Installation Instructions: Air-Fi® Wireless Communications Interface (WCI)

Model Numbers

X13790901, X13790902, X13790903, X13790904, X13790941, X13790963, X13790964

Notes:

Models X13790901, X13790902, X13790903, X13790904, and X13790963 are intended for installation in accordance with manufacturer instructions, NEC/CEC Part 1, and local authority jurisdiction. Suitable for plenum use.

Safety Warnings

WARNING: Only qualified personnel should install and service the equipment. Installation, startup, and servicing of HVAC equipment can be hazardous and requires specific knowledge and training. Improper installation, adjustment, or alteration by unqualified persons could result in death or serious injury. Observe all precautions in literature and on equipment tags.

Warnings, Cautions, and Notices

Read this manual thoroughly before operating or servicing. Safety advisories are provided throughout. Personal safety and proper operation depend on strict observance of precautions.

WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

CAUTION: Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. May also alert against unsafe practices.

NOTICE: Indicates a situation that could result in equipment or property-damage only accidents.

Important Environmental Concerns

Discusses the impact of certain man-made chemicals (CFCs, HCFCs) on the stratospheric ozone layer and Trane's advocacy for responsible refrigerant handling.

Important Responsible Refrigerant Practices

Emphasizes the importance of responsible refrigerant practices for the environment, customers, and the industry. Technicians must be certified. References US Federal Clean Air Act (Section 608) and potential state/municipal requirements.

Proper Field Wiring and Grounding Required!

WARNING: Failure to follow code could result in death or serious injury. All field wiring must be performed by qualified personnel. Improperly installed and grounded wiring poses FIRE and ELECTROCUTION hazards. Follow NEC and local/state/national electrical codes.

Personal Protective Equipment (PPE) Required!

WARNING: Failure to wear proper PPE can result in death or serious injury. Technicians must use PPE for electrical, mechanical, and chemical hazards as per manual, tags, and instructions. This includes cut-resistant gloves, safety glasses, hard hats, fall protection, electrical PPE, and arc flash clothing. Refer to SDS and OSHA guidelines. For hazardous chemicals, consult SDS and OSHA/GHS guidelines. For electrical hazards, use PPE per OSHA, NFPA 70E, or country-specific requirements before servicing. NEVER perform switching, disconnecting, or voltage testing without proper PPE and arc flash clothing. Ensure meters are properly rated.

Follow EHS Policies!

WARNING: Failure to follow instructions can result in death or serious injury. Trane personnel must follow company EHS policies (hot work, electrical, fall protection, lockout/tagout, refrigerant handling). Local regulations supersede if more stringent. Non-Trane personnel should always follow local regulations.

Copyright and Trademarks

This document is the property of Trane and may not be reproduced without written permission. Trane reserves the right to revise content without notice. All referenced trademarks belong to their respective owners.

Revision History

Updated model numbers and notes information on the front cover.

Set Addresses

For detailed information and procedures, refer to:

Connecting the Wiring Harness to the WCI

Power OFF Device

WARNING: Hazardous Voltage! Failure to disconnect power before servicing could result in death or serious injury. Disconnect all electric power, including remote disconnects. Follow proper lockout/tagout procedures. Verify no power is present with a voltmeter.

Wire identification:

Diagram Description: A diagram illustrates the wiring harness connections to the WCI, showing the color coding for LINK-, LINK+, +24VDC/VAC, and Ground/Common.

Connect WCI Wires to Controller

Use a PM014 with Tracer SC with 1 or more wireless networks, or Tracer SC+ when needed to stay within IMC power budget.

Wiring to IMC Terminals: Connect both 2-connector screw terminal blocks to either of the IMC terminals on the PM104.

Diagram Description: Multiple wiring diagrams illustrate connections between the WCI and various controllers and modules, including:

Power ON Device and Network Formation

Identifying the Network Coordinator (One per Network) and Initiating Network Formation

Scenario 1: Tracer® SC/SC+ is present when WCI is powered:

  1. The WCI wired to Tracer SC/SC+ becomes the network coordinator.
  2. Network formation is initiated, and the network automatically opens for 60 minutes.
  3. LEDs on the coordinator illuminate as described in Table 1.

