Installation Guide for Danfoss models including: FC-321P75KT5P20H2XGCXXXSXXXXAXBXCXXXXDX, FC 321 Automation Drive, FC 321, Automation Drive, Drive
File Info : application/pdf, 37 Pages, 964.27KB
DocumentDocumentInstallation Guide VLT®AutomationDrive EZ FC 321 0.33200 hp vlt-drives.danfoss.com VLT®AutomationDrive EZ FC 321 Installation Guide Overview 1 Overview 1.1 Safety and Installation Awareness Before starting installation, get familiarized with all safety guidelines and precautions in this guide. Additional resources - including the VLT® Safe Torque Off Operating Guide for VLT® AutomationDrive EZ FC 321, the Programming Guide, and the Application Guide - can be downloaded at www.danfoss.com/service-and-support. 1.2 Tools Needed The following tools are required for installing the VLT® AutomationDrive EZ FC 321. · Lifting aids to place the unit into position. · Drill with 10 mm and 12 mm drill bits. · Tape measurer. · Torx, Phillips, and slotted screwdrivers (T15, T20, T25, T30, T50, PZ1, SL1, and SL2). · Wrench with extensions and 717 mm sockets. · Wire crimper. · Sheet metal punch and/or pliers for cable entry plate. 1.3 Items Supplied Items supplied vary according to product configuration. · Make sure that the items supplied and the information on the nameplate correspond to the order confirmation. · Check the packaging and the drive visually for damage caused by inappropriate handling during shipment. File any claim for damages with the carrier. Retain damaged parts for clarification. e30bj018.10 VLT R Automation Drive 1 3 2 T/C: FC-321P75KT5P20H2XGCXXXSXXXXAXBXCXXXXDX 4 P/N: 134G6302 S/N: 999999G999 55 kW / 75 kW; 75 kW / 90 kW (NO) 5 IN: 3x380-500V 50/60Hz 87/86A; 161/145A (NO) 6 OUT: 3x0-Vin 0-590Hz 87/83A; 105/100A (NO) Chassis/IP20 Tamb. 50oC /122 oF 7 Danfoss A/S 6430 Nordborg Denmark www.danfoss.com 8 MADE IN USA 76 X1 E134261 IND. CONT. EQ. R US LISTED UL Voltage 525-600 V 9 DANGER See manual for special condition/mains fuse voir manual de conditions speciales/fusibles ` 15 min. 10 Illustration 1: Nameplate Example 2 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide Overview 1 Type code 6 Output voltage, frequency, and current (at low/high 2 Code number voltages) 3 Serial number 7 Enclosure size and IP rating 4 Power rating 8 Maximum ambient temperature 9 Certifications 5 Input voltage, frequency, and current (at low/high voltages) 10 Discharge time (Warning) NOTICE Do not remove the nameplate from the drive (loss of warranty). Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 3 VLT®AutomationDrive EZ FC 321 Installation Guide Safety Instructions 2 Safety Instructions 2.1 Overview This Safety chapter only relates to installing the drive. When programming or operating the drive, refer to the Application Guide or Programming Guide for applicable safety instructions. To install this product safely: · Check that the content of the delivery is correct and complete. · Never install or start up damaged units. File a complaint immediately to the shipping company, if you receive a damaged unit. · Follow the instructions provided in this installation guide. · Make sure that all personnel working on or with the drive have read and understood this guide and any additional product manuals. Contact Danfoss if you are unclear of the given information, or if you are missing information. 2.2 Target Group and Necessary Qualifications Correct and reliable transport, storage, installation, operation, and maintenance are required for the trouble-free and safe operation of the drive. Only skilled personnel are allowed to perform all related activities for these tasks. Skilled personnel are defined as properly trained staff, who are familiar with and authorized to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Also, the skilled personnel must be familiar with the instructions and safety measures described in this manual and the other product-specific manuals. If you are not a skilled electrician, do not perform any electrical installation, and troubleshooting activities. 2.3 Safety Symbols The following symbols are used in this manual: DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE Indicates information considered important, but not hazard-related (for example, messages relating to property damage). 2.4 General Safety Precautions For US and Canadian markets: NOTE! Download the English and French product guides with applicable safety, warning and caution information from https:// www.danfoss.com/en/service-and-support/. REMARQUE Vous pouvez télécharger les versions anglaise et française des guides produit contenant l'ensemble des informations de sécurité, avertissements et mises en garde applicables sur le site https://www.danfoss.com/en/service-and-support/. WARNING LACK OF SAFETY AWARENESS This document gives important information on how to prevent injury and damage to the equipment or the system. Ignoring them can lead to death, serious injury, or severe damage to the equipment. - Make sure to fully understand the dangers and safety measures incurred in the application. 4 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide Safety Instructions WARNING HAZARDOUS VOLTAGE AC drives contain hazardous voltage when connected to the AC mains or connected on the DC terminals. Failure to perform installation, start-up, and maintenance by skilled personnel can result in death or serious injury. - Only skilled personnel must perform installation, start-up, and maintenance. WARNING DISCHARGE TIME The drive contains DC-link capacitors, which can remain charged even when the drive is not powered. High voltage can be present even when the warning indicator lights are off. Failure to wait the specified time after power has been removed before performing service or repair work can result in death or serious injury. - Stop the motor. - Disconnect AC mains, permanent magnet type motors, and remote DC-link supplies, including battery back-ups, UPS, and DC-link connections to other drives. - Wait for the time specified in the Discharge Time tables for the capacitors to discharge fully before performing any service or repair work. - Measure the voltage level to verify full discharge. Table 1: Discharge Time Voltage [V] 200240 380500 525600 525690 Minimum waiting time (minutes) 4 15 [hp] 0.345.0 7.550 1.010 15100 1.010 15100 20 60100 125200 125200 WARNING UNINTENDED START When the drive is connected to the AC mains, DC supply, or load sharing, the motor may start at any time, causing risk of death, serious injury, and equipment or property damage. The motor may start by activation of an external switch, a fieldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up software, or after a cleared fault condition. - Press [Off] on the LCP before programming parameters. - Disconnect the drive from the mains whenever personal safety considerations make it necessary to avoid unintended motor start. - Check that the drive, motor, and any driven equipment are in operational readiness. CAUTION INTERNAL FAILURE HAZARD An internal failure in the drive can result in serious injury when the drive is not properly closed. - Ensure that all safety covers are in place and securely fastened before applying power. Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 5 VLT®AutomationDrive EZ FC 321 Installation Guide Safety Instructions CAUTION HOT SURFACES The drive contains metal components that are still hot even after the drive has been powered off. Failure to observe the high temperature symbol (yellow triangle) on the drive can result in serious burns. - Be aware that internal components, such as busbars, may be extremely hot even after the drive has been powered off. - Do not touch exterior areas that are marked by the high temperature symbol (yellow triangle). These areas are hot while the drive is in use and immediately after being powered off. 2.5 Lifting the Drive NOTICE LIFTING HEAVY LOAD The weight of the drive is heavy and failure to follow local safety regulations for lifting heavy weights may cause death, personal injury, or property damage. - Ensure that the lifting equipment is in proper working condition. - Check the weight of the drive and verify that the lifting equipment can safely lift the weight. - Always lift the drive using a lifting bar inserted into the lifting eyes. Maximum diameter for the lifting bar: 20 mm (0.8 in). - The angle from the top of the drive to the lifting cable: 60° or greater. - Test lift the unit approximately 610 mm (24 in) to verify the proper center of gravity lift point. Reposition the lifting point if the unit is not level. Table 2: Drive Weights and Dimensions Enclosure size Protection rating A2 IP20/Chassis A3 IP20/Chassis A5 IP66 - Type 4X B1 IP66 - Type 4X B2 IP66 - Type 4X B3 IP20/Chassis B4 IP20/Chassis C1 IP66 - Type 4X C2 IP66 - Type 4X C3 IP20/Chassis C4 IP20/Chassis D1h Type 12 D2h Type 12 D3h IP20/Chassis D4h IP20/Chassis Dimensions (HxWxD) [in] 10.6x3.6x8.7 10.6x5.2x8.7 16.6x9.6x7.9 18.9x9.6x10.3 25.6x9.6x10x3 15.8x6.5x9.8 20.5x9.1x9.6 26.8x12.2x12.3 30.4x14.6x13.2 21.7x12.2x13 26x14.6x13 35.5x12.8x14.9 43.6x12.8x14.9 35.8x19.8x14.8 44.2x14.8x14.8 Weight [lb] 10.8 14.6 31.5 51 60 26.5 52 99 143 77 110 136.7 275.6 136.7 238.1 6 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide Safety Instructions 2.6 Mechanical Installation Precautions WARNING EXPLOSIVE ATMOSPHERE Installing the drive in a potentially explosive atmosphere can lead to death, personal injury, or property damage. - Install the unit in a cabinet outside of the potentially explosive area. - Use a motor with an appropriate ATEX protection class. - Install a PTC temperature sensor to an ATEX PTC-Thermistor device to monitor the motor temperature. - Install short motor cables. - Use sine-wave output filters when shielded motor cables are not used. 2.7 Electrical Installation Precautions Before you do electrical work on the drive, lock out and tag out all power sources to the drive. WARNING INDUCED VOLTAGE Induced voltage from output motor cables that run together can charge equipment capacitors, even with the equipment turned off and locked out/tagged out. Failure to run output motor cables separately or to use shielded cables could result in death or serious injury. - Run output motor cables separately or use shielded cables. - Simultaneously lock out/tag out all the drives. Protective earth connection and RCD requirements A properly dimensioned protective earth (PE) setup is essential for the safety of the drive system protecting the user against electrical shock. The PE connections of the drive installation ensure that the drive system remains safe preventing that the single fault currents will generate any hazardous voltages on accessible conductive part, for example, conductive enclosure parts. The VLT® AutomationDrive EZ FC 321 shall be installed according to the requirement for PE connection and supplementary protective bonding as specified in IEC/EN 60364-5-54 cl. 543 and 544. For the automatic disconnection, if there is a fault at the motor side, it shall also be ensured that the impedance of the PE connection between drive and motor is sufficiently low to ensure compliance with IEC/EN 60364-4-41 cl. 411 or 415. The impedance is verified by initial and periodic test according to IEC 60364-4-41. In some regions, extra local requirements apply and must be adhered to. The suitability for connection of PE and protective bonding of accessible conductive parts according to IEN/EN 60364-5-54 to the drive is ensured by following the design according to IEC/EN 61800-5-1. Where the FC 321 is used as a component inside specific applications, special requirement for proper connection to the PE may apply, for example, IEC/EN 60204 and IEC/EN 61349-1. Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 7 VLT®AutomationDrive EZ FC 321 Installation Guide Safety Instructions WARNING ELECTRICAL SHOCK HAZARD - LEAKAGE CURRENT HAZARD >3.5 MA Leakage currents exceed 3.5 mA. Failure to connect the drive properly to protective earth (PE) can result in death or serious injury. - Ensure reinforced protective earthing conductor according to IEC 60364-5-54 cl. 543.7 or according to local safety regula- tions for high touch current equipment. The reinforced protective earthing of the can be done with: - a PE conductor with a cross-section of at least 10 mm2 (8 AWG) Cu or 16 mm2 (6 AWG) Al - an extra PE conductor of the same cross-sectional area as the original PE conductor as specified by IEC 60364-5-54 with a minimum cross-sectional area of 2.5 mm2 (14 AWG) (mechanical protected) or 4 mm2 (12 AWG) (not mechanical protected). - a PE conductor completely enclosed with an enclosure or otherwise protected throughout its length against mechanical damage. - a PE conductor part of a multi-conductor power cable with a minimum PE conductor cross-section of 2.5 mm2 (14 AWG) (permanently connected or pluggable by an industrial connector. The multi-conductor power cable shall be installed with an appropriate strain relief). - NOTE: In IEC/EN 60364-5-54 cl. 543.7 and some application standards (for example IEC/EN 60204-1), the limit for requiring reinforced protective earthing conductor is 10 mA leakage current. WARNING ELECTRICAL SHOCK HAZARD - LEAKAGE CURRENT Leakage currents can exceed 5%. Failure to ground the drive properly can result in death or serious injury. - When the leakage currents exceed 5%, the protective earth (PE) shall be oversized by one number according to IEC/EN 60364-5-54 cl. 543. - Ensure that the minimum size of the ground conductor complies with local safety regulations. WARNING ELECTRICAL SHOCK AND FIRE HAZARD - RCD COMPLIANCE The unit can cause a DC fault current in the PE conductor. Failure to use a Type B residual current-operated protective device (RCD) may lead to the RCD not providing the intended protection and therefore may result in death, fire, or other serious hazard. - When an RCD is used for protection against electrical shock or against fire, only a Type B device is allowed on the supply side. Other precautions CAUTION THERMISTOR INSULATION Risk of personal injury or equipment damage. - To meet PELV insulation requirements, use only thermistors with reinforced or double insulation. NOTICE EXCESSIVE HEAT AND PROPERTY DAMAGE Overcurrent can generate excessive heat within the drive. Failure to provide overcurrent protection can result in risk of fire and property damage. - Other protective devices such as short-circuit protection or motor thermal protection between drive and motor are required for applications with multiple motors. - Input fusing is required to provide short circuit and overcurrent protection. If fuses are not factory-supplied, the installer must provide them. See 4.11 Fuses and Circuit Breakers for fuse specifications. 8 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide Safety Instructions NOTICE PROPERTY DAMAGE Protection against motor overload is not included in the default setting. The ETR function provides class 20 motor overload protection. Failure to set the ETR function means that motor overload protection is not provided and property damage can occur if the motor overheats. - Enable the ETR function. See the application guide for more information. 2.8 Safe Operation When operating the unit, refer to the Programming Guide and Application Guide for guidance and all applicable safety instructions. · The drive is not suitable as the only safety device in the system. Make sure that additional monitoring and protection devices on drives, motors, and accessories are installed according to the regional safety guidelines and accident prevention regulations. · Keep all doors, covers, and terminal boxes closed and securely fastened during operation. Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 9 VLT®AutomationDrive EZ FC 321 Installation Guide Mechanical Installation 3 Mechanical Installation 3.1 Connection Tightening Torques Table 3: Tightening Torque for Cables Location Enclosure sizes A2A5 B1/B3 Mains terminals [in-lb] 4.45.3 15.9 Motor terminals [in-lb] 4.45.3 15.9 Ground terminals [in-lb] Brake terminals [in-lb] Relay terminals [in-lb] 4.45.3 17.726.6 15.9 4.45.3 B2/B4 39.8 39.8 17.726.6 39.8 4.45.3 C1/C3 89 89 17.726.6 89 4.45.3 C2/C4 124 (up to 3 AWG) 212 (over 3 AWG) 124 (up to 3 AWG) 212 (over 3 AWG) 17.726.6 124 4.45.3 1 Bolt size M10/M12 2 Bolt size M8/M10 3.2 Cooling · Ensure that top and bottom clearance for air cooling is provided. See Table 4 for clearance requirements. D1h/D3h 168/335(1) 168/335(1) 84/169(2) 84 4 e30bd528.10 a a Illustration 2: Top and Bottom Cooling Clearance Table 4: Minimum Airflow Clearance Requirements Enclosure A2A3, A5 a [in] 3.9 B1B4 7.8 C1, C3 7.8 C2, C4 8.9 D1hD4h 8.9 10 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide Mechanical Installation 3.3 Mounting Procedure 1. Ensure that the strength of the mounting location supports the unit weight. The drive allows side-by-side installation. 2. Place the unit as near to the motor as possible. Keep the motor cables as short as possible. 3. Mount the unit vertically to a solid flat surface or to the optional backplate to provide cooling airflow. 4. Use the slotted mounting holes on the unit for wall mount, when provided. 3.3.1 Mounting with Mounting Plate and Railings A mounting plate is required when mounted on railings. e30bd504.11 Illustration 3: Proper Mounting with Mounting Plate 3.4 Preparing Cable Entry Holes Procedure 1. Remove cable entry from the drive. Avoid that foreign parts fall into the drive when removing the knockouts. 2. Support the cable entry where the knockout is to be removed. 3. Remove the knockout with a strong mandrel and a hammer. 4. Remove burrs from the hole. 5. Mount the cable entry on the drive. Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 11 VLT®AutomationDrive EZ FC 321 Installation Guide Electrical Installation 4 Electrical Installation 4.1 EMC-compliant Installation To obtain an EMC-compliant installation, refer to the wiring schematic (see Illustration 5) and follow the electrical installation instructions. Also, remember to practice the following: · When using relays, control cables, a signal interface, fieldbus, or brake, connect the shield to the enclosure at both ends. If the ground path has high impedance, is noisy, or is carrying current, break the shield connection on 1 end to avoid ground current loops. · Convey the currents back to the unit using a metal mounting plate. Ensure good electrical contact from the mounting plate through the mounting screws to the drive chassis. · Use shielded cables for motor output cables. An alternative is unshielded motor cables within metal conduit. · Ensure that motor and brake cables are as short as possible to reduce the interference level from the entire system. · Provide a minimum 200 mm (7.9 in) separation between mains input, motor cables, and control cables. · For communication and command/control lines, follow the particular communication protocol standards. For example, USB must