SDP2500 Differential Pressure Transmitter
Installation Instructions
Issued 19.01.2023 | Rev.2
Application
The SDP2500 is a differential pressure transmitter featuring 8 selectable ranges and a 0-10 V output. It is designed for monitoring differential pressure in air and other non-flammable, non-aggressive gases. Applications include monitoring air filters, fans, industrial cooling air cycles, overheating protection, and control of air and fire damper actuators. The device can be screw-mounted onto a flat surface or prepared for mounting on a DIN rail TS35 (35x7.5 mm) according to EN 60715.
(Image description: The transmitter unit is shown, featuring two enclosures. One enclosure has a transparent cover, revealing internal components. The unit is designed for mounting on flat surfaces or DIN rails.)
(Link: Solution Navigator)
Security Advice
Installation and assembly of electrical equipment should only be performed by authorized personnel.
The product must only be used for its intended application. Unauthorized modifications are prohibited.
The product must not be used with equipment that could, in case of failure, directly or indirectly threaten human health or life, or endanger human beings, animals, or assets.
Ensure all power is disconnected before installing. Do not connect to live/operating equipment.
Please comply with:
- Local laws, health & safety regulations, technical standards, and regulations.
- The condition of the device at the time of installation to ensure safe installation.
- This data sheet and installation manual.
Before mounting, commissioning, and operation, ensure the correct pressure gauge has been selected regarding measuring range, design, and suitable wetted medium for the specific measuring conditions. Pressure gauges should only be installed and maintained by qualified personnel authorized by the plant operator. Failure to comply with applicable regulations may result in serious personal injury and/or property damage.
Notes on Disposal
As a component of a large-scale fixed installation, JCI products are intended for permanent use as part of a building or structure at a pre-defined location. Therefore, the Waste Electrical and Electronic Act (WEEE) is not applicable. However, most products may contain valuable materials that should be recycled and not disposed of as domestic waste. Please observe relevant local disposal regulations.
EU Conformity
Johnson Controls, Inc. declares that these products comply with the essential requirements and other relevant provisions of the EMC Directive and RoHS Directive.
(Logos: CE, UKCA)
Enclosure with UV and Weather Protection
Outdoor mounted plastics can lose color and quality over time. Therefore, all hinged cover enclosures are made of special white polycarbonate (PC). Light-stable colorants and additives are used to achieve optimum polymer protection while maintaining color stability. The titanium dioxide used is specifically developed for polycarbonate and offers excellent UV protection by reflecting the entire light spectrum, including the UV component around 340 nm. This effectively counteracts photochemical polymer degradation. Colors remain stable and do not fade for a long time. The material is also resistant to cold and frost.
Technical Specifications
Models and Outputs
Model | Analogue Output |
---|---|
SDP2500-R8 | 0..10V |
SDP2500-R8-AZ | 0..10V, AZ |
SDP2500-R8-D | 0..10V, with LCD |
SDP2500-R8-AZ-D | 0..10V, AZ, with LCD |
SDP2500-C4-AZ-D | 0..10V, AZ, with LCD, Calibration certificate - 0, 250, 500Pa |
SDP2500-C5-AZ | 0..10V, AZ, Calibration certificate - 0, +500, +1000Pa |
SDP2500-C5-AZ-D | 0..10V, AZ, with LCD, Calibration certificate - 0, +500, +1000Pa |
SDP2500-C6-AZ-D | 0..10V, AZ, with LCD, Calibration certificate - 0, +750, +1000Pa |
SDP2500-C8-AZ | 0..10V, AZ, Calibration certificate - 0, +1250, +2500Pa |
General Specifications
Parameter | Value |
---|---|
Power supply | 15..24 V = (±10%) or 24 V ~ (±10%) SELV |
Power consumption | typ. 1.1 W (24 V =) | 1.7 VA (24 V ~) |
Measuring range pressure | -100..+100 | 0..+100 | 0..+250 | 0..+500 | 0..+1000 | 0..+1500 | 0..+2000 | 0..+2500 Pa (default) |
Analogue output | 0..10 V, min. load 10 kΩ |
Accuracy pressure | Deviation compared to reference device: Measuring range ≤500 Pa: ±5 Pa, Measuring range >500 Pa: ±10 Pa |
Max. working overpressure | 400 kPa |
Display | LCD 37.5x31.6 mm, measured values: Pa |
Enclosure | Hinged cover enclosure, PC, pure white (with LCD, transparent cover) |
Protection | IP54 according to EN 60529, IP65 with bolted cover |
Cable entry | M20 for cable max. Ø=8 mm, seal insert for double cable entry for wire max Ø=6 mm |
Connection electrical | Terminal block, max. 1.5 mm² |
Ambient condition | -10..+50 °C, max. 85% rH, short term condensation |
Storage condition | -30..+70 °C, max. 85% rH, short term condensation |
Mounting
Before installing the device, please check all pressurized tubes for tightness.
