DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL

R410A Split Series

Installation manual | Manuel d'installation | Manual de instalación

MODELS

Safety Considerations

[DANGER] Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.

[WARNING] Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.

[CAUTION] Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.

[NOTE] Indicates situations that may result in equipment or property-damage accidents only.

DANGER

WARNING

CAUTION

NOTE

Accessories

Item CodeDescriptionQuantity
AMounting plate1
BMounting plate fixing screw 3/16" x 1" (M4 x 25mm)7
CTitanium apatite photocatalytic air-purifying filter *1*22
DWireless remote controller1
ERemote controller holder1
FFixing screw for remote controller holder 1/8" x 13/16" (M3 x 20mm)2
GDry battery AAA. LR03(alkaline)2
HIndoor unit fixing screw 3/16" x 1/2" (M4 x 12mm)2
JInsulation tape1
KOperation manual1
LInstallation manual1
MWarranty1

*1 Only for FTX(K)09/12/15/18/24* *2 09/12 class: without frame, 15/18/24 class: with frame

Choosing an Installation Site

Before choosing the installation site, obtain user approval.

1. Indoor unit

The indoor unit should be positioned in a place where:

2. Wireless remote controller

Turn on all the fluorescent lamps in the room, if any, and find a location where the remote controller signals are properly received by the indoor unit (within 23ft (7m)).

Indoor Unit Installation Diagram

This diagram illustrates the components and installation points for the indoor unit. It shows the mounting plate (A) and its fixing screw (B). Instructions are provided for attaching the indoor unit by hooking its bottom frame to the mounting plate, with guidance on removing the front grille if needed. The diagram also shows how to remove the indoor unit by pushing up the front grille.

The mounting plate (A) must be installed on a wall that can support the weight of the indoor unit.

Clearance requirements are shown: at least 1-3/16" (30mm) from the ceiling and at least 1-15/16" (50mm) from walls on both sides.

Air filters are shown. The titanium apatite photocatalytic air-purifying filter (C) is mentioned (sold separately for FTXN or FTKN models).

The service lid is removable and its opening method is described: remove screw, pull lid horizontally, then pull down.

Instructions are given to cut thermal insulation pipe to size, wrap it with tape ensuring no gaps, and then wrap the entire pipe with finishing tape from bottom to top.

The wireless remote controller (D) and its fixing screw (F) for the holder (E) are shown. A note advises to check signal reception before screwing the holder to the wall.

Indoor Unit Installation

1. Installing the mounting plate

The mounting plate should be installed on a wall that can support the weight of the indoor unit.

  1. Temporarily secure the mounting plate to the wall, ensure it is level, and mark drilling points.
  2. Secure the mounting plate to the wall with screws.

Recommended mounting plate retention spots and dimensions

09/12 class

Diagram shows the mounting plate with 7 retention spots. It indicates where to place a leveler. Dimensions are provided in inches (mm): 1-3/4 (44.5) top/bottom, 4-5/8 (117) and 4-5/8 (116.5) sides. Gas pipe end is at 1-15/16" (50), liquid pipe end at 13-1/4" (337), and drain hose position is indicated. A pocket is shown for the removed pipe port cover.

15/18/24 class

Diagram shows the mounting plate with 7 retention spots. Dimensions provided in inches (mm): 1-3/4 (44.5) top/bottom, 4-5/8 (117) and 5 (126.5) sides. Gas pipe end is at 2-3/8" (60), liquid pipe end at 17-1/8" (435). Drain hose position is indicated. A note shows how to use a tape measure to position the end of the pipe.

2. Drilling a wall hole and installing wall embedded pipe

[WARNING] For metal frame or metal board walls, use a wall embedded pipe and wall hole cover in the feed-through hole to prevent heat, electric shock, or fire.

Diagram shows wall embedded pipe and wall hole cover, with hole sizes for different classes.

3. Installing the indoor unit

Follow precautions when bending or curing refrigerant pipes to avoid abnormal sound.

3-1. Right-side, right-back, or right-bottom piping

  1. Attach the drain hose to the underside of the refrigerant pipes with adhesive vinyl tape.
  2. Wrap the refrigerant pipes and drain hose together with insulation tape (J).
  3. Pass the drain hose and refrigerant pipes through the wall hole, then set the indoor unit on the mounting plate (A) hooks using the markings at the top of the unit as a guide.
  4. Open the front panel (refer to "Installation Tips" page 10) and the service lid (refer to "Indoor Unit Installation Diagram" page 4).
  5. Pass the inter-unit wire from the outdoor unit through the wall hole to the front of the indoor unit, bending cable tie wires upward.
  6. Press the bottom frame of the indoor unit to set it on the mounting plate hooks, ensuring wire leads do not catch.

Diagrams show different piping directions (right-side, right-back, right-bottom) and how to bind pipes with tape. Another diagram shows hanging the unit on the mounting plate hooks and a wire guide.

3-2. Left-side, left-back, or left-bottom piping

How to replace the drain plug and drain hose

Diagrams show drain hose attachment positions (left/right side, front/back) and how to set the drain plug, warning against applying lubricating oil.

