Installation Guide for RLE models including: TH140 Temperature And Humidity Sensor, TH140, Temperature And Humidity Sensor, Humidity Sensor

11x17 Blank Title Block

rstelzer

PDF FMS to TH140/TH140D Integration - RLE Technologies

SHEET: 1 OF 18 104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone (970) 484-6650 Fax www.rletech.com FMS Sensor Wiring Guide Rev 1-2 FMS to TH140/TH140D Integration

FMS to TH140/TH140D Integration

SHEET: 1 OF 16 104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone (970) 484-6650 Fax www.rletech.com FMS Sensor Wiring Guide 106 FMS Rev 2. (8/ 3) FMS to TH140/TH140D Integration


File Info : application/pdf, 18 Pages, 1.19MB

PDF preview unavailable. Download the PDF instead.

FMS-Sensor-Wiring-Guide-11-21
104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

TB1 VDC + -

P1 VDC

EXTERNAL

TB2 Input 1-4

24VDC + +

Ch1 + -

Ch2 + -

Ch3 + -

Ch4 + -

FMS to TH140/TH140D Integration

Ch5 + -

TB3 Input 5-8

Ch6 + -

Ch7 + -

EXTERNAL

Ch8 + -

GND - -

TB4

RELAY 1 NC NO C

RELAY 2 NC NO C

2

PWR(4-20 SEND) COMMON RH OUT (4-20 RTN) T OUT (4-20 RTN) RTD/OVERRIDE RTD/OVERRIDE SLIDER RIGHT SLIDER WIPER SLIDER LEFT

BACK PIECE

CENTER PIECE (WITH CIRCUIT BOARD)

Output Select

SW1

Volts

mA

1

RH 10/5V TEMP 10/5V

TEMP RANGE 50-95/32-122

TEMP F/C

SETUP
1. Set the switch position to mA. Set the temperature range to 50-95 or 32-122. The Sensor is shipped from the factory with the switch in the volts position and the temperature range is set for 50-95F. The switch position must be set to the mA position.
2. Wire the sensor as shown. 3. Configure the Falcon Input channel (temperature) for "Analog
4-20mA" and enter the Gain and Offset values. For the 50-95F range use Gain 11.25, Offset 38.75. For 32-122F range use Gain 22, Offset 10.
4. Configure the Falcon Input Channel (humidity) for "Analog 420mA" and enter the Gain of 25 and Offset of -25.
5. Verify the "Calc" Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page.

Figure 1.1: FMS Wiring with the TH140/TH140D

5 3

5 4

Figure 1.2: Temperature Setup 50 ­ 95 Degree F Range

Figure 1.3: Humidity Setup

TROUBLESHOOTING
1. Calculate the TH140 Output current for temperature.
Formula for calculating the correct RAW value ( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
Example if Room Temp is 70F and your sensor has a range of 50-95
( (70 - 50) / (95 - 50)) x 16 + 4 = 11.11
2. Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%)
3. If measured current current does not match calculated current then check wiring and check TH140/TH140D jumper and switch settings.
4. Compare the measured current matches the current reading in the Falcon.
5. Check the wiring if the Falcon current reading does not match the measured current reading.
6. If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.

7. If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.

8. If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.

9. Use similar troubleshooting procedure except use the following formula to calculate the humidity mA output.

mA =

Room Humidity 100

x 16 + 4

FMS Sensor Wiring Guide

SHEET: 1 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

TB1 VDC + -

P1 VDC

EXTERNAL

TB2 Input 1-4

24VDC + +

Ch1 + -

Ch2 + -

Ch3 + -

Ch4 + -

FMS to T120D Integration

Ch5 + -

TB3 Input 5-8

Ch6 + -

Ch7 + -

EXTERNAL

Ch8 + -

GND - -

TB4

RELAY 1 NC NO C

RELAY 2 NC NO C

2

PWR(4-20 SEND) COMMON RH OUT (4-20 RTN) T OUT (4-20 RTN) RTD/OVERRIDE RTD/OVERRIDE SLIDER RIGHT SLIDER WIPER SLIDER LEFT

BACK PIECE

CENTER PIECE (WITH CIRCUIT BOARD)

