Service Facts

Single Packaged Cooling/Electric Heat

Model: A5PA3042A1000A

Illustration of a single packaged cooling and electric heat unit.

⚠️ SAFETY WARNING

Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment.

Document Date: September 2024

Document ID: A5PA3042A-SF-1A-EN

SAFETY SECTION

Important Information

This document contains a wiring diagram, a parts list, and service information. This is customer property and is to remain with this unit. Please return to service information pack upon completion of work.

⚠️ WARNING: HAZARDOUS VOLTAGE!

Failure to follow this Warning could result in property damage, severe personal injury, or death. Disconnect all electric power, including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized.

⚠️ WARNING: SAFETY AND ELECTRICAL HAZARD!

Failure to follow this Warning could result in property damage, severe personal injury, or death. These servicing instructions are for use by qualified personnel only. To reduce the risk of electrical shock, do not perform any servicing other than that contained in these operating instructions unless you are qualified to do so.

⚠️ CAUTION: GROUNDING REQUIRED!

Failure to inspect or use proper service tools may result in equipment damage or personal injury. Reconnect all grounding devices. All parts of this product that are capable of conducting electrical current are grounded. If grounding wires, screws, straps, clips, nuts, or washers used to complete a path to ground are removed for service, they must be returned to their original position and properly fastened.

⚠️ CAUTION: SHARP EDGE HAZARD!

Failure to follow this Caution could result in property damage or personal injury. Be careful of sharp edges on equipment or any cuts made on sheet metal while installing or servicing.

⚠️ WARNING: UNIT CONTAINS R-454B REFRIGERANT!

Proper service equipment is required. Failure to use proper service tools may result in equipment damage or personal injury.

⚠️ WARNING: SERVICE!

USE ONLY R-454B REFRIGERANT AND APPROVED COMPRESSOR OIL.

⚠️ WARNING: LEAK DETECTION SYSTEM!

LEAK DETECTION SYSTEM installed. Unit must be powered except for service.

⚠️ WARNING: SAFETY HAZARD!

Children should be supervised to ensure that they do not play with the appliance.

⚠️ WARNING: SAFETY HAZARD!

This appliance is not to be used by persons (including children) with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning the use of the appliance by a person responsible for their safety.

⚠️ WARNING: SAFETY HAZARD!

Operating the unit without the access panels properly installed may result in severe personal injury or death. Do not operate the unit without the evaporator fan access panel or evaporator coil access panel in place.

⚠️ WARNING: RISK OF FIRE!

Flammable refrigerant used. To be repaired only by trained service personnel. Do not puncture refrigerant tubing. Dispose of refrigerant in accordance with federal and/or local regulations.

⚠️ WARNING! (California Proposition 65)

This product can expose you to chemicals including lead, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov.

Important Notes

Wear appropriate gloves, arm sleeve protectors and eye protection when servicing or maintaining this equipment. Air filters and media wheels or plates shall meet the test requirements in UL 900.

Product Specification

Model: A5PA3042A1000A

SpecificationValueSpecificationValue
RATED Volts/PH/Hz208-230/1/60Volts/Ph/Hz208-230/1/60
Performance Cooling BTUH (a)40000F.L. Amps/L.R Amps1.5 / 3.07
Indoor Airflow (CFM)1500INDOOR FAN TYPECONSTANT TORQUE ECM
Power Input (KW)3.53Dia. x Width (in.)10.62 X 10.62
EER2/SEER2 (BTU/Watt-Hr.) (b)10.6 / 13.4Drive/No. SpeedsDIRECT / 4
Sound Power Rating [dB(A)] (c)74.6CFM @ 0.0 in. w.g. (f)SEE FAN PERF TABLE
POWER CONN. - V/Ph/Hz208-230/1/60Motor - HP/R.P.M.3/4 / 1050
Min. Brch. Cir. Ampacity (d)26Volts/Ph/Hz208-230/1/60
Fuse Size Max. (amps)40F.L. Amps6.0
Fuse Size Recmd. (amps)40FILTER / FURNISHEDNO
COMPRESSORSCROLLType RecommendedTHROWAWAY
VOLTS/PH/HZ208-230/1/60Recmd. Face Area (sq. ft) (g)5.3
R.L. Amps - L.R. Amps14.7 / 109REFRIGERANTR-4545B
OUTDOOR COIL - TYPESPINE-FINCharge (lbs.)7.3
Rows/F.P.I2 / 24CHARGING SPECIFICATIONS
Face Area (sq. ft.)15.63Subcooling12° F
Tube Size (in.)3/8DIMENSIONS HxWXL
INDOOR COIL - TYPEMCHECrated (in.)46 X 47 X 62
Rows/F.P.I2 / 16WEIGHT
Face Area (sq. ft.)3.9Shipping (lbs.) / Net (lbs.)564 / 460
Tube Size (in.)0.81
Refrigeration ControlEXPANSION VALVE
Drain Conn. Size (in.)3/4 FEMALE NPT
OUTDOOR FAN TYPEPROPELLER
DIA. (IN.)28.3
DRIVE/NO. SPEEDSDIRECT / 1
CFM @ 0.0 in. w.g. (e)3400
Motor - HP/R.P.M1/4 / 825