  1. Attach the drain hose to the underside of the refrigerant pipes with adhesive vinyl tape.
  2. Connect the drain plug to the drain port if not using a drain hose.
  3. Shape refrigerant pipes along the path marking on the mounting plate (A).
  4. Pass drain hose and refrigerant pipes through the wall hole, then position the indoor unit on the mounting plate hooks using the markings.
  5. Pull in the inter-unit wire.
  6. Connect the refrigerant pipes.
  7. If pulling the drain hose through the back, wrap refrigerant pipes and drain hose together with insulation tape (J).
  8. Press the bottom edge of the indoor unit to secure it to the mounting plate hooks with indoor unit fixing screws (H).

Diagrams illustrate left-side, left-back, and left-bottom piping, drain plug setting, and securing the unit with screws.

3-3. Wall embedded piping

Follow instructions for left-side, left-back, or left-bottom piping.

  1. Insert the drain hose to a depth of 1-15/16" (50mm) or more so it won't be pulled out of the drain pipe.

Diagram shows the drain hose insertion depth into the inner wall and the vinyl chloride drain pipe.

Wiring

  1. Insert wires, including the ground wire, into the conduit and secure with a lock nut onto the conduit mounting plate.
  2. Strip wire ends (3/4 inch (20mm)).
  3. Match wire colors with terminal numbers on the indoor and outdoor unit terminal blocks and secure wires with screws.
  4. Connect the ground wire to its terminal.
  5. Gently pull wires to ensure secure connection.
  6. Shape wires so the service lid fits securely, then close it.

Diagrams show the terminal block, conduit mounting plate, wire retainer, and connections for indoor and outdoor units. It specifies AWG16 for connection wires less than 33ft (10m) and AWG14 for longer runs.

[WARNING] Do not use tapped wires, extension cords, or starburst connections. Do not use locally purchased electrical parts. Do not connect the power wire to the indoor unit. Doing so may cause overheating, electric shock, or fire.

Drain piping

  1. Connect the drain hose as described. The drain hose should be inclined downward, with no trap permitted, and the end should not be submerged in water.
  2. Remove air filters and pour water into the drain pan to check for smooth water flow.
  3. If drain hose extension or embedded piping is required, use appropriate parts.
  4. When extending the drain hose, use a commercially available extension hose with a 5/8 inch (16mm) inner diameter. Thermally insulate the indoor section of the extension hose.

Diagrams illustrate proper drain hose installation and extension hose connection.

Refrigerant Piping Work

1. Flaring the pipe end

  1. Cut the pipe end with a pipe cutter.
  2. Remove burrs with the cut surface facing downward to prevent filings from entering the pipe.
  3. Put the flare nut on the pipe.
  4. Flare the pipe.
  5. Check that the flaring is done correctly.

Diagrams show pipe cutting, burr removal, and flaring tools (Flare tool for R410A, Conventional flare tool) with specifications for die and nut size. A check section emphasizes a flaw-free inner surface and an evenly flared pipe end.

[WARNING] Do not apply mineral oil to the flare. Prevent mineral oil from entering the system. Never use previously used piping. Never install a dryer. Incomplete flaring may result in refrigerant gas leakage.

2. Refrigerant piping

[CAUTION] Use the flare nut fixed to the main unit. Apply refrigeration oil only to the inner surface of the flare (use R410A oil). Use a torque wrench when tightening flare nuts.

Align flares and tighten nuts 3-4 turns by hand, then fully with a spanner and torque wrench.

Diagrams show applying oil to the flare inner surface, not the outer surface or flare nut. A diagram shows tightening with a spanner and torque wrench.

Piping size and Flare nut tightening torque

Piping sizeFlare nut tightening torque
O.D. 3/8 inch (9.5mm)24-1/8 - 29-1/2 ft lbf (32.7-39.9 N m)
O.D. 1/2 inch (12.7mm)36-1/2 - 44-1/2 ft lbf (49.5-60.3 N m)
O.D. 5/8 inch (15.9mm)45-5/8 - 55-5/8 ft. Ibf (61.8-75.4 N m)
O.D. 1/4 inch (6.4mm)10-1/2 - 12-3/4 ft lbf (14.2-17.2 N m)

2-1. Caution on piping handling

Diagrams show placing a cap on pipe ends or covering with tape. A diagram shows pipe bending near a wall.

2-2. Selection of copper and heat insulation materials

When using commercial copper pipes and fittings:

Diagrams show gas pipe, inter-unit wire, liquid pipe, gas pipe insulation, finishing tape, liquid pipe insulation, and drain hose.

