Airmaster AMX 4: Operation and Maintenance
This manual provides comprehensive instructions for the safe and efficient operation and maintenance of the Airmaster AMX 4 decentralized ventilation system.
Introduction
This manual is intended for both general users who operate the system via Local Web Tool or Airlinq® Online, and for trained personnel performing maintenance on the unit. It should be read thoroughly before operating or maintaining the AMX 4 system. Keep this manual for future reference and pass it on to the system's owner.
The AMX 4 system is a decentralized ventilation unit for indoor use, suitable for office environments and modular buildings. It provides ventilation, cooling, and heating within a single unit.
Safety Instructions
WARNING: Failure to comply with instructions marked with a warning symbol may result in personal injury or material damage.
- FIRE HAZARD: The unit contains R290 (propane), a highly flammable substance. Do not expose to heat, sparks, or open flames.
- ELECTRICAL HAZARD: Electrical work on the AMX 4 must only be performed by an authorized electrician or Airmaster A/S.
- REPAIR HAZARD: Repairs must be carried out by authorized experts. Contact Airmaster A/S or your local representative.
- ELECTRICAL SAFETY: Never open the bottom panels before disconnecting the unit's power supply. Ensure no one can turn on the power while service work is in progress.
- OPERATIONAL SAFETY: Do not start the unit until all bottom panels are closed.
- FILTER REQUIREMENT: The unit must not be operated without the filters specified in this manual (see section 4.3.1).
CAUTION: Maintenance according to this manual can be performed by the end-user, but service, repair, or improvements must be carried out by authorized experts. Contact Airmaster A/S or your local representative.
Note: Laypersons should not perform maintenance on the AMX 4 system.
Product Identification
Product Name: AMX 4
Article Number: 9500004001
Type: Decentralized ventilation system
Specifications:
- Capacity (30 dB(A)): 256 m³/h
- Weight (complete unit excl. panels): 232 kg
- Weight (panels): 6 kg
- Weight (bottom plates, 3 pcs.): 24 kg
- Dimensions (W x H x D): 2055 x 358 x 1100 mm
- Cabinet Color: RAL 9005 (deep black)
- Panel and Bottom Plate Color: RAL 9010 (pure white)
- Supply Voltage: 220-240V/50Hz, ~1N+PE
- Duct Connection: 2 x Ø200 mm
- Sound Pressure Level: <70 dB(A)
- IP Classification: IP10
Refer to the datasheet for AMX 4 for further information, available on the Airmaster website.
Intended Use
The AMX 4 is designed for indoor use in office environments and modular buildings, providing ventilation, cooling, and heating.
Unintended Use: The unit is not intended for operation by persons (including children) with reduced physical, sensory, or cognitive capabilities, or lack of experience and knowledge, unless supervised or instructed by a responsible person.
Filter Classes
Filter Type | Standard Filter | Optional |
---|---|---|
Supply air filter, fine | ePM10 50% | ePM1 55% or ePM1 80% |
Exhaust air filter, fine | ePM10 50% | - |
Supply air filter, coarse | ISO coarse 30% (PPI) | - |
Contact Airmaster A/S or your local representative for purchasing and further information.
Manufacturer
Airmaster A/S
Industrivej 59
9600 Aars
Denmark
Phone: +45 9862 48 22
Email: info@airmaster.dk
Website: www.airmaster.dk
Operation
Operation of the AMX 4 can be done in two ways:
- Via Local Web Tool
- Via Airlinq® Online
Both tools allow you to control, monitor, and manage the unit. The Local Web Tool is part of the standard delivery, while Airlinq® Online is optional.
Local Web Tool with Internet Access
The Local Web Tool has four user profiles: 'viewer', 'basic', 'technical', and 'advanced'. Access the unit by entering its IP address in a browser. Log in with your user profile and password.
User Profile | Menus |
---|---|
viewer | Settings, Status, Graphs |
basic | Settings, Status, Graphs, Service, Override |
technical | Settings, Status, Graphs, Service, Override, Firmware |
advanced | Settings, Status, Graphs, Service, Override, Firmware, Network |
Local Web Tool without Internet Access
If you do not have internet access, the AMX unit can function as a Wi-Fi access point. Turn off the unit, wait 10 seconds, then turn it on. Search for available Wi-Fi networks; the unit will appear as AM-xxxxxxxxx (where x is the serial number). Connect to it using the password 'fresh_air'. The Local Web Tool will open automatically. Log in with one of the four user profiles.