Notes:

Pressure Curves

Figure 1. Pressure Curves for A5PA3042 - Cooling

Liquid Pressure Plot

This graph displays Liquid Pressure (PSIG) against Outdoor Temperature (Degree F). It includes curves representing different Indoor Entering Wet Bulb temperatures (71, 67, 63, and 59 Deg F). The plot helps determine system performance by locating points based on measured temperatures and pressures.

Suction Pressure Plot

This graph displays Suction Pressure (PSIG) against Outdoor Temperature (Degree F). Similar to the liquid pressure plot, it includes curves for different Indoor Entering Wet Bulb temperatures. It aids in diagnosing system performance and charge levels.

Procedure for Checking Cooling Performance

To check cooling performance when the outdoor temperature is above 65 Deg F: Select the proper indoor CFM, allow pressures to stabilize. Measure indoor wet bulb temperature, outdoor temperature, discharge, and suction pressures. Locate the outdoor temperature on the x-axis (1), locate the indoor wet bulb temperature on the y-axis or corresponding curve (2). Find the intersection point (3). Read the discharge or suction pressure in the left column (4).

Example and Actual Tolerances

Example: (1) Outdoor Temp. 82 F, (2) Indoor Wet Bulb 67 F. At intersection (3), (4) Discharge Pressure @ 1500 CFM is 310 PSIG, (5) Suction Pressure @ 1500 CFM is 137 PSIG.

Actual: Discharge Pressure should be +/- 10 PSI of chart. Suction Pressure should be +/- 3 PSIG of chart.

Drawing Number: A5PA3042

Sequence of Operation

General

Operation of the system cooling (and optional heating) cycles is controlled by the comfort control. Once the comfort control is set to either the HEAT or COOL, unit operation is automatic. The optional automatic changeover comfort control, when set to AUTO, automatically changes to heat or cool with sufficient room temperature change. With the unit disconnect closed, voltage is supplied to the unit control transformer and the crankcase heater (if provided). On single phase units, the crankcase heater is an option that is field installed.

Cooling Mode

With the comfort control set to COOL and the fan set to AUTO, the compressor contactor (CC) and the indoor fan motor (IDM) are energized. The energized compressor contactor (CC) completes the circuit to the compressor (CPR) and a secondary circuit to the outdoor fan motor (ODM). If the compressor safety controls are closed, the compressor (CPR) will operate with the outdoor fan motor (ODM). The indoor fan motor (IDM) will operate. The comfort control will continue to cycle the compressor and fans to maintain the desired temperature. With the fan switch set to ON, the indoor fan motor (IDM) will continue to run regardless of compressor and condenser fan operation. Continuous fan mode during cooling operation may not be appropriate in humid climates. If the indoor air exceeds 60% relative humidity or simply feels uncomfortably humid, it is recommended that the fan only be used in the AUTO mode.

Heating Mode

Heating mode uses electric heaters, which are installed separately. Refer to the Supplemental Electric Heaters Installer's Guide for additional information. On a call for heat, power from the comfort control is received at "W1," which energizes the "AH" contactor coil. The "AH" contactor closes, powering the heater provided all element limits are closed. If two stages of heat are provided and additional heat is required, the comfort control's second stage "W2" circuit is energized powering the "BH" contactor coil.