use shielded cables, but RS485/ethernet can use shielded UTP or unshielded UTP cables. · Ensure that all control terminal connections are PELV. NOTICE TWISTED SHIELD ENDS (PIGTAILS) Twisted shield ends increase the shield impedance at higher frequencies, which reduces the shield effect and increases the leakage current. - Use integrated shield clamps instead of twisted shield ends. NOTICE SHIELDED CABLES If shielded cables or metal conduits are not used, the unit and the installation do not meet regulatory limits on radio frequency (RF) emission levels. NOTICE EMC INTERFERENCE Failure to isolate power, motor, and control cables can result in unintended behavior or reduced performance. - Use shielded cables for motor and control wiring. - Provide a minimum 200 mm (7.9 in) separation between mains input, motor cables, and control cables. NOTICE INSTALLATION AT HIGH ALTITUDE There is a risk for overvoltage. Isolation between components and critical parts could be insufficient and may not comply with PELV requirements. - Use external protective devices or galvanic isolation. For installations above 2000 m (6500 ft) altitude, contact Danfoss re- garding protective extra low voltage (PELV) compliance. NOTICE PROTECTIVE EXTRA LOW VOLTAGE (PELV) COMPLIANCE Prevent electric shock by using PELV electrical supply and complying with local and national PELV regulations. 12 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide 1 90 2 3 4 L1 L2 L3 PE 5 L1 L2 L3 PE IEC 60309 Illustration 4: Example of Proper EMC Installation 4 4 Electrical Installation RELAY 1 RELAY 2 e30bf228.11 M 91 L1 92 L2 AINS L3 93 +DC BR- B 99 UVMOTOR W - LC - 6 7 10 8 9 11 12 13 14 15 u v 16 w PE 17 18 Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 13 VLT®AutomationDrive EZ FC 321 Installation Guide Electrical Installation 1 Programmable logic controller (PLC) 10 Mains cable (unshielded) 2 Minimum 16 mm2 (6 AWG) equalizing cable 11 Output contactor, and so on. 3 Control cables 12 Cable insulation stripped 4 Minimum 200 mm (7.9 in) between control cables, 13 Common ground busbar. Follow local and national motor cables, and mains cables requirements for cabinet grounding. 5 Mains supply options, see IEC/EN 61800-5-1 14 Brake resistor 6 Bare (unpainted) surface 15 Terminal box 7 Star washers 16 Connection to motor 8 Brake cable (shielded) not shown, but same gounding principle applies as for motor cable 9 Motor cable (shielded) 17 Motor 18 EMC cable gland NOTICE EMC INTERFERENCE Use shielded cables for motor and control wiring, and separate cables for input power, motor wiring, and control wiring. Failure to isolate power, motor, and control cables can result in unintended behavior or reduced performance. Minimum 200 mm (7.9 in) clearance is required between power, motor, and control cables. 14 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide Electrical Installation e30bj012.10 3-phase power input DC bus +10 V DC 0/-10 V DC to +10 V DC 0/420 mA 0/-10 V DC to +10 V DC 0/420 mA 91 (L1) 92 (L2) 93 (L3) 95 PE 88 (-) 89 (+) 50 (+10 V OUT) 53 (A IN) S201 54 (A IN) S202 55 (COM A IN) 12 (+24 V OUT) 13 (+24 V OUT) 18 (D IN) 19 (D IN) 20 (COM D IN) 27 (D IN/OUT) 29 (D IN/OUT)1) 32 (D IN) 33 (D IN) ON 12 ON ON 12 12 Switch mode power supply 10 V DC 24 V DC 15 mA 130/200 mA +- + - (U) 96 (V) 97 (W) 98 (PE) 99 (R+) 82 (R-) 81 ON=0/420 mA OFF=0/-10 V DC to +10 V DC P 5-00 24 V (NPN) 0 V (PNP) 24 V (NPN) 0 V (PNP) 24 V (NPN) 24 V 0 V (PNP) 0 V 24 V (NPN) 24 V 24 V (PNP) 0 V 24 V (NPN) 0 V (PNP) 24 V (NPN) 0 V (PNP) Relay 1 03 02 01 Relay 2 06 05 04 (COM A OUT) 39 (A OUT) 42 S801 5V ON=Terminated OFF=Open S801 0 V RS485 interface (N RS485) 69 (P RS485) 68 (COM RS485) 612) 37 (D IN)1) Illustration 5: Wiring Schematic Motor Brake resistor 240 V AC, 2 A 240 V AC, 2 A 400 V AC, 2 A Analog Output 0/420 mA RS-485 : Chassis : Ground : PE : Ground 1 : Ground 2 4.2 Cable Specifications NOTICE WIRE TYPE AND RATINGS All wiring must comply with local and national regulations regarding cross-section and ambient temperature requirements. For power connections, minimum 167 °F rated copper wire is recommended. Table 5: Control Cable Specifications Type of cable Flexible wire without cable end sleeves Rigid wire without cable end sleeves Flexible wire with cable end sleeves Flexible wire with cable end sleeves with collar Maximum cross-section [AWG] 16 16 18 20 Minimum cross-section [AWG] 24 24 24 24 Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 15 VLT®AutomationDrive EZ FC 321 Installation Guide Electrical Installation Table 6: Power Cable Sizes for 104 °F Ambient Temperature, 200240 V and 380500 V Enclosure size Maximum cable size [AWG], mains, motor, brake A2A5 12 B1/B3 7 B2/B4 2 C1 1/0 C3 1/0 C2/C4 4/0 D1h/D3h 3/0 D2h/D4h 2x3/0 Table 7: Power Cable Sizes for 104 °F Ambient Temperature, 525600 V Enclosure size Maximum cable size [AWG], mains, motor, and brake A3/A5 12 B1/B3 7 B2/B4 2 C1 1/0 C3 1/0 C2/C4 4/0 Table 8: Power Cable Sizes for 104 °F Ambient Temperature, 525690 V Enclosure size Maximum cable size [AWG], mains, motor, and brake D1h/D3h 3/0 D2h/D4h 2x400 4.3 Terminal Descriptions Table 9: Digital Inputs/Outputs Terminal Parameter 12, 13 Default setting +24 V DC 18 Parameter 5-10 Terminal 18 Digital In- [8] Start puts 19 Parameter 5-11 Terminal 19 Digital In- [0] No operation puts 32 Parameter 5-14 Terminal 32 Digital Input [0] No operation 33 Parameter 5-15 Terminal 33 Digital Input [0] No operation 27 Parameter 5-12 Terminal 27 Digital Input [2] Coast inverse Description +24 V DC supply voltage for digital inputs and external transducers. Maximum output current 200 mA for all 24 V loads. Digital inputs For digital input or output. Default setting is input. 16 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide Electrical Installation Terminal Parameter 29 Parameter Terminal 29 Digital Input 20 37 Default setting Description [14] Jog Common for digital inputs and 0 V potential for 24 V supply. Safe Torque Off (STO) Safe input. Used for STO. Table 10: Analog Inputs/Outputs Terminal Parameter Default setting Description 39 Common for analog output. 42 Parameter 6-50 Terminal 42 Speed 0high lim- Programmable analog output. 020 mA or 420 mA at a maxi- Output it mum of 500 . 50 +10 V DC 10 V DC analog supply voltage potentiometer or thermistor. 15 mA maximum. 