Scenario 2: No Tracer® SC/SC+ is present when WCI is powered:

  1. Identify a centrally located WCI to be the network coordinator.
  2. Manually open the network by pressing the START/JOIN button for 5 seconds on the chosen WCI.
  3. The WCI becomes the network coordinator, and network formation is initiated.
  4. Observe the LEDs on the network coordinator (see Table 1).

Diagram Description: A diagram shows a WCI with "Press START/JOIN for 5 seconds" indicated, leading to the WCI becoming a coordinator with NWK, CRD, and OPEN NET LEDs illuminated steadily. Another diagram shows multiple WCIs connecting to controllers, with the NWK LED illuminating on each WCI that joins the network.

The Network Forms: The NWK LED illuminates on every WCI that joins the network.

Notes:

LED Identification and Interpretation

Table 1. LED identification and interpretation

LEDLED ActivityIndicates
Network LED (green) NWKOn solidWCI is a network member
Flashes for 10 seconds every 2.5 minutes.WCI is not a member of a network. The WCI will join a network when the NWK LED is flashing. If an open network with matching rotary settings is found, the WCI joins, and the NWK and OPEN LEDs turn solid.
Coordinator LED (yellow) CRDOn solidWCI is network coordinator
Open Net LED (yellow) OPEN NETOn solidNetwork is open for joining
OffNetwork is closed for joining
Reception LED (yellow) RX LINKFlashes(a)Data received
On(b)Data received
Off(c)No data received
Transmission LED (green) TX LINKFlashes(a)Data transmitted
On(b)Data transmitted
Off(c)No data transmitted
Diagnostic LED (red) DIAG(d)OffNormal operation
Flashes (½ second on, ½ second off repeating)Hardware failure or failed re-flash of a radio. Corrective action: Replace WCI.
Triple flash patternFailed to join network. Occurs for 30 seconds after failing to join. Continues until successful join. Corrective Action: Ensure network is formed and open, allow time for WCI to join.
Double flash patternNormal for a repeater. WCI lost IMC communication to the UC/BCI/Tracer® SC/SC+. Corrective action: Check IMC wiring, cycle power to controller/WCI. WCI was not configured correctly (e.g., missing BACnet ID or rotary address). Corrective Action: Cycle power to controller/WCI.
Power LED (green) PWROn solidWCI has power.
OffWCI does not have power. Corrective Action: Check WCI power wiring for 24v DC or AC.

(a) LED flashes steadily (approx. 3 flashes per second) on WCIs built before 2019.

(b) LED appears steady for WCIs built 2019 and after; may appear dim and flicker occasionally with data traffic.

(c) LED is off for all WCIs.

(d) If multiple conditions are present, priority is in the listed order.

Firmware Requirements for Devices in an Air-Fi® Wireless Network

This table lists the minimum firmware levels required for devices to participate in an Air-Fi Wireless network.

Table 2. Minimum firmware levels required

DeviceOne or no WCSsMultiple WCS-SB, or -SD and/or an RH sensor module (WCS-SH)WCS-SO/SCO2WCS-SB/R
Tracer® SCv3.6.xxxN/AN/AN/A
UC210All versionsv2.00.xxx.modv3.0v3.0
UC400v6.00.xxx.modv8.00.xxx.modv9.0v9.0
UC600v4.00.xxx.modv5.00.xxx.modv6.0v6.0
BCI-Iv25.00.xxx.modv28.00.xxx.modNot supported(a)Not supported
BCI-Rv5.02.xxx.modv6.00.xxx.modv7.0Not supported
RTRMv12 or higher (requires physical board replacement)N/AN/AN/A
Tracer® TUv8.2v8.6v9.3v9.3
TU Adapterv1.00.xxx.modN/AN/AN/A
WCIv1.00.000.modv2.00.000.modv2.01.004.modv2.01.004.mod
Tracer® SC+v5.1v5.1v5.1v5.1
BCI2-IAll versionsAll versionsNot supported(a)Not supported
BCI2-RAll versionsAll versionsAll versionsNot supported
BCI2-CN/AN/AN/AN/A
Symbio™ 210/210eAll versionsAll versionsAll versionsAll versions
Symbio™ 400-B/500All versionsAll versionsAll versionsAll versions
Symbio™ 700All versionsAll versionsAll versionsAll versions
Symbio™ 800All versionsAll versionsAll versionsAll versions