Note: The comfort control must be configured to provide a “G” signal to energize the indoor fan during the heating mode.

Table 1. Pressure Drop for Electric Heater

AIRFLOW CFMNUMBER OF RACKSAIR PRESSURE DROP INCHES W.G.
12
600.003-
800.004-
1000.005.007
1200.006.008
1400.007.009
1600.008.01
2000.01.02

From Dwg. No. 21A730642

Indoor Fan Performance (230v)

A5PA3042A1 - External Static Pressure (IN.WG) Horizontal Airflow [Cooling Down Airflow]

Motor SpeedEXTERNAL STATIC PRESSURE (IN.WG)
0.00.10.20.30.40.50.60.70.80.91
Watts224 [228]233 [238]242 [247]252 [257]262 [267]------
LOWCFM1358 [1345]1393 [1379]1348 [1334]1296 [1283]1253 [1241]------
Watts306 [312]316 [322]327 [333]337 [344]348 [354]359 [366]369 [377]382 [389]395 [403]--
MED-LOW(a)CFM1521 [1506]1490 [1475]1448 [1433]1391 [1377]1362 [1348]1338 [1325]1315 [1302]1307 [1293]1254 [1241]--
Watts----455 [464]467 [477]477 [487]490 [499]503 [513]513 [523]-
MED-HIGHCFM----1529 [1514]1491 [1476]1467 [1453]1425 [1411]1385 [1371]1345 [1331]-
Watts----490 [499]502 [511]514 [523]527 [536]540 [550]554 [564]568 [578]
HIGHCFM----1533 [1518]1505 [1490]1476 [1461]1447 [1433]1415 [1401]1383 [1369]1347 [1334]

Note: Airflow must not exceed 1575 CFM due to condensate blowoff.

(a) Factory Default Setting.

Charging in Cooling above 55°F OD Ambient

If servicing the equipment requires system evacuation, then re-charge the system to the weight specified on the nameplate. Verify the system subcooling using the Subcooling Charging Table and, if necessary, adjust the charge using the procedure below.

  1. For best results -- the indoor temperature should be kept between 70°F to 80°F. Add system heat if needed.
  2. Whenever charge is removed or added, the system must be operated for a minimum of 20 minutes to stabilize before accurate measurements can be made.
  3. Measure Liquid Line Temperature and Refrigerant Pressure at service valved in the compressor compartment.
  4. Locate your liquid line temperature in the left column of the table, and the intersecting liquid line pressure under the subcool value column, Add refrigerant to raise the pressure to match the table, or remove refrigerant to lower the pressure. Again, wait 20 minutes for the system conditions to stabilize before adjusting charge again.

Note: System charge shall never be more than 110% or less than 90% of nameplate charge. If specified subcooling cannot be achieved within those charge bounds, contact your Field Service Representative.

5. When system is correctly charged, you can refer to System Pressure Curves to verify typical performance.

CHARGING BELOW 55°F

Evacuate system and weigh in nameplate charge or use factory charge. Correct subcooling may be verified when the temperature is above 55°F.

R-454B REFRIGERANT CHARGING CHART

LIQUID TEMP (°F)DESIGN SUBCOOLING (°F)
67891011121314
LIQUID GAGE PRESSURE (PSI)
55164167170172175178181184187
60178181184187190194197200203
65193197200203206210213217220
70210213217220223227230234238
75227230234238241245249252256
80245249252256260264268272276
85264268272276280284288292297
90284288292297301305309314318
95305309314318323327332336341
100327332336341346351355360356
105351355360365370375380385390
110375380385390396401406412417
115401406412417422428433439445
120428433439445450456462468474
125456462468474480486492498504

Wiring Diagrams

Figure 2. A5PA3042 - Control Box and Components

This diagram illustrates the electrical connections within the control box of the A5PA3042 unit. It shows the layout of components such as the compressor (CPR), outdoor fan motor (ODM), indoor fan motor (IDM), contactors (CC, AH, BH), transformer (TNS), and various safety switches (HI_TEMP.SW, LPCO, HPCO). It also details low voltage wiring connections to a thermostat and the refrigerant leak detection and mitigation control board, including LED status indicators.