53 Parameter group 6-1* Analog Reference Input 1 Analog input. For voltage or current. Switches A53 and A54 select mA or V. 54 Parameter group 6-1* Analog Feedback Input 2 55 Common for analog input. Table 11: Serial Communication Terminal Parameter 61 Default setting 68 (+) 69 (-) Parameter group 8-3* FC Port Settings Parameter group 8-3* FC Port Settings Description Integrated RC-filter for cable shield. ONLY for connecting the shield if EMC problems occur. RS485 interface. A control card switch is provided for termination resistance. Table 12: Relays Terminal Parameter Default setting Description 01, 02, 03 Parameter 5-40 Function Relay [0] [9] Alarm 04, 05, 06 Parameter 5-40 Function Relay [1] [5] Running Form C relay output. For AC or DC voltage and resistive or inductive loads. 4.4 Connecting the Control Cables to the Control Terminals The control terminal connectors can be unplugged from the drive for convenience when wiring. Either solid or flexible wire can be connected to the control terminals. NOTICE ELECTRICAL INTERFERENCE Minimize interference by keeping control wires as short as possible and separate from high-power cables. 1. Strip 10 mm (0.4 in) of the outer plastic layer from the end of the wire. Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 17 VLT®AutomationDrive EZ FC 321 Installation Guide 2. Insert the control wire into the appropriate terminals. 12 13 18 19 27 29 32 33 Electrical Installation e30bd546.12 (0.140 inm)m 3. Pull gently on the wire to ensure that the contact is firmly established. Loose control cable can cause equipment faults or reduced performance. 4.5 Start/Stop Terminal 18 = Parameter 5-10 Terminal 18 Digital Input [8] Start. Terminal 27 = Parameter 5-12 Terminal 27 Digital Input [0] No operation (Default [2] Coast inverse). Terminal 37 = Safe Torque Off. 12 13 18 19 27 29 32 33 20 37 +24V P 5-10 [8] P 5-12 [0] e30ba155.12 Speed Start/Stop Safe Stop Start/Stop [18] Illustration 6: Start/Stop 4.6 Pulse Start/Stop Terminal 18 = Parameter 5-10 Terminal 18 Digital Input [9] Latched start. Terminal 27 = Parameter 5-12 Terminal 27 Digital Input [6] Stop inverse. Terminal 37 = Safe Torque Off. 18 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 +24V P 5 - 10[9] P 5 - 12 [6] e30ba156.12 VLT®AutomationDrive EZ FC 321 Installation Guide 12 13 18 19 27 29 32 33 20 37 Electrical Installation Start Stop inverse Safe Stop Speed Start (18) Start (27) Illustration 7: Pulse Start/Stop 4.7 Speed Up/Speed Down Terminal 18 = Parameter 5-10 Terminal 18 Digital Input [8] Start. Terminal 27 = Parameter 5-12 Terminal 27 Digital Input [19] Freeze reference. Terminal 37 = Safe Torque Off. Terminal 29 = Parameter 5-13 Terminal 29 Digital Input [21] Speed up. Terminal 32 = Parameter 5-14 Terminal 32 Digital Input [22] Speed down. 12 +24V e30ba021.13 18 Par. 5-10 27 Par. 5-12 29 32 37 Illustration 8: Speed Up/Speed Down Par. 5-13 Par. 5-14 Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 19 VLT®AutomationDrive EZ FC 321 Installation Guide 4.8 Potentiometer Reference Voltage reference via a potentiometer Reference source 1 = [1] Analog input 53 (default). Terminal 53, low voltage = 0 V. Terminal 53, high voltage = 10 V. Terminal 53, low reference/feedback = 0 RPM. Terminal 53, high reference/feedback = 1500 RPM. Switch S201 = OFF (U) Speed RPM P 6-15 39 42 50 53 54 55 +10V/30mA e30ba154.11 Electrical Installation Ref. voltage P 6-11 10V 1 k Illustration 9: Potentiometer Reference 4.9 Connecting the Motor WARNING INDUCED VOLTAGE Induced voltage from output motor cables that run together can charge equipment capacitors, even with the equipment turned off and locked out/tagged out. Failure to run output motor cables separately or to use shielded cables could result in death or serious injury. - Run output motor cables separately or use shielded cables. - Simultaneously lock out/tag out all the drives. · Run output motor cables separately or · Use shielded cables. · Comply with local and national electrical codes for cable sizes. For maximum wire sizes, see 4.2 Cable Specifications. · Follow motor manufacturer wiring requirements. · Motor wiring knockouts or access panels are provided at the base of IP55 (NEMA 12) units. · Do not wire a starting or pole-changing device (for example a Dahlander motor or slip ring asynchronous motor) between the drive and the motor. 4.9.1 Grounding the Cable Shield Procedure 1. Strip a section of the outer cable insulation. 2. Position the stripped wire under the cable clamp to establish mechanical fixation and electrical contact between the cable shield and ground. 20 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide 3. Connect the ground wire to the nearest grounding terminal. W V U 96 97 98 e30bd531.11 Electrical Installation 4. Connect the 3-phase motor wiring to terminals 96 (U), 97 (V), and 98 (W). 5. Torque-tighten the terminals, see Table 3. Example Mains input, motor, and grounding for basic drives. Actual configurations vary with unit types and optional equipment. Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 21 VLT®AutomationDrive EZ FC 321 Installation Guide M 91 L1 92 L2 A IN S L3 93 +DC BR- B 99 U MVOTWOR 99 RELAY 1 REALY 2 130BF048.11 Electrical Installation Illustration 10: Example of Motor, Mains, and Ground Wiring 4.10 Connecting AC Mains · Size the wiring based on the input current of the drive. For maximum wire sizes, see 4.2 Cable Specifications. · Comply with local and national electrical codes for cable sizes. 4.10.1 Connecting the Drive to Mains Procedure 1. Connect the 3-phase AC input power wiring to terminals L1, L2, and L3. 2. Depending on the configuration of the equipment, connect the input power to the mains input terminals or the input disconnect. 3. Ground the cable. 4. When supplied from an isolated mains source (IT mains or floating delta) or TT/TN-S mains with a grounded leg (grounded delta), ensure that parameter 14-50 RFI Filter is set to [0] Off. This setting prevents damage to the DC link and reduces ground capacity currents in accordance with IEC 61800-3. 