Output Select

SW1

Volts

mA

1

RH 10/5V TEMP 10/5V

TEMP RANGE 50-95/32-122

TEMP F/C

Figure 2.1: FMS Wiring with the T120D

SETUP
1. Set the switch position to mA. Set the temperature range to 50-95 or 32-122. The sensor is shipped from the factory with the switch in the volts position and the temperature range is set for 50-95F. The switch position must be set to the mA position.
2. Wire the sensor to the CH # being used.
3. Configure the Falcon Input channel (temperature) for "Analog 4-20mA" and enter the Gain and offset values. For the 50-95F range use Gain 11.25, Offset 38.75. For 32-122F range use Gain 22, Offset 10.
4. Verify the "Calc" value displays the correct room temperature. The temperature can also be viewed on the Falcon main page.
TROUBLESHOOTING
1. Calculate the T120D Output current for temperature.
Formula for calculating the correct RAW value ( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
Example if Room Temp is 70F and your sensor has a range of 50-95

( (70 - 50) / (95 - 50)) x 16 + 4 = 11.11

4 3
Figure 2.2: 50-95F Range Setup

4 3
Figure 2.3: 32-122F Range Setup

2. Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/1%).
3. If measured current does not match calculated current then check wiring and check T120D jumper and switch settings.
4. Compare the measured current matches the current reading in the Falcon.
5. Check the wiring if the Falcon current reading does not match the measured current reading.
6. If the Falcon current reading matches the measured current and the Falcon Calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.

FMS Sensor Wiring Guide

SHEET: 2 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

TB1 VDC + -

P1 VDC

EXTERNAL

TB2 Input 1-4

24VDC + +

Ch1 + -

Ch2 + -

Ch3 + -

Ch4 + -

FMS to HEW3MSTA Integration

Ch5 + -

TB3 Input 5-8

Ch6 + -

Ch7 + -

EXTERNAL

Ch8 + -

GND - -

TB4

RELAY 1 NC NO C

RELAY 2 NC NO C

NC TT+
RHRH+

SETUP
1. The temperature range is 50-95 degF
2. Wire the sensor as shown.
3. Configure the Falcon Input channel (temperature) for "Analog 4-20mA" and enter the Gain and Offset values. For the 50-95F range use Gain 11.25, Offset 38.75.
4. Configure the Falcon Input Channel (humidity) for "Analog 420mA" and enter the Gain of 25 and Offset of -25.
5. Verify the "Calc" Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page.

Figure 3.1: FMS Wiring with the HEW3MSTA

5 3

5 4

Temperature Signal

.

Humidity Signal

.

Figure 3.2: Temperature Setup 50 ­ 95 Degree F Range

Figure 3.3: Humidity Setup

TROUBLESHOOTING
1. Calculate the output current for temperature.
Formula for calculating the correct RAW value ( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
Example if Room Temp is 70F and your sensor has a range of 50-95
( (70 - 50) / (95 - 50)) x 16 + 4 = 11.11
2. Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%)
3. If measured current current does not match calculated current then check wiring.
4. Compare the measured current matches the current reading in the Falcon.
5. Check the wiring if the Falcon current reading does not match the measured current reading.
6. If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.

8. If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.

9. Use similar troubleshooting procedure except use the following formula to calculate the humidity mA output.

mA =

Room Humidity 100

x 16 + 4

FMS Sensor Wiring Guide

SHEET: 3 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

TB1 VDC + -

P1 VDC

EXTERNAL

TB2 Input 1-4

24VDC + +

Ch1 + -

Ch2 + -

Ch3 + -

Ch4 + -

FMS to TEAMS Integration

Ch5 + -

TB3 Input 5-8

Ch6 + -

Ch7 + -

EXTERNAL

Ch8 + -

GND - -

TB4

RELAY 1 NC NO C

RELAY 2 NC NO C

SETUP
1. The temperature range is 50-95 degF
2. Wire the sensor as shown. Orange wires are polarity independent
3. Configure the Falcon Input channel (temperature) for "Analog 4-20mA" and enter the Gain and Offset values. For the 50-95F range use Gain 11.25, Offset 38.75.
4. Verify the "Calc" Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page.