Figure 3. A5PA3042 - System Wiring Schematic

This is a detailed wiring schematic for the A5PA3042 unit, showing factory wiring for 230V and modifications for 208V operation. It depicts the connections between the unit factory wiring, thermostat, optional start kit, compressor, outdoor fan motor, indoor fan motor, electric heater components (AH, BH), and control board. It includes important notes regarding conductor types, voltage limitations, and fuse replacement.

Legend

DEVICE DESIGDESCRIPTIONLINE NUMBER
A2L SRA2L SENSOR28
AH, BHCONTACTOR, ELECTRIC HEATER27
CCCONTACTOR13,30
CFIOUTDOOR FAN CAPACITOR12
CPRCOMPRESSOR
CRCOMPRESSOR RUN CAPACITOR12
FUFUSE25
HHEATER RELAY27,33
HI-TEMP-SWHIGH TEMPERATURE SWITCH29
HPCOHIGH-PRESSURE CUTOFF30
IDMINDOOR MOTOR18,36
LPCOLOW-PRESSURE CUTOFF30
ODMOUTDOOR MOTOR15
PPMHEATER PLUG27,28
TNSTRANSFORMER, 208/230V 24V22
IOLINTERNAL OVERLOAD
CNCONNECTOR AND WIRE NUT9

WIRE COLOR DESIGNATION: ABBR COLOR ABBR COLOR ABBR COLOR BK BLACK PR PURPLE GR GREEN BL BLUE RD RED YL YELLOW BR BROWN WH WHITE OR ORANGE

Refrigerant Circuits

Diagram of Refrigerant Flow

This diagram illustrates the refrigerant circuit of the unit. It shows the path of the refrigerant through the indoor coil, expansion valve, compressor, equalizer line, liquid line, drier, and outdoor coil. Arrows indicate the direction of refrigerant flow. Key components like Schrader valves (LO, HI), LPCO, HPCO, and the expansion valve bulb are labeled.

Troubleshooting Chart

P-Primary Causes / S-Secondary Causes

This chart helps diagnose system faults by listing common issues and their potential primary (P) or secondary (S) causes related to the refrigerant circuit and electrical systems.

SYSTEM FAULTSPower SupplyHigh Voltage WiringCompr. IOLRun CapacitorStart capacitorStart RelayContactor ContactsLow Voltage WiringControl TransformerContactor CoilLow Voltage FuseStuck CompressorIneffecient CompressorRefrigerant UnderchargeRefrigerant OverchargeExcessive Evap. LoadNoncondensablesRestricted O.D. AirflowO.D. Air RecirculationTXV Stuck OpenLow SuperheatHigh SuperheatRestricted I.D. AirflowRef. Circuit RestrictionsMitigation System
REFRIGERANT CIRCUIT
Liquid Pressure too HighPSSS
Liquid Pressure too LowPSS
Suction Pressure too HighSPSSP
Suction Pressure too LowSSPSS
Liquid Refrigerant Floodback (TXV System)PSPS
I.D. Coil FrostingPSSPS
Compressor Runs Inadequate or No CoolingPSPSSPPSSSSPSSSSSSSPP
ELECTRICAL
Compressor & O.D. Fan Do Not StartPPSSPPPPP
Compressor will not Start but O.D. Fan RunsPSPPPS
O.D. Fan will Not StartPP
Compressor Hums but will Not StartPPPPSS
Compressor Cycles on IOLPSPPPSPSPSSSSSSSS
I.D. Blower willnot StartPSSPP

MCB Code Table

ConditionGreen LEDAmber LED
Idle or OffOffOff
StartupOnOn
No Active AlarmSlow FlashOn
Active Alarm (Refrigerant Leak, Sensor Communication Error, or Sensor Error)3 FlashOn
Past Refrigerant Detected Alarm4 FlashOn
Past Sensor Communication Error5 FlashOn
Past Sensor Error6 FlashOn

Important Product Information

Unit Details

Packaged Unit Serial Number: _________________________

Packaged Unit Model Number: _________________________

Date of Installation: _________________________

Dealer: _________________________

Service Information

Call your installing dealer if the unit is inoperative. Before you call, always check the following to be sure service is required:

  1. Be sure the main switch that supplies power to the unit is in the ON position.
  2. Replace any burned-out fuses or reset circuit breakers.
  3. Be sure the thermostat is properly set.