22 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide L 1 91 L 2 92 L 3 93 e130bt336.11 Electrical Installation Illustration 11: Connecting to AC Mains 4.11 Fuses and Circuit Breakers 4.11.1 Fuse Recommendations Fuses ensure that possible damage to the drive is limited to damages inside the unit. Danfoss recommends fuses and/or circuit breakers on the supply side as protection. For further information, see the application guide Fuses and Circuit Breakers. NOTICE Use of fuses on the supply side is mandatory for IEC 60364 (CE) and NEC 2009 (UL) compliant installations. Recommendations · gG type fuses. · Eaton/Moeller type circuit breakers. For other circuit breaker types, ensure that the energy into the drive is equal to or lower than the energy provided by Eaton/Moeller types. For further information, see the application guide Fuses and Circuit Breakers. The recommended CE and UL compliant fuses are suitable for use on a circuit capable of 100000 Arms (symmetrical), depending on the drive voltage rating. With the proper fusing, the drive short circuit current rating (SCCR) is 100000 Arms. 4.11.2 CE Compliance Table 13: 200240 V, Enclosure Sizes A, B, C, and D Enclosure Power [hp] Recommended fuse Recommended max- Recommended circuit breaker size imum fuse Eaton/Moeller Maximum trip level [A] A2 0.342.0 gG-10 gG-25 PKZM0-25 25 3.0 gG-16 A3 4.0 gG-16 gG-32 PKZM0-25 25 5.0 gG-20 A5 0.342.0 gG-10 gG-32 PKZM0-25 25 3.04.0 gG-16 5.0 gG-20 B1 7.5 gG-25 gG-80 PKZM4-63 63 Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 23 VLT®AutomationDrive EZ FC 321 Installation Guide Electrical Installation Enclosure Power [hp] Recommended fuse Recommended max- Recommended circuit breaker Maximum trip lev- size imum fuse Eaton/Moeller el [A] 10.0 gG-32 B2 15.0 gG-50 gG-100 NZMB1-A100 100 B3 7.5 gG-25 gG-63 PKZM4-50 50 B4 10 gG-32 gG-125 NZMB1-A100 100 15 gG-50 20 gG-63 C1 20 gG-63 gG-160 NZMB2-A200 160 25 gG-80 30 gG-100 aR-160 C2 40 aR-160 aR-200 NZMB2-A250 250 50 aR-200 aR-250 C3 25 gG-80 gG-150 NZMB2-A200 150 30 aR-125 aR-160 C4 40 aR-160 aR-200 NZMB2-A250 250 50 aR-200 aR-250 D1h/D3h 60 aR-350 aR-350 75 aR-400 aR-400 D2h/D4h 100 aR-550 aR-550 Table 14: 380500 V, Enclosure Sizes A, B, C, and D Enclosure Power [hp] Recommended fuse Recommended max- Recommended circuit breaker size imum fuse Eaton/Moeller A2 0.54.0 gG-10 gG-25 PKZM0-25 5.0 gG-16 A3 7.510 gG-16 gG-32 PKZM0-25 A5 0.54.0 gG-10 gG-32 PKZM0-25 5.010 gG-16 B1 1520 gG-40 gG-80 PKZM4-63 B2 25 gG-50 gG-100 NZMB1-A100 30 gG-63 B3 1520 gG-40 gG-63 PKZM4-50 B4 25 gG-50 gG-125 NZMB1-A100 30 gG-63 Maximum trip level [A] 25 25 25 63 100 50 100 24 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide Electrical Installation Enclosure Power [hp] Recommended fuse Recommended max- Recommended circuit breaker size imum fuse Eaton/Moeller 40 gG-80 C1 40 gG-80 gG-160 NZMB2-A200 50 gG-100 60 gG-160 C2 75 aR-200 aR-250 NZMB2-A250 100 aR-250 C3 50 gG-100 gG-150 NZMB2-A200 60 gG-160 gG-160 C4 75 aR-200 aR-250 NZMB2-A250 100 aR-250 D1h/D3h 125 aR-315 aR-315 150 aR-350 aR-350 200 aR-400 aR-400 Maximum trip level [A] 160 250 150 250 Table 15: 525600 V, Enclosure Sizes A, B, C, and D Enclosure Power [hp] Recommended fuse Recommended max- Recommended circuit breaker size imum fuse Eaton/Moeller A2 1.0-5.0 gG-10 gG-25 PKZM0-25 A3 7.5 gG-10 gG-32 PKZM0-25 10 gG-16 A5 7.5 gG-10 gG-32 PKZM0-25 10 gG-16 B1 15 gG-25 gG-80 PKZM4-63 20 gG-32 25 gG-40 B2 30 gG-50 gG-100 NZMB1-A100 40 gG-63 B3 15 gG-25 gG-63 PKZM4-50 20 gG-32 B4 25 gG-40 gG-125 NZMB1-A100 30 gG-50 40 gG-63 C1 50 gG-63 gG-160 NZMB2-A200 Maximum trip level [A] 25 25 25 63 100 50 100 160 Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 25 VLT®AutomationDrive EZ FC 321 Installation Guide Electrical Installation Enclosure Power [hp] Recommended fuse Recommended max- Recommended circuit breaker size imum fuse Eaton/Moeller 60 gG-100 60 aR-160 aR-250 C2 100 aR-200 aR-250 NZMB2-A250 C3 50 gG-63 gG-150 NZMB2-A200 60 gG-100 gG-150 NZMB2-A200 C4 75 aR-160 aR-250 NZMB2-A250 100 aR-200 Maximum trip level [A] 250 150 250 Table 16: 525690 V, Enclosure Size D Enclosure Power [hp] D1h/D3h 125 150 200 Recommended fuse size aR-315 aR-315 aR-315 Recommended maximum fuse aR-315 aR-315 aR-315 4.11.3 UL Compliance Fuse classification for UL Compliance NOTICE UL COMPLIANCE To comply with NEC 2017, it is mandatory to use fuses or circuit breakers. Danfoss recommends using a selection of the fuses listed in the following tables. These fuses are suitable for use on a circuit capable of delivering 100000 Arms (symmetrical), 240 V, 500 V, or 600 V depending on the drive voltage rating. With the proper fusing, the drive short-circuit current rating (SCCR) is 100000 Arms. For semiconductor fuse types, the drive controller and the overcurrent protection device must be integrated within the same overall assembly. Table 17: UL Fuse Classification Chart UL class Fuse overload characteristics Interrupting rating AC voltage rating [A] [V] Available ampere rating RK1 Ultra fast-acting, current limiting/time de- 200.000 250 lay 600 1600 T Fast-acting 200.000 300 600 11.200 J Fast-acting CC Fast-acting 200.000 600 200.000 600 1600 530 26 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide Electrical Installation Table 18: Recommended Maximum UL Fuse Class, Voltage Range 3x200240 V, Enclosure Sizes A, B, and C Class fuses Semiconductor fuses Power [hp] RK1/J/T [A] CC [A] SIBA Littelfuse Ferraz Shawmut (Mersen) 0.340.5 5 5 5017906-005 0.751.5 10 10 5017906-010 2.0 15 15 5017906-016 3.0 20 20 5017906-020 4.0 25 25 5017906-025 5.0 30 30 5012406-032 7.5 50 5014006-050 10 60 5014006-063 15 80 5014006-080 2025 125 2028220-125 30 150 2028220-150 L25S-150 A25X-150 40 200 2028220-200 L25S-200 A25X-200 50 250 2028220-250 L25S-250 A25X-250 Table 19: Recommended Maximum UL Fuse Class, Voltage Range 380500 V, Enclosure Sizes A, B, and C Class fuses Semiconductor fuses Power [hp] RK1/J/T [A] CC [A] SIBA Littelfuse Ferraz Shawmut (Mersen) 0.51.5 6 6 5017906-006 2.03.0 10 10 5017906-010 4.0 15 15 5017906-016 5.0 20 20 5017906-020 7.5 25 25 5017906-025 10 30 30 5012406-032 15 40 5014006-040 20 50 5014006-050 25 60 5014006-063 30 80 2028220-100 40 100 2028220-125 50 125 2028220-125 60 150 2028220-160 75 200 2028220-200 L50-S-225 A50-P-225 100 250 2028220-250 L50-S-250 A50-P-250 Bussmann (Eaton) FWX-5 FWX-10 FWX-15 FWX-20 FWX-25 FWX-30 FWX-50 FWX-60 FWX-80 FWX-125 FWX-150 FWX-200 FWX-250 Bussmann (Eaton) FWH-6 FWH-10 FWH-15 FWH-20 FWH-25 FWH-30 FWH-40 FWH-50 FWH-60 FWH-80 FWH-100 FWH-125 FWH-150 FWH-200 FWH-250 Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 27 VLT®AutomationDrive EZ FC 