone uses its own temperature sensor instead of a traditional thermostat.
Controller
1. Mount either the HVAC dual zone controller (Fig. 1) or triple zone controller (Fig. 2) by securing it to a solid surface with #8 x 1" wood screws or equivalent through each of the six mounting holes (Fig. 1A, 2A).
Figure 1 & 2 Description: These figures show the Lippert HVAC Dual-Zone Control (model 406350) and the Lippert MyRV HVAC V2 Triple-Zone Control (model 709169) boards. They illustrate the DIP switches for configuration and various connectors labeled for HVAC harness, CAN bus, Generator, and Zone inputs (Zone 1, Zone 2, Zone 3).
Controller Installation Steps
2. Connect to DC 12V power using the main power harness (Fig. 3).
Figure 3 Description: This figure shows a 12V DC power harness with a red and black wire, terminating in a connector.
NOTE: The controller draws a low amount of current. Power and ground can be obtained from another nearby module.
3. Using the 6-pin wire harness and wire diagram, connect the outputs from the controller to the appropriate inputs on the air conditioning, heat pump, or furnace (referencing Fig. 1D, 1E on the controller diagrams). Perform this for each zone used.
NOTE: If utilizing both zone connections on a dual-zone controller, label the zone harnesses as "Zone1" or "Zone2" to prevent accidental swapping. Use "Zone3" for triple zone controllers.
4. Connect both CAN bus cables (Fig. 4) from the CAN ports on the controller (Fig. 1B, 1C) to link the module into the CAN network.
Figure 4 Description: This figure shows a coiled CAN bus cable with connectors on both ends.
NOTE: Heat pump systems must have a single-wire "heat demand" configuration. The controller does not support independent contacts for the heat pump reversing valve; it drives a single lead for heat pump demand, similar to the gas furnace demand.
NOTE: Coleman Mach systems implement this scheme in Analog Control Box setups. Ensure the installed system complies with this setup.
Harness Connections
Generator connections to the HVAC thermostat control (Fig. 5A, 6A) are made via the 6-pin connector (Fig. 5B, 6B). When wired into the generator's "running signal", the system tracks total generator running hours and can display an alert for scheduled maintenance.
NOTE: The controller implements an automatic priming cycle at the beginning of the startup sequence. A solenoid priming click will be heard a few seconds before the generator engine starts.
Figure 5 & 6 Description: These figures illustrate all harness connections to the dual-zone (Fig. 5) and triple-zone (Fig. 6) controllers. They show the location of the HVAC harness, CAN bus ports, PWR connector, and Zone connectors (Zone 1, Zone 2, Zone 3), along with generator harness connections and color codes for various signals.
1. Connect 12V DC power and ground (Fig. 5C, 6C).
2. Connect CANBUS data wires (Fig. 5D, 6D) in the proper sequence with other OneControl system components.
3. Wire the harness to Zone 1 on the controller (Fig. 5E, 6E), Zone 2 (Fig. 5F, 6F), and Zone 3 (Fig. 6G), connecting to the OneControl system's designated zone.
Zone Sensor Installation
The OneControl Zone Sensor Kit includes a sensor with a cable, a cable hold-down clamp, and a sensor cover. A sensor must be installed in each climate zone to be controlled.
Each climate zone requires at least one temperature sensor connected between the blue with stripe "Sensor Power" lead and the blue "Zone Temperature Input" lead. The zone sensor should be installed on an interior wall, ideally between 54" and 66" above the floor.
⚠️ WARNING: Disconnect all power sources and the HVAC controller power connections before installing the zone sensor. Failure to do so may result in serious personal injury from electric shock.
Location Selection
NOTE: Select a sensor location carefully to ensure proper operation of the OneControl HVAC control system. Use these guidelines:
- A. Mount the sensor at least 54" but no higher than 66" above floor height.
- B. Install the zone sensor on an interior wall. Avoid installation on outside walls.
NOTE: Do not mount the sensor in close proximity (less than 36") to direct heat or cold-air sources. Avoid locations near outside doors, windows, or corners of outside walls. Avoid areas with poor air circulation, such as under cupboards or above appliances.