(a) The WCS-SO/SCO2 sensor can be installed in another controller in the building and referenced to BCI-I/BCI2-I.

Note: If all devices cannot be powered on simultaneously, power them on in the following order: 1. All WCIs 2. All Tracer® SCs 3. All Controllers 4. All WCSs.

Models: X13790901, X13790902, X13790903, X13790904, X13790941, X13790963, X13790964, X13790 Series Air-Fi Wireless Communications Interface, X13790 Series, Air-Fi Wireless Communications Interface, Wireless Communications Interface, Communications Interface, Interface

File Info : application/pdf, 2 Pages, 2.60MB

PDF preview unavailable. Download the PDF instead.

BAS-SVN038F-EN 09152024

References

Acrobat Distiller 24.0 (Windows)

Related Documents

Preview Trane Air-Fi Wireless System: Installation, Operation, and Maintenance Guide
Comprehensive guide for the Trane Air-Fi Wireless System, covering installation, operation, and maintenance of the Air-Fi Wireless Communications Interface (WCI) and Air-Fi Wireless Communications Sensors (WCS). Learn about device compatibility, network setup, security, and troubleshooting.
Preview Trane Air-Fi™ Wireless Communications Sensor (WCS) Quick Reference Guide
This guide provides quick reference information for the Trane Air-Fi™ Wireless Communications Sensor (WCS), detailing how to adjust room temperature, system settings, fan speed, manage occupancy, and understand error codes. It includes safety warnings and battery life indicators.
Preview Trane Symbio 700 Controller Application Guide for Precedent Rooftop Air-Conditioners
This application guide provides detailed information on the Trane Symbio 700 controller for Precedent packaged rooftop air-conditioners, covering configuration, control capabilities, and troubleshooting.
Preview Trane Tracer SC+ System Controller and Tracer Synchrony User Interface Product Catalog
A comprehensive product catalog detailing the Trane Tracer SC+ System Controller and its associated Tracer Synchrony User Interface. This catalog covers system architecture, user interface navigation, system control applications, unit control options, hardware components, and specifications. It highlights features such as energy savings, remote access, and support for open protocols like BACnet and LonTalk.
Preview Trane Air-Fi™ Wireless Communications Sensor (WCS-SD-SB) Installation Guide
Detailed installation instructions for the Trane Air-Fi™ Wireless Communications Sensor (WCS-SD-SB), covering setup, addressing, network configuration, error codes, and signal testing for HVAC systems.
Preview Trane Symbio 800 Integration Guide: BACnet and Modbus
This guide provides detailed instructions for integrating Trane Symbio 800 controllers with BACnet and Modbus protocols. It covers communication setup, configuration parameters for both protocols, points lists, arbitration logic, and controller layout, aimed at system integrators and controls contractors.
Preview Trane Symbio 500 Programmable Controller Installation Guide
Comprehensive installation instructions for the Trane Symbio 500 Programmable Controller, covering safety warnings, wiring requirements, mounting, and startup procedures.
Preview Trane BACnet Communication Interface (BCI2-I) Integration Guide for IntelliPak
This integration guide from Trane provides detailed information on configuring and using the BACnet Communication Interface (BCI2-I) with IntelliPak and Commercial Self-Contained HVAC systems. Learn about BACnet protocols, service tools, and device management.