321 Installation Guide Electrical Installation Table 20: Recommended Maximum UL Fuse Class, Voltage Range 525690 V, Enclosure Sizes A, B, and C Class fuses Semiconductor fuses Power [hp] RK1/J/T [A] CC [A] SIBA 1.5 5(1) 5 5017906-005 2.03.0 10 10 5017906-010 4.0 15 15 5017906-016 5.0 20 20 5017906-020 7.5 25 25 5017906-025 10 30 30 5017906-030 15 35 5014006-040 20 45 5014006-050 25 50 5014006-050 30 60 5014006-063 40 80 5014006-080 50 100 5014006-100 60 125 2028220-125 75 150 2028220-150 100 175 2028220-200 1 Bussmann Class T allowed up to 6 A. UL Compliance only for 525600 V. NOTICE Table 21: UL Approved Branch Circuit Protection Enclosure size Enclosure (1) Voltage [V] Power [hp] HO Maximum interrupting rating for listed circuit breakers Maximum ampere rating [A] Further information A4/A5 Type 4X 380500 0.5, 0.75, 100 kA (at 25 (T5) 1.0, 1.5, 2.0, 480 V) 3.0, 4.0, 5.0, 7.5, 10 Any UL 489 listed circuit breaker, maximum 25 A. A5 Type 4X 200240 V 4.0, 5.0 Specific type 25 (T2) ABB MS165-25 480V/277Y 65 kA. A5 Type 4X 380500 V 7.5, 10 (T5) Specific type 25 ABB MS165-25 480V/277Y 65 kA. A5 Type 4X 525600 V 5.0, 7.5, 10 Specific type 25 (T6) ABB MS165-25 600V/347Y 30 kA. 28 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide Electrical Installation Enclosure size Enclosure (1) B1 Type 4X B1 Type 4X B1 Type 4X B1 Type 4X B2 Type 4X B2 Type 4X C1 Type 4X C2 Type 4X Voltage [V] Power [hp] HO Maximum interrupting rating for listed circuit breakers Maximum ampere rating [A] Further information 200240 V (T2) 7.5, 10 Specific type 4054 ABB MS165-54 480V/277Y 65 kA. 380500 V (T5) 15, 20 Specific type 4054 ABB MS165-54 480V/277Y 65 kA. 380500 V (T5) 15, 20 100 kA 60 Any UL 489 circuit breaker type with maximum interrupt rating and maximum ampere rating in list. 525600 V (T6) 15, 20 50 kA 40 Any UL 489 circuit breaker type with maximum interrupt rating and maximum ampere rating in list. 380500 V (T5) 25, 30 100 kA 100 Any UL 489 circuit breaker type with maximum interrupt rating and maximum ampere rating in list 525600 V (T6) 25, 30 35 kA 60 any UL 489 circuit breaker type with maximum interrupt rating and maximum ampere rating in list. 380500 V (T5) 40, 50, 60 100 kA 200 Any UL 489 circuit breaker type with maximum interrupt rating and maximum ampere rating in list. 380500 V (T5) 75, 100 100 kA 250 Any UL 489 circuit breaker type with maximum interrupt rating and maximum ampere rating in list. 1 Only Type 4X enclosures can be used. Not valid for Open type (IP20) units. Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 29 VLT®AutomationDrive EZ FC 321 Installation Guide Specifications 5 Specifications 5.1 Ambient Conditions 5.1.1 Environment Enclosure Vibration test Maximum THDv Maximum relative humidity Aggressive environment (IEC 60068-2-43) H2S test Ambient temperature Minimum ambient temperature during full-scale operation Minimum ambient temperature at reduced speed performance Temperature during storage/transport Maximum altitude above sea level without derating EMC standards, Emission EMC standards, Immunity Energy efficiency class(1) IP20/Chassis, IP54/NEMA 12, IP66/Type 4X 1.0 g 10% 593 (IEC 721-3-3); Class 3K3 (non-condensing) during operation Class Kd Maximum 122 °F (24-hour average maximum 113 °F) 32 °F 14 °F -13 to +149/158 °F 3280 ft EN 61800-3 EN 61800-3 IE2 1 Determined according to IEC 61800-9-2 and EN 50598-2 at: · Rated load. · 90% rated frequency. · Switching frequency factory setting. · Switching pattern factory setting. 5.2 Mains Supply Supply terminals (6-pulse) Supply voltage(1)(2) Supply voltage(1)(2) Supply voltage(1)(2) Supply voltage(1)(2) Supply frequency Maximum imbalance temporary between mains phases True power factor () Displacement power factor (cos ) Switching on the input supply L1, L2, L3 (power-ups) 10 hp Switching on input supply L1, L2, L3 (power-ups) 15100 hp Switching on input supply L1, L2, L3 (power-ups) 125 hp Environment according to EN60664-1 L1, L2, L3 200240 V ±10% 380500 V ±10% 525600 V ±10% 575690 V ±10% 47.563 Hz 3.0% of rated supply voltage 0.9 nominal at rated load Near unity (>0.98) Maximum twice per minute Maximum once per minute Maximum once per 2 minutes Overvoltage category III/pollution degree 2 1 Mains voltage low/mains dropout: During low mains voltage or a mains dropout, the drive continues until the DC-link voltage drops below the minimum stop level, which typically corresponds to 15% below the drive's lowest rated supply voltage. Power-up and full torque cannot be expected at mains voltage lower than 10% below the drive's lowest rated supply voltage. 2 The unit is suitable for use on a circuit capable of delivering not more than 100000 RMS symmetrical Amperes, 240/500/600 V maximum. 5.3 Control Input/Output and Control Data 5.3.1 Digital Inputs Programmable digital inputs 4 (6)(1) 30 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide Specifications Terminal number Logic Voltage level Voltage level, logic 0 PNP Voltage level, logic 1, PNP Voltage level, logic 0 NPN(2) Voltage level, logic 1 NPN(2) Maximum voltage on input Pulse frequency range (Duty cycle) minimum pulse width Input resistance, Ri 18, 19, 27(1), 29(1), 32, 33 PNP or NPN 024 V DC <5 V DC >10 V DC >19 V DC <14 V DC 28 V DC 0110 kHz 4.5 ms Approximately 4 k 1 Terminals 27 and 29 can also be programmed as output. 2 Except STO input terminal 37. 5.3.2 STO Terminal 37 (Terminal 37 is Fixed PNP Logic) Voltage level Voltage level, logic 0 PNP Voltage level, logic 1 PNP Maximum voltage on input Typical input current at 24 V Typical input current at 20 V Input capacitance 024 V DC <4 V DC >20 V DC 28 V DC 50 mA rms 60 mA rms 400 nF All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. When using a contactor with a DC coil inside in combination with STO, it is important to make a return way for the current from the coil when turning it off. This can be done by using a freewheel diode (or, alternatively, a 30 V or 50 V MOV for quicker response time) across the coil. Typical contactors can be bought with this diode. 