Airlinq® Online
Airlinq® Online is a professional web portal for Airmaster systems connected via Ethernet. It is designed to control, monitor, and manage ventilation solutions. Access Airlinq® Online via a smartphone, tablet, or PC without installing any software. You need internet access via your web browser. After activating your access via the invitation email, go to https://online.airling.eu/ and log in.
LED Signals
The AMX 4 is equipped with an LED indicating the system's operating status. The LED is located on the back, right side of the unit.
Color | Light | Status | Meaning |
---|---|---|---|
Blue | Blinking | Booting phase | Indicates the unit is in the booting phase (up to 5 minutes). If blinking continues beyond 5 minutes, contact Airmaster for assistance. |
Blue | Solid | Startup phase | Indicates the unit has completed startup and is in the startup phase (up to 30 minutes). The light will turn solid green upon completion. |
Blue/Green | Blinking | Test mode | The unit is in test mode. |
Green | Blinking | Inactive | Indicates the unit is inactive but ready for operation according to configured parameters. |
Green | Solid | In operation | Indicates the unit is operating according to configured parameters. |
Green/Red | Blinking | Warning | Indicates a problem that the unit cannot resolve. Operation may continue with limited functionality or reduced capacity. |
Red | Blinking | Propane alarm | Indicates detected propane in the unit. The unit will ventilate to the outside and stop. |
Red | Solid | Alarm | Indicates an alarm. The unit will stop and can only be restarted once the problem is resolved. |
Control Functions
The AMX 4 system combines ventilation and recirculation with heating or cooling.
- Ventilation + Cooling
- Ventilation + Heating
- Recirculation + Cooling
- Recirculation + Heating
Boost Function
The Boost function temporarily changes the airflow. When activated, the unit automatically adjusts the supply and exhaust fans according to pre-programmed values. The standard boost period is 30 minutes with 100% airflow, after which the unit returns to normal operation. The boost period length can be adjusted via Local Web Tool or Airlinq® Online.
CO2 Sensor
The built-in CO2 sensor controls the system based on indoor air quality. If the CO2 level exceeds 400 ppm, the unit adjusts the airflow. When the CO2 level drops below 400 ppm, the unit returns to normal operation.
Propane Sensor
The unit is equipped with a propane sensor that monitors for leaks in the heat pump circuit. If propane is detected, the unit initiates a ventilation procedure to expel the propane safely. An alarm is simultaneously sent to the control system. After the ventilation procedure, the unit stops and can only be restarted after inspection/repair. The propane sensor continues to monitor the unit; if propane is still present, the ventilation procedure is repeated.
External Start (Optional)
An external start function is available as an option, allowing connection to an external start contact. This contact should be a 'sealed potential-free contact' with silver/gold contacts for small signals.
Adjustment of Supply Air Louvers
The supply air louvers can be adjusted to control the throw (length) and spread of the supply air. The louvers are located behind the grille.
Adjusting Louver Angles:
- Standard Spread and Throw: Louvers set for a 45° angle.
- Narrow Spread and Long Throw: Outer louvers on both sides are closed to achieve a longer throw.
- Wide Spread and Short Throw: Outer louvers on both sides are set at a lower angle than the middle louvers.
- Asymmetrical Throw: One side has a smaller louver angle than the other to create asymmetry.
Use a long-nosed pliers to adjust the louvers, being careful as they can break if bent too many times.
Maintenance
Maintenance Plan
Task | Frequency |
---|---|
Exterior Cleaning | Depends on the local environment. Clean the unit regularly. Refer to section 9.3.1. |
Condensate System Check and Cleaning | Clean and check the condensate system at least every 12 months. If filters are replaced more often than every 12 months, check and clean the condensate system at the same time. Refer to section 9.3.3. |
Filter Replacement | Replace filters when the system indicates, and at least every 14 months. Comply with any deviating local regulations. Refer to section 9.2. |
Interior Cleaning | Clean the unit internally when replacing filters, at least every 14 months. Refer to section 9.3.2. |
Filter Replacement
WARNING: Wear safety glasses, disposable gloves, and a face mask when replacing filters.