Figure 4.1: FMS Wiring with the TEAMS
5 3

Temperature Signal

.

Figure 4.2: Temperature Setup 50 ­ 95 Degree F Range

TROUBLESHOOTING 1. Calculate the output current for temperature.
Formula for calculating the correct RAW value ( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
Example if Room Temp is 70F and your sensor has a range of 50-95
( (70 - 50) / (95 - 50)) x 16 + 4 = 11.11
2. Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%)
3. If measured current current does not match calculated current then check wiring.
4. Compare the measured current matches the current reading in the Falcon.
5. Check the wiring if the Falcon current reading does not match the measured current reading.
6. If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.

FMS Sensor Wiring Guide

SHEET: 4 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

CT120/CT300/CT800/CT2400 FMS Integration

TB1 VDC + -

P1 VDC

EXTERNAL TB2 Input 1-4 24VDC Ch1 Ch2 Ch3 ++ + - + - + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

EXTERNAL

Ch6 Ch7 Ch8 GND

+ - + - + - --

TB4

RELAY 1

RELAY 2

NC NO C

NC NO C

Figure 5.1: FMS Wiring

1

2

3

-+

FMS Configuration 1. Set Input Type to an
Analog 4-20 mA Input.
2. For a 0-100 Amp setting, use a gain of 25 and an offset of -25.
3. For other settings, use the integrated gain/offset calculator.

Figure 5.2: FMS Input Configuration Interface

FMS Sensor Wiring Guide

SHEET: 5 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

PFM FMS Integration

TB1 VDC + -

P1 VDC

EXTERNAL TB2 Input 1-4 24VDC Ch1 Ch2 Ch3 ++ + - + - + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

EXTERNAL

Ch6 Ch7 Ch8 GND

+ - + - + - --

TB4

RELAY 1

RELAY 2

NC NO C

NC NO C

NO NC C

FMS Configuration
Set Input Type to a Digital NO Input type for each PFM Relay Output wired into the Falcon.

Figure 6.1: FMS Wiring

FMS Input Configuration Interface

FMS Sensor Wiring Guide

SHEET: 6 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

GD100 FMS Integration

TB1 VDC + -

P1 VDC

EXTERNAL TB2 Input 1-4 24VDC Ch1 Ch2 Ch3 ++ + - + - + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

EXTERNAL

Ch6 Ch7 Ch8 GND

+ - + - + - --

TB4

RELAY 1

RELAY 2

NC NO C

NC NO C

FMS Configuration
Set Input Type to a Digital NO

Figure 7.1: FMS Wiring

FMS Input Configuration Interface

FMS Sensor Wiring Guide

SHEET: 7 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

AFS-(WM/DM) F200 Integration

TB1 VDC + -

P1 VDC

EXTERNAL TB2 Input 1-4 24VDC Ch1 Ch2 Ch3 ++ + - + - + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

EXTERNAL

Ch6 Ch7 Ch8 GND

+ - + - + - --

TB4

RELAY 1

RELAY 2

NC NO C NC NO C

Figure 8.1: FMS Wiring

SW2
1 2 3
SW1
1
SW3

1. Set Jumper Switches on AFS-XX to appropriate

settings.

Output Selection SW1:

4-20mA Output

Working Range SW2:

0-2000 Ft/Min Range 0-3000 Ft/Min Range 0-4000 Ft/Min Range

Response Time SW3: Fast Slow

2. Set FMS Input Channel to an Analog 4-20 mA.

3. For a 0-2000 Ft/Min Range, use a gain of 500 and an offset of -500.

4. For other settings, use the integrated gain/offset calculator. FMS Configuration

2

3

4

FMS AFS-xx Input Configuration Interface

FMS Sensor Wiring Guide

SHEET: 8 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

AFS-D FMS Integration

TB1 VDC + -

P1 VDC

EXTERNAL TB2 Input 1-4 24VDC Ch1 Ch2 Ch3 ++ + - + - + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

EXTERNAL

Ch6 Ch7 Ch8 GND

+ - + - + - --

TB4

RELAY 1

RELAY 2

NC NO C

NC NO C

Figure 9.1: FMS Wiring

FMS Input Configuration Interface

FMS Configuration
Set Input Type to a NC Digital Contact for each AFS-D wired into the Falcon. Assign an on/ off label for each sensor connected.