Service Phone: _________________________

About Trane and American Standard Heating and Air Conditioning

Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com.

Certifications

AHRI Certified®: Unitary Small AC, AHRI Standard 210/240. Certification applies only when the complete system is listed with AHRI. For verification, go to ahridirectory.org.

UL Listed: cULus Listed mark.

Manufacturer Information

The manufacturer has a policy of continuous data improvement and reserves the right to change design and specifications without notice. They are committed to using environmentally conscious print practices.

Document Supersedes

Supersedes (New), Dated: 13 Sep 2024

Models: A5PA3042A1, RF110460, RF110460 24 Inch Conditioner Single Packaged Cooling Electric Heat, 24 Inch Conditioner Single Packaged Cooling Electric Heat, Single Packaged Cooling Electric Heat, Packaged Cooling Electric Heat, Electric Heat, Heat

File Info : application/pdf, 16 Pages, 827.06KB

PDF preview unavailable. Download the PDF instead.

RunTru Service Facts A5PA3042A

References

PTC Arbortext Publishing Engine PDFlib PDI 9.2.0 (C /Win64); modified using iText 2.1.7 by 1T3XT

Related Documents

Preview Trane Single Packaged Heat Pump Installation, Operation, and Maintenance Manual (2-5 Ton, R-454B)
Comprehensive guide for installing, operating, and maintaining Trane's 2-5 Ton Single Packaged Heat Pump units (R-454B). Covers safety, specifications, installation, startup, maintenance, troubleshooting, and performance data.
Preview Trane Foundation™ Packaged Rooftop Units: Installation, Operation, and Maintenance Guide
Comprehensive guide for Trane Foundation™ Packaged Rooftop Units (15-25 Tons, Cooling Only with Electric Heat). Covers installation, operation, maintenance, safety warnings, and technical specifications for models like EDK180-300.
Preview Trane 4WCA4048C1000A Single Packaged Heat Pump Submittal Specifications
Detailed submittal specifications for the Trane 4WCA4048C1000A Single Packaged Heat Pump, including product dimensions, performance data, mechanical specifications, and accessories.
Preview Trane & American Standard Priority Series Packaged Gas/Electric HVAC Units: Installation, Operation, and Maintenance Manual
Comprehensive guide for Trane and American Standard Priority Series 2-5 Ton Packaged Gas/Electric HVAC units (R-454B refrigerant). Covers installation, operation, maintenance, safety, and specifications for models like 5YCZ5024A, 5YCZ5030A, 5YCZ5036A, 5YCZ5042A, 5YCZ5048A, and 5YCZ5060A.
Preview Trane Precedent Standard Efficiency Packaged Heat Pumps: Quick Reference Guide (3-10 Tons)
Quick reference guide for Trane Precedent™ Standard Efficiency packaged heat pumps, covering models from 3 to 10 tons. Includes performance data, electrical specifications, fan data, dimensional information, and factory-installed options.
Preview Trane 4TCA4060C Single Packaged Cooling/Electric Heat Specifications and Outline Drawings
Detailed specifications, product information, and outline drawings for the Trane 4TCA4060C Single Packaged Cooling/Electric Heat unit, including technical data, dimensions, and performance characteristics.
Preview Trane 4WCA4036C1000A Single Packaged Heat Pump Submittal and Specifications
Detailed submittal and technical specifications for the Trane 4WCA4036C1000A Single Packaged Heat Pump. This document covers performance data, dimensions, electrical requirements, and features for residential HVAC applications, highlighting its 3-ton capacity and 13.4 SEER2 efficiency.
Preview Trane TSC060G4R0A001S Packaged Cooling and Heat Pump Parts List and Model Description
Explore the Trane TSC060G4R0A001S packaged cooling and heat pump system with this detailed parts list and model number breakdown. Find component diagrams, part numbers, and configuration specifics for Trane HVAC units.