AZ - Automatic Zero-Point Calibration (optional)
Initial Power ON: Upon initial power-up, the Auto-zero reset is performed multiple times within intervals shorter than 10 minutes (unlike normal operation). This compensates for the sensor and PCB self-heating after startup, ensuring accurate measurements. After approximately 30 minutes, the device enters full operational mode.
Transmitters equipped with automatic zero-point correction are maintenance-free.
The auto-zero calibration electronically adjusts the transmitter to zero every 10 minutes. This function eliminates output signal drifts caused by thermal, electronic, or mechanical effects. The auto-zero adjustment takes approximately 4 seconds, after which the device returns to normal operation. During the 4-second correction phase, output and display values freeze to the last measured value. After correction, display values and output signal resume live mode.
Connection and Configuration
Connection
Terminal Connections:
- 1: UB+ (Power supply 24V)
- 2: GND (Ground)
- 3: AOU1 (Analog output 0..10 V)
(Diagram description: A block diagram showing terminal connections labeled UB+, GND, and AOU1. It also indicates a power LED status indicator and a button for manual zero point correction.)
DIP Switch Settings
DIP 1-3: Measuring Ranges
DIP 1 | DIP 2 | DIP 3 | Range |
---|---|---|---|
OFF | OFF | OFF | 0..+2500 Pa (default setting) |
ON | OFF | OFF | 0..+2000 Pa |
OFF | ON | OFF | 0..+1500 Pa |
ON | ON | OFF | 0..+1000 Pa |
OFF | OFF | ON | 0..+500 Pa |
ON | OFF | ON | 0..+250 Pa |
OFF | ON | ON | 0..+100 Pa |
ON | ON | ON | -100..+100 Pa |
DIP 4: Response Time
DIP 4 | Response time |
---|---|
OFF | 4 s (default setting) |
ON | 10 s |
DIP 5: Display Settings
DIP 5 | LCD Backlight |
---|---|
OFF | Backlight OFF |
ON | Backlight ON (default setting) |
Dimensions
Dimensions are provided in millimeters (mm):
Overall Unit: Width: 90 mm, Height: 77 mm, Depth: 52 mm.
Mounting Cutout/Panel Depth: Width: 88 mm, Height: 52 mm.
(Diagram description: Three views of the transmitter unit showing its external dimensions. One view is a side profile, another is a top/front view showing mounting holes and connections, and a third is a detailed view of the connection terminals and DIP switches.)
To achieve IP 65 protection according to EN 60529, the cover must be bolted at the designated location, for example, using a 3.5x10 mm screw according to EN 7981.
Manual Zero-Point Correction
1 - Status (Power LED): Indicates device power status.
2 - Button for manual zero point correction: It is recommended to perform manual zero-point correction every 12 months during normal operation.
Attention: The power supply must be connected for at least one hour before performing manual zero-point correction.
- Remove both connection tubes from the pressure terminals '+' and '-'.
- Press the button until the LED lights up permanently.
- Wait until the LED flashes again and reinstall the connection tubes to the pressure terminals, observing the '+' and '-' polarity.
Contact Information
UK Single Point of Contact
Johnson Controls
TYCO Park
Grimshaw Lane
MANCHESTER M40 2WL
United Kingdom
EU Single Point of Contact
Johnson Controls
Voltaweg 20
6101 XK Echt
The Netherlands
APAC Single Point of Contact
JOHNSON CONTROLS
C/O CONTROLS PRODUCT MANAGEMENT
NO. 32 CHANGJIANG RD NEW DISTRICT
WUXI JIANGSU PROVINCE 214028
CHINA
Website: www.johnsoncontrols.com
Locations: www.johnsoncontrols.com/locations
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls. All other marks herein are the marks of their respective owners. © 2023 Johnson Controls.