FMS Sensor Wiring Guide

SHEET: 9 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

MD3 FMS Integration

TB1 VDC + -

P1 VDC

EXTERNAL TB2 Input 1-4 24VDC Ch1 Ch2 Ch3 ++ + - + - + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

EXTERNAL

Ch6 Ch7 Ch8 GND

+ - + - + - --

TB4

RELAY 1

RELAY 2

NC NO C

NC NO C

Supplied 12VDC Wall Adapter Power Supply

NC Contact

Figure 10.1: FMS Wiring

FMS Input Configuration Interface

FMS Configuration
Set Input Type to a Digital NC Input Type for each MD3 wired into the Falcon.

FMS Sensor Wiring Guide

SHEET: 10 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

MDS FMS Integration

TB1 VDC + -

P1 VDC

EXTERNAL TB2 Input 1-4 24VDC Ch1 Ch2 Ch3 ++ + - + - + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

EXTERNAL

Ch6 Ch7 Ch8 GND

+ - + - + - --

TB4

RELAY 1

RELAY 2

NC NO C

NC NO C

Figure 11.1: FMS Wiring

FMS Input Configuration Interface

FMS Configuration
Set Input Type to a Digital NC Input Type for each MDS wired into the Falcon.

FMS Sensor Wiring Guide

SHEET: 11 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

SMK FMS Integration

NO
COM

TB1 VDC + -

P1 VDC

EXTERNAL TB2 Input 1-4 24VDC Ch1 Ch2 Ch3 ++ + - + - + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

EXTERNAL

Ch6 Ch7 Ch8 GND

+ - + - + - --

TB4

RELAY 1

RELAY 2

NC NO C NC NO C

++-

FMS Configuration Set Input Type to a NO Digital Contact for each SMK wired into the Falcon.

Figure 12.1: FMS Wiring

FMS Input Configuration Interface

FMS Sensor Wiring Guide

SHEET: 12 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

HD150 & HD150-2 FMS Integration

TB1 VDC + -

P1 VDC

EXTERNAL TB2 Input 1-4 24VDC Ch1 Ch2 Ch3 ++ + - + - + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

EXTERNAL

Ch6 Ch7 Ch8 GND

+ - + - + - --

TB4

RELAY 1

RELAY 2

NC NO C

NC NO C

Power (White)

Low (Yellow)

High (Red)

FMS Configuration
Set Input Type to a Digital NO Input type for each HD150/HD150-2 Relay Output wired into the Falcon.

Figure 13.1: FMS Wiring

FMS Input Configuration Interface

FMS Sensor Wiring Guide

SHEET: 13 OF 18

Rev 11-21

ON 485 TERM SEL M/S
Pin 1 Pin 2 Pin 3 Pin 4 Pin 5 Pin 6 Pin 7 Pin 8

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

KPO Falcon Integration

RELAY COM1 COM2

TB4
RELAY 1 RELAY 2 NC NO C NC NO C

K1 TX TX 232

TB5 KEYPAD

IOIOI
P2 RS232
COM1

1 2

K2 RX RX 485

SW1 + - GND

COM1

SELECT

RS485 COM1 IOIOI

IOIOI
P3 RS232
COM2

P4 RJ11 P5 RJ45 TELCO NETWORK

Falcon TB5-1 Falcon TB5-2 Falcon TB5-3 Falcon TB5-4 Falcon TB5-5 Falcon TB5-6 Falcon TB5-7

Column 1

Keypad Pin 3 - Orange

Column 2

Keypad Pin 4 - Green

Column 3

Keypad Pin 5 - Grey

Row 1

Keypad Pin 1 - Red

Row 2

Keypad Pin 2 - White

Row 3

Keypad Pin 8 - Yellow

Row 4

Keypad Pin 7 - Blue

No Connection Keypad Pin 6 - Black

Figure 14.1: FMS Wiring with KPO

FMS Configuration Enter in Keypad users and corresponding codes in
the Falcon's Keypad/DTMF Access User Configuration menu.