5.3.3 Analog Inputs Number of analog inputs Terminal number Modes Mode select Voltage mode Voltage level Input resistance, Ri Maximum voltage Current mode Current level Input resistance, Ri Maximum current Resolution for analog inputs Accuracy of analog inputs Bandwidth 2 53, 54 Voltage or current Switch S201 and switch S202 Switch S201/switch S202 = OFF (U) -10 V to +10 V (scaleable) Approximately 10 k ±20 V Switch S201/S202 = ON (I) 0/4 to 20 mA (scaleable) Approximately 200 30 mA 10 bit (+ sign) Maximum error 0.5% of full scale 100 Hz The analog inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 31 VLT®AutomationDrive EZ FC 321 Installation Guide Specifications e30ba117.11 +24 V 18 Control PELV isolation Mains 37 Functional isolation RS485 High voltage Illustration 12: PELV Isolation 5.3.4 Pulse/Encoder Inputs Programmable pulse/encoder inputs Terminal number pulse/encoder Maximum frequency at terminals 29, 32, 33 Maximum frequency at terminals 29, 32, 33 Maximum frequency at terminals 29, 32, 33 Voltage level Maximum voltage on input Input resistance, Ri Pulse input accuracy (0.11 kHz) Encoder input accuracy (111 kHz) Motor DC-bus 2/1 29, 33(1)/32(2), 33(2) 110 kHz (Push-pull driven) 5 kHz (Open collector) 4 Hz See 5.3.1 Digital Inputs. 28 V DC Approximately 4 k Maximum error: 0.1% of full scale Maximum error: 0.05% of full scale 1 Pulse inputs are 29 and 33. 2 Encoder inputs: 32=A, 33=B. The pulse and encoder inputs (terminals 29, 32, 33) are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. 5.3.5 Digital Outputs Programmable digital/pulse outputs Terminal number Voltage level at digital/frequency output Maximum output current (sink or source) Maximum load at frequency output Maximum capacitive load at frequency output Minimum output frequency at frequency output Maximum output frequency at frequency output Accuracy of frequency output Resolution of frequency outputs 2 27, 29(1) 024 V 40 mA 1 k 10 nF 0 Hz 32 kHz Maximum error: 0.1% of full scale 12 bit 1 Terminals 27 and 29 can also be programmed as input. The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. 5.3.6 Analog Output Number of programmable outputs Terminal number Current range at analog output Maximum load GND - analog output less than Accuracy on analog output 1 42 0/4 to 20 mA 500 Maximum error: 0.5% of full scale 32 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide Specifications Resolution of analog output 12 bit The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. 5.3.7 Control Card, 24 V DC Output Terminal number Output voltage Maximum load 12, 13 24 V +1, -3 V 200 mA The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital inputs and outputs. 5.3.8 Control Card, +10 V DC Output Terminal number Output voltage Maximum load 50 10.5 V ±0.5 V 15 mA The 10 V DC supply is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. 5.3.9 Control Card, RS485 Serial Communication Terminal number Terminal number 61 68 (P,TX+, RX+), 69 (N,TX-, RX-) Common for terminals 68 and 69 The RS485 serial communication circuit is galvanically isolated from the supply voltage (PELV). 5.3.10 Control Card, USB Serial Communication USB standard USB plug 1.1 (full speed) USB type B plug Connection to the PC is carried out via a standard host/device USB cable. The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. The USB ground connection is not galvanically isolated from protective earth. Use only an isolated laptop as PC connection to the USB connector on the drive. 5.3.11 Relay Outputs Programmable relay outputs Relay 01 terminal number Maximum terminal load (AC-1)(1) on 13 (NC), 12 (NO) (resistive load) Maximum terminal load (AC-15)(1) (inductive load @ cos 0.4) Maximum terminal load (DC-1)(1) on 12 (NO), 13 (NC) (resistive load) Maximum terminal load (DC-13)(1) (inductive load) Relay 02 terminal number Maximum terminal load (AC-1)(1) on 45 (NO) (resistive load)()() Maximum terminal load (AC-15)(1) on 45 (NO) (inductive load @ cos 0.4) Maximum terminal load (DC-1)(1) on 45 (NO) (resistive load) Maximum terminal load (DC-13)(1) on 45 (NO) (inductive load) Maximum terminal load (AC-1)(1) on 46 (NC) (resistive load) Maximum terminal load (AC-15)(1) on 46 (NC) (inductive load @ cos 0.4) 2 13 (break), 12 (make) 240 V AC, 2 A 240 V AC, 0.2 A 60 V DC, 1 A 24 V DC, 0.1 A 46 (break), 45 (make) 400 V AC, 2 A 240 V AC, 0.2 A 80 V DC, 2 A 24 V DC, 0.1 A 240 V AC, 2 A 240 V AC, 0.2 A Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 33 VLT®AutomationDrive EZ FC 321 Installation Guide Specifications Maximum terminal load (DC-1)(1) on 46 (NC) (resistive load) Maximum terminal load (DC-13)(1) on 46 (NC) (inductive load) Minimum terminal load on 13 (NC), 12 (NO), 46 (NC), 45 (NO) Environment according to EN 60664-1 50 V DC, 2 A 24 V DC, 0.1 A 24 V DC 10 mA, 24 V AC 20 mA Overvoltage category III/pollution degree 2 1 IEC 60947 parts 4 and 5. The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV). 5.3.12 Control Card Performance Scan interval 1 ms 5.3.13 Control Characteristics Resolution of output frequency at 0590 Hz Repeat accuracy of precise start/stop (terminals 18, 19) System response time (terminals 18, 19, 27, 29, 32, 33) Speed control range (open loop) Speed control range (closed loop) Speed accuracy (open loop) Speed accuracy (closed loop), depending on resolution of feedback device Torque control accuracy (speed feedback) All control characteristics are based on a 4-pole asynchronous motor. ±0.003 Hz ±0.1 ms 2 ms 1:100 of synchronous speed 1:1000 of synchronous speed 304000 RPM: Error ±8 RPM 06000 RPM: Error ±0.15 RPM Maximum error ±5% of rated torque 34 | Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 VLT®AutomationDrive EZ FC 321 Installation Guide 6 Appendix 6.1 Abbreviations Table 22: Abbreviations Term Definition AC Alternating current AWG American wire gauge DC Direct current EMC Electromagnetic compatibility ETR Electronic thermal relay IEC International Electrotechnical Commission IP Ingress protection LCP Local control panel LOP Local operation pad mA Milliamp NC Normally closed NEMA National Electrical Manufacturers Association NO Normally open PELV Protective extra low voltage PTC Positive temperature coefficient RMS Root means square (cyclically alternating electric current) RPM Revolutions per minute STO Safe Torque Off UPS Uninterruptible power supply UTP Unshielded twisted pair V Volt Appendix Danfoss A/S © 2021.05 AN354546796134en-000201 / 130R0954 | 35 Danfoss A/S Ulsnaes 1 DK-6300 Graasten vlt-drives.danfoss.com Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. *130R0954* Danfoss A/S © 2021.05 *M0026701* AN354546796134en-000201 / 130R0954