Running the Zone Sensor Wire
A. The zone sensor wire must connect to the HVAC controller.
B. Using a drill and a 3/8" bit, drill a hole in the wall where the sensor will be mounted.
C. Insert the wire through the drilled hole.
D. Secure the sensor to the wall using a "P-clip" (Fig. 7) and a #8 pan head screw.
3. Cover the sensor, "P-clip", and the hole with a plastic thermistor cover (Fig. 8).
4. Secure the cover with two #4 screws.
5. Connect the zone sensor wire between the blue/white stripe sensor power lead and the blue zone temperature input lead on the pigtail harness (Fig. 5B, 6B).
Figure 7 & 8 Description: Figure 7 shows a "P-clip" used for mounting the sensor. Figure 8 shows the plastic thermistor cover that conceals the sensor and mounting hardware.
Operation
⚠️ CAUTION: Adhere to all local and national codes. Disconnect all external A/C power to the unit before installing, removing, or cleaning.
All user control and input is accomplished using the OneControl mobile application, OneControl tablet, or OneControl Touch Panel (OCTP). When using the HVAC system, controls typically found on a thermostat are located within the HVAC icon on the OneControl Touch Panel.
Power On/Off
1. The device can be powered on or off using the button on the front of the device (Fig. 9).
NOTE: It will take a few moments for the system to start up and load.
Figure 9 Description: This figure shows the OneControl Touch Panel device with the Lippert logo and a power/reset button.
2. To enter or exit sleep mode, press and release the power button.
Touch Panel
1. Locate the "OneControl" control panel (Fig. 10).
2. Press the icon of the system you wish to operate.
3. Push the system "Home" button (Fig. 10A) to return to the OneControl home screen.
NOTE: The touch panel displays icons representing devices currently connected to the "OneControl" system (Fig. 11) via CAN bus.
Figure 10 Description: This figure shows the OneControl home screen with icons for "MyRV", "Generator", and "OneControl".
Figure 11 Description: This figure shows the OneControl system screen with icons for various RV functions including "Doors", "Fan", "Generator", "HVAC", "Landing Gear", "Lighting", "Monitor Panel", and "Slides".
Adjusting HVAC Control
1. From the touch panel home screen, select the HVAC icon to open the app (Fig. 12A).
2. In the HVAC menu screen, select the Climate Zone you wish to adjust (Fig. 13).
3. On the left side of the screen (Fig. 14), there are two boxes: the top box controls the heating/cooling mode, and the bottom box controls the fan.
Figure 12 Description: This figure shows the OneControl home screen with the "HVAC" icon highlighted.
Figure 13 Description: This figure shows the HVAC menu with options to select a climate zone, such as "Bedroom Climate Zone" and "Main Climate Zone", and shows mode and fan settings.
Figure 14 Description: This figure shows the Climate HVAC Mode selection screen. The top box allows selection of "Heat/Cool", "Heat", "Cool", or "Off". The bottom box controls fan settings.
A. Press the top box to choose the HVAC mode. A selection box will appear with available options:
- Heat/Cool: Select a high and low set point; the HVAC system will maintain the temperature between these points.
- Heat: Select a desired set point; the furnace or heat pump will operate to maintain that temperature. If a heat pump is equipped, you will be prompted to choose between gas or heat pump as the heat source.
- Cool: Select a desired set point; the A/C will operate to maintain that temperature.
- Off: This setting turns the HVAC system off completely.
B. Once the desired mode is selected, press the "Close" button (Fig. 14A).
C. Press the bottom box to access fan settings (Fig. 15). A selection box will appear with available options:
- High: The high fan runs continuously until another setting is chosen.
- Low: The low fan runs continuously until another setting is chosen.
- Auto: The fan runs when the HVAC system calls for heating or cooling and shuts off after the set point is reached.
NOTE: The fan will continue to run for two minutes after the set-point has been reached to cool the compressor/furnace.