RLE - KPO Keypad
123 456 789 * 0#

Figure 8.2: FMS Keypad Configuration Interface

FMS Sensor Wiring Guide

SHEET: 14 OF 18

Rev 11-21

GND V+ CH1 Temperature CH2 Humidity
V3.1 Copyright 2007 BAPI

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

FMS BAPI Temperature/Humidity Falcon Integration

TB1 VDC + -

P1 VDC

EXTERNAL

TB2 Input 1-4

24VDC + +

Ch1 + -

Ch2 + -

Ch3 + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

Ch6 + -

Ch7 + -

EXTERNAL

Ch8 + -

GND - -

TB4

RELAY 1 NC NO C

RELAY 2 NC NO C

SETUP
1. Wire the sensor as shown.
2. Configure the Falcon Input channel (temperature) for "Analog 4-20mA" and enter the gain and offset values. For the 32120F range use Gain 22, Offset -10.
3. For other temperature ranges, use the Calculator function on the webpage
4. Configure the Falcon Input Channel (humidity) for "Analog 420mA" and enter the Gain of 25 and Offset of -25.
5. Verify the "Calc" Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page.

1

Figure 15.1: Falcon Wiring with the BAPI Temperature/Humidity sensor

5 2
3

5 4

Temperature Setup 32 - 120 Degree F Range

Humidity Setup

TROUBLESHOOTING
1. Calculate the BAPI Output current for temperature.
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
Example if Room Temp is 70F and your sensor has a range of 32-120
( (70 - 32) / (120 - 32)) x 16 + 4 = 10.90
2. Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%)
3. If measured current current does not match calculated current then check wiring and check the BAPI switch settings.
4. Compare the measured current matches the current reading in the Falcon.
5. Check the wiring if the Falcon current reading does not match the measured current reading.
6. If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the following formula to calculate the humidity mA output.

mA =

Room Humidity 100

x 16 + 4

FMS Sensor Wiring Guide

SHEET: 15 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

FMS HW2XA2A Temperature/Humidity Integration

TB1 VDC + -

P1 VDC

EXTERNAL

TB2 Input 1-4

24VDC + +

Ch1 + -

Ch2 + -

Ch3 + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

Ch6 + -

Ch7 + -

EXTERNAL

Ch8 + -

GND - -

TB4

RELAY 1 NC NO C

RELAY 2 NC NO C

GND

SETUP
1. Wire the sensor as shown.
2. Configure the Falcon Input channel (temperature) for "Analog 4-20mA" and enter the gain and offset values. For the 32122F range use Gain 22.5, Offset 9.5.
3. For other temperature ranges, use the Calculator function on the webpage
4. Configure the Falcon Input Channel (humidity) for "Analog 420mA" and enter the Gain of 25 and Offset of -25.
5. Verify the "Calc" Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page.

Humidity
Temperature V+
Figure 16.1: Falcon Wiring with the HW2XA2A Temperature/Humidity sensor

54321

Temperature Setup 32 - 122 Degree F Range

Humidity Setup

TROUBLESHOOTING
1. Calculate the output current for temperature.
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
Example if Room Temp is 70F and your sensor has a range of 32-122
( (70 - 32) / (122 - 32)) x 16 + 4 = 10.75
2. Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%)
3. If measured current current does not match calculated current then check wiring.
4. Compare the measured current matches the current reading in the Falcon.
5. Check the wiring if the Falcon current reading does not match the measured current reading.
6. If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the following formula to calculate the humidity mA output.

mA =

Room Humidity 100

x 16 + 4

FMS Sensor Wiring Guide

SHEET: 16 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

FMS Dwyer Temperature/Humidity Falcon Integration

TB1 VDC + -

P1 VDC

EXTERNAL

TB2 Input 1-4

24VDC + +

Ch1 + -

Ch2 + -

Ch3 + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

Ch6 + -

Ch7 + -

EXTERNAL

Ch8 + -

GND - -

TB4

RELAY 1 NC NO C

RELAY 2 NC NO C

1

SETUP
1. Wire the sensor as shown.
2. Configure the Falcon Input channel (temperature) for "Analog 4-20mA" and enter the gain and offset values. For the -40 140F range use Gain 45, Offset -85.
3. For other temperature ranges, use the Calculator function on the webpage
4. Configure the Falcon Input Channel (humidity) for "Analog 420mA" and enter the Gain of 25 and Offset of -25.
5. Verify the "Calc" Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page.