CAUTION: Used filters must be disposed of immediately after removal from the unit. Store used filters in a dust-proof bag.
NOTE: Used filters must be disposed of according to their contamination (waste code 1502 for particles, 150203 for atmospheric particles, or 150202 for 'hazardous' substances).
NOTE: All filters must be replaced. Do not attempt to wash or vacuum them. The AMX 4 has two filters on the intake side and two on the exhaust side, each with a coarse and a fine filter.
Replacing Exhaust Air Filters
- Open the bottom plate on the right side of the unit using the provided key.
- Open the filter cover.
- Open the hinges holding the coarse filter in place.
- Remove the filter and replace it with a new one.
- Close the coarse filter hinges.
- Open the hinge holding the fine filter in place.
- Remove the filter and replace it with a new one. Note the arrow marking on the bottom of the fine filter; this arrow should point towards the center of the unit.
- Close the fine filter hinge.
- Close the filter cover.
- Close the bottom plate.
This completes the exhaust filter replacement. Proceed to replace the supply air filters.
Replacing Supply Air Filters
Follow the instructions in section 9.2.1, "Replacing Exhaust Air Filters", but on the left side of the unit. Refer to Figure 20, Figure 21, and Table 7.
After replacing the filters, reset the filter service indicator (see section 9.2.3).
Filter Service Reset
The standard code for resetting the filter service is 9732. Filter reset is performed either in the Local Web Tool or Airlinq® Online.
Cleaning the Unit
Regular cleaning ensures error-free operation. This section provides guidelines for both exterior and interior cleaning.
Exterior Cleaning
CAUTION: The unit must be switched off before cleaning.
Use a soft, damp cloth to remove dust and dirt. Do not use aggressive cleaning agents like turpentine; use clean water or water with a mild detergent. The space between the unit and the wall/ceiling can be dusted with a dust cloth or a vacuum cleaner with a soft brush attachment. The exhaust grille and ventilation openings should be cleaned regularly, preferably by vacuuming with a soft nozzle.
Interior Cleaning
CAUTION: The unit must be switched off and disconnected from the mains before opening the bottom plates. Ensure no one turns on the power.
Use a vacuum cleaner or a soft brush to remove dust and dirt from the unit. Pay special attention to cleaning the heat exchanger and fans.
Condensate System
CAUTION: The unit must be switched off and disconnected from the mains before opening the bottom plates. Ensure no one turns on the power.
You must remove the bottom plates and the lower steel plates to access the condensate system (see section 7 in the installation manual).
Cleaning
The condensate system consists of three parts. The middle part collects liquid from the other two. You must clean and check all three parts.
- Disconnect the condensate tray at the rear of the unit by unscrewing the bolts. Cut and remove the cable tie holding the condensate hose.
- Clean the tray, drain, and hoses. Ensure there are no obstructions in the drain or hose. If you remove the hose, secure it again with a suitable hose clamp.
- Reassemble the tray.
- Repeat for the tray at the front of the unit.
- Disconnect the middle tray.
- Clean the tray, drain, and hoses. Ensure there are no obstructions and secure the hoses if removed.
- Refer to Figure 23: Clean the condensate pump if necessary with a damp cloth. There are two pumps, one on each side of the middle tray.
- Reassemble the middle tray.
- Perform a check (see section 9.3.3.2).
- Once the check is satisfactory, reassemble the lower steel plates and bottom plates. Remember to insert a new cable tie to secure the condensate hose; it must not hang loosely.
- Turn on the unit.
Check
Pour approximately 1.5 liters of water into the condensate tray at the rear of the unit. The water drains into the middle tray by gravity. Check that this occurs and check for leaks. Repeat for the tray at the front of the unit, ensuring water drains to the middle tray and checking for leaks. To check the condensate pumps in the middle tray, briefly turn on the power and check that water is pumped out and that there are no leaks.
Service/Repair
For service or repair, contact Airmaster A/S or your local representative. Contact information for Airmaster can be found in section 4.4 on page 10.
Disassembly and Disposal
Disassembly
To disassemble the AMX 4 unit, follow the instructions in the installation and mounting manuals in reverse order:
- Mounting Manual: Section 7
- Installation Manual: Sections 7 and 8
Refer to the mounting manual for information on transport and storage if you need to move or store the unit.