D. After selecting the desired fan setting, press the "Close" button (Fig. 15A).
Figure 15 Description: This figure shows the Climate Fan Mode selection screen with options for "High", "Low", and "Auto" fan speeds.
4. In the center of the screen, a temperature is displayed with a radius around it (Fig. 16). A white circle on this radius is used to adjust the set-point:
- A. Press and hold the white circle to drag it around the radius. Clockwise rotation raises the set temperature; counterclockwise rotation lowers it.
- B. Release the finger from the white circle once the desired set-point is reached.
NOTE: In "Heat/Cool" mode, there will be two white circles (Fig. 17). The left circle sets the low end of the temperature range, and the right circle sets the high end.
5. To the right of the set temperature, the system status is displayed (e.g., "currently 78° F cooling", "currently 65° F heating with gas", "currently 72° F idle").
Figure 16 Description: This figure shows the temperature adjustment interface for a single climate zone, displaying the current temperature (e.g., 68° F) and mode (Cool), with a circular slider for set-point adjustment.
Figure 17 Description: This figure shows the temperature adjustment interface for "Heat/Cool" mode, displaying the temperature range (e.g., 65-72° F) with two circular sliders for low and high set-point adjustment.
Wiring Diagram
The following wiring diagrams illustrate possible appliance connections, depending on the OEM installed controller.
OneControl® HVAC Triple Zone Wiring Diagram
For: Furnace, A/C, Heat Pump, Dual Speed Fan
Figure 18 Description: This is a schematic wiring diagram for the OneControl Triple Zone Controller (715845). It shows connections from the Breaker Box to the controller's Zone Connector, including AC Hot, AC Neut, 12V to Zone, Compressor, Rev. Valve, High Fan, Low Fan, Heat Demand, LP Gas Supply, and Ground. It also shows optional Generator and Zone T Sense connections. A table lists the wire colors, signals, and corresponding Zone Connector pin numbers.
Color | Signal | Zone Connect |
---|---|---|
Red | Common | 6 |
White | Gas Heat | 2 |
Green | High Fan | 8 |
Yellow | Compressor | 3 |
Orange | Rev. Valve | 4 |
Gray | Low Fan | 7 |
Blue | Zone Temp Input | 1 |
Blue w/stripe | Sensor Power | 5 |
OEM installers should connect the red common wire to 12V+ or 12V- (ground) depending on the AC unit manufacturer.
OneControl® HVAC Dual Zone Wiring Diagram
For: Furnace, A/C, Heat Pump, Dual Speed Fan
Figure 19 Description: This is a schematic wiring diagram for the OneControl Dual Zone Controller (406350). It shows connections from the Breaker Box to the controller's Zone Connector, including Gnd, Zone Power (+12V DC), Gas Heat, High Fan, Compressor, Rev. Valve, Low Fan, Reserved, Zone Temp Input, Freeze Detect Input, and Sensor Power. It also shows optional Generator and Zone T Sense connections. A table lists the wire colors, signals, and corresponding Zone Connector pin numbers.
Color | Signal | Zone Connect |
---|---|---|
Brown | Gnd | 1 |
Red | Zone Power (+12V DC) | 7 |
White | Gas Heat | 2 |
Green | High Fan | 8 |
Yellow | Compressor | 3 |
Orange | Rev. Valve | 9 |
Gray | Low Fan | 4 |
Pink | Reserved | 10 |
Blue | Zone Temp Input | 5 |
Purple | Freeze Detect Input | 11 |
Blue w/ stripe | Sensor Power | 6 |
Purple w/stripe | Sensor Power | 12 |
Notes
This section is intended for user notes.
Contact Information & Copyright
The contents of this manual are proprietary and copyright protected by Lippert. Copying or dissemination of portions of this manual requires prior written consent from an authorized Lippert representative. Unauthorized use voids any applicable warranty. Information is subject to change without notice at Lippert's discretion. Revised editions are available for free download from lippert.com.
Please recycle obsolete materials.
For concerns or questions, please contact Lippert:
- Phone: 432-LIPPERT (432-547-7378)
- Web: lippert.com
- Email: customerservice@lci1.com