TEMP RECEIVER PWR + RH RECEIVER

Figure 16.1: Falcon Wiring with the Dwyer Temperature/Humidity sensor

5 2
3

5 4

Temperature Setup -40 - 140 Degree F Range

Humidity Setup

TROUBLESHOOTING
1. Calculate the Dwyer Output current for temperature.
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
Example if Room Temp is 70F and your sensor has a range of -40 - 140
( (70 - -40) / (140 - -40)) x 16 + 4 = 13.77
2. Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%)
3. If measured current current does not match calculated current then check wiring.
4. Compare the measured current matches the current reading in the Falcon.
5. Check the wiring if the Falcon current reading does not match the measured current reading.
6. If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the following formula to calculate the humidity mA output.

mA =

Room Humidity 100

x 16 + 4

FMS Sensor Wiring Guide

SHEET: 17 OF 18

Rev 11-21

104 Racquette Drive Fort Collins, CO 80524 (970) 484-6510 Phone
(970) 484-6650 Fax www.rletech.com

FMS WIRED-TH Temperature/Humidity Integration

TB1 VDC + -

P1 VDC

EXTERNAL

TB2 Input 1-4

24VDC + +

Ch1 + -

Ch2 + -

Ch3 + -

Ch4 + -

Ch5 + -

TB3 Input 5-8

Ch6 + -

Ch7 + -

EXTERNAL

Ch8 + -

GND - -

TB4

RELAY 1 NC NO C

RELAY 2 NC NO C

GND
Humidity
Temperature V+
Figure 16.1: Falcon Wiring with the WIRED-TH Temperature/Humidity sensor

Temperature Setup -20 - 140 Degree F Range

Humidity Setup

SETUP
1. Wire the sensor as shown.
2. Configure the Falcon Input channel (temperature) for "Analog 4-20mA" and enter the gain and offset values. For the -20140F range use Gain 40.0, Offset 60.0.
3. For other temperature ranges, use the Calculator function on the webpage
4. Configure the Falcon Input Channel (humidity) for "Analog 420mA" and enter the Gain of 25 and Offset of -25.
5. Verify the "Calc" Value displays the correct room temperature. The temperature can also be viewed on the Falcon main page.

TROUBLESHOOTING
1. Calculate the output current for temperature.
( (Actual temp - Sensor Low) / (Sensor High - Sensor Low)) x 16 + 4
Example if Room Temp is 70F and your sensor has a range of -20-140
( (70 - -20) / (140 - -20)) x 16 + 4 = 13.0
2. Measure the current flowing into the Falcon Ch- terminal with a current meter. Verify that it is close to the calculated current (+/-1%)
3. If measured current current does not match calculated current then check wiring.
4. Compare the measured current matches the current reading in the Falcon.
5. Check the wiring if the Falcon current reading does not match the measured current reading.
6. If the Falcon current reading matches the measured current and the Falcon calculated value does not match the room temperature then the offset and gain values are wrong. Double check the Gain and Offset values.
7. If the temperature displayed in the Falcon is 1 or 2 degrees above or below the room temperature then adjust the offset by 1 or 2. Do not adjust the gain. Only tweak the offset once the previous troubleshooting steps have been performed.
8. If the Falcon still does not display the correct temperature contact RLE Technologies technical support at 970.484.6510.
9. Use similar troubleshooting procedure except use the following formula to calculate the humidity mA output.

mA =

Room Humidity 100

x 16 + 4

FMS Sensor Wiring Guide

SHEET: 18 OF 18

Rev 11-21



References

Microsoft Office Visio 2007 Microsoft Office Visio 2007