Disposal
NOTE: The AMX 4 unit contains R290 (propane) and oils. Disposal must be carried out by authorized professionals in accordance with local legislation and regulations. The unit must not be disposed of as household waste.
NOTE: Electrical and electronic equipment (EEE) contains materials, components, and substances that can be hazardous and pose a risk to human health and the environment if WEEE is not handled correctly. Disposal must be carried out by authorized professionals in accordance with local legislation and regulations. The unit must not be disposed of as household waste.
Product information according to Regulation (EU) No 1253/2014, Annex IV – Information requirements for residential ventilation units as referred to in Article 4(1) can be found on our website. It contains a description of the necessary tools and procedures for manual disassembly for efficient material recycling. Go to Downloads/Approvals and select 'Demontage'.
Appendix A: EU Declaration of Conformity
Airmaster A/S hereby declares that the following ventilation unit (series and type (serial numbers)) AMX 4 (404000001 - 404099999) is in conformity with the following directives, regulations, and standards:
- 2006/42/EC – Machinery Directive
- 2014/30/EU – Electromagnetic Compatibility
- 2011/65/EU – Restriction of Hazardous Substances in Electrical and Electronic Equipment
The unit complies with:
- Regulation (EU) 626/2011 concerning the energy labelling of air conditioners.
- Regulation (EU) 206/2012 implementing Directive 2009/125/EC regarding ecodesign requirements for air conditioners and comfort fans.
- Regulation (EU) 1253/2014 implementing Directive 2009/125/EC regarding ecodesign requirements for ventilation units.
Relevant standards include EN 60335-1:2012, EN 60335-2-40:2003, EN 378-2:2016, and DS 469.
Reservation: This declaration is void if modifications are made to the ventilation unit or its equipment (supplied by the manufacturer) without the manufacturer's written approval.
Place: Aars
Date: 2024-01-25
Signed: Jesper Mogensen, CTO
Related Documents
![]() |
AirMaster AM 950 F SSL Technical Specifications and Dimensions Detailed technical specifications, dimensions, and connection information for the AirMaster AM 950 F SSL ventilation unit. Includes multilingual terminology for key components. |
![]() |
AIRMASTER AM 500 Datablad: Teknisk Information og Ydeevnedata Detaljerede tekniske specifikationer, ydeevnedata, og funktioner for AIRMASTER AM 500 luftbehandlingsaggregat, inklusive kapacitet, lydniveauer og energieffektivitet. |
![]() |
Airmaster CC150 Ventilation Unit Technical Drawings and Specifications Detailed technical drawings and contact information for Airmaster ventilation units, including the CC150 model. Provides an overview of components and multilingual terminology for ventilation functions. |
![]() |
Airmaster AMX4: Advanced All-in-One Ventilation, Heating, and Cooling System Discover the Airmaster AMX4, a revolutionary all-in-one indoor climate solution that integrates ventilation, heating, and cooling. Learn about its energy efficiency, advanced control features, quiet operation, and seamless integration for optimal comfort. |
![]() |
Airmaster AMX4 : Système Tout-en-un de Ventilation, Chauffage et Refroidissement Découvrez l'Airmaster AMX4, une solution révolutionnaire tout-en-un pour la ventilation, le chauffage et le refroidissement. Offre une efficacité énergétique, un confort optimal et un contrôle intelligent pour votre climat intérieur. |
![]() |
Airmaster AM1000 HH TB Smoke Detector Technical Drawings and Specifications Detailed technical drawings, dimensions, and component terminology for the Airmaster AM1000 HH TB Smoke detector. Includes contact information for Airmaster and its global distributors. |
![]() |
Airmaster AM 950 C / AM 950 F Operation & Maintenance Manual Comprehensive operation and maintenance guide for Airmaster AM 950 C and AM 950 F air handling units. Covers safety instructions, control functions, LED signals, internal control functions, and service procedures. |
![]() |
AIRMASTER AM 1200 V Technical Data Sheet with Ø315 Top Hat Module Comprehensive technical specifications and performance data for the AIRMASTER AM 1200 V ventilation unit, featuring the Ø315 top hat module. Includes airflow capacities, sound pressure levels, thermal efficiency, power consumption, and installation options. |