SidePiping sizeMinimum bend radiusPiping thicknessThermal insulation sizeThermal insulation thickness
Gas sideO.D. 3/8 inch (9.5mm)1-3/16 inch (30mm) or more0.031 inch (0.8mm) (C1220T-O)I.D. 15/32-19/32 inch (12-15mm)13/32 inch (10mm) Min.
Gas sideO.D. 1/2 inch (12.7mm)1-9/16 inch (40mm) or more0.039 inch (1.0mm) (C1220T-O)I.D. 9/16-5/8 inch (14-16mm)
Gas sideO.D. 5/8 inch (15.9mm)1-15/16 inch (50mm) or more(C1220T-O)I.D. 5/8-13/16 inch (16-20mm)
Liquid sideO.D. 1/4 inch (6.4mm)1-3/16 inch (30mm) or more0.031 inch (0.8mm) (C1220T-O)I.D. 5/16-13/32 inch (8-10mm)

Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Installation Tips

1. Removing and installing the front panel

Removal method

  1. Place fingers in indentations on the unit and open the front panel.
  2. Push up the front panel while pushing the left side shaft outward (repeat for the right side).
  3. Pull the front panel toward yourself to remove it.

Diagrams show indentations on the unit and the front panel shaft.

Installation method

Align the front panel shaft with the grill grooves, push in fully, then close slowly. Push the center of the lower panel surface to engage hooks.

2. Removing and installing the front grille

Removal method

  1. Remove the front panel to access the air filter.
  2. Remove 2 screws from the front grille (3 screws for 15, 18, 24-class models).
  3. In front of the mark area (3 locations), pull the front grille toward you while pushing down on the upper hooks.

Diagrams show the mark area, upper hooks, and the action of pushing down and pulling.

[CAUTION] Be sure to wear protection gloves. When there is insufficient work space, place hands under the center of the front grille, push up, and pull toward you.

Installation method

  1. Install the front grille, engaging the upper hooks (3 locations).
  2. Install 2 screws (3 for 15, 18, 24-class models).
  3. Install the air filter, then mount the front panel.

3. How to set the different addresses

When installing two indoor units in one room, set wireless remote controllers to different addresses. Change the address setting of one unit. Be careful not to damage surrounding parts when cutting jumpers.

  1. Remove the battery cover on the remote controller and cut the address jumper.
  2. Press TEMP °F/°C and OFF simultaneously.
  3. Press TEMP °F/°C, select '8', then press FAN. The indoor unit OPERATION lamp will blink for about 1 minute.
  4. Press the indoor unit ON/OFF switch while the OPERATION lamp is blinking.

If setting fails, repeat from the beginning. Pressing FAN for 5 seconds after completion returns the remote controller to the previous display.

Diagram shows a remote controller with jumper settings (EXIST, CUT) corresponding to ADDRESS 1 and 2, and an indoor unit ON/OFF switch with an OPERATION lamp.

Trial Operation and Testing

1. Trial operation and testing

To operate in COOL mode in winter or HEAT mode in summer, use the following method:

  1. Press TEMP °F/°C and OFF simultaneously.
  2. Press TEMP °F/°C, select '7', then press FAN.
  3. Press COOL or HEAT to turn on the system.

Trial operation stops automatically after about 30 minutes. Press OFF to stop manually. Some functions may not be available in trial operation mode.

Diagrams show remote controller displays for HEAT PUMP model and COOLING ONLY model during trial operation setup.

2. Test items

Test itemsSymptomCheck
Indoor and outdoor units are installed properly on solid bases.Fall, vibration, noise
No refrigerant gas leaks.Incomplete cooling/heating function
Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated.Water leakage
Draining line is properly installed.Water leakage
System is properly grounded.Electrical leakage
The specified wires are used for inter-unit wiring.No operation or burn damage
Indoor or outdoor unit's air inlet or air outlet are unobstructed.Incomplete cooling/heating function
Stop valves are opened.Incomplete cooling/heating function
Indoor unit properly receives remote control commands.No operation

Company Information

GOODMAN MANUFACTURING COMPANY, L.P.
5151 San Felipe, Suite 500
Houston, TX 77056 USA

DAIKIN INDUSTRIES, LTD.
Head office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com

The document includes an Intertek ETL certification mark.

A two-dimensional barcode is present, identified as a manufacturing code (3P379970-5B M15B134 (1510) HT).

PDF preview unavailable. Download the PDF instead.

FTX12NMVJU-Installation-Manual Toolkit http://www.activepdf.com Toolkit http://www.activepdf.com

Related Documents

Preview Daikin R410A Split Series Air Conditioner Installation Guide
Comprehensive installation manual for Daikin R410A Split Series room air conditioners, covering safety precautions, site selection, unit installation, wiring, piping, and trial operation.
Preview Daikin Room Air Conditioner R410A Split Series Installation Manual
This installation manual provides comprehensive instructions for installing Daikin R410A Split Series Room Air Conditioners. It covers essential safety considerations, site selection criteria, detailed steps for indoor unit installation, wiring, drain piping, refrigerant piping work, and trial operation procedures. Includes diagrams and model information.
Preview Daikin Room Air Conditioner R410A Split Series Installation Manual
This installation manual provides detailed instructions for the Daikin R410A Split Series Room Air Conditioner, covering safety considerations, installation procedures, wiring, piping, and testing for models FTX/FTK/FTXN/FTKN NMVJU.
Preview Daikin Room Air Conditioner Installation Manual - R410A Split Series
Comprehensive installation manual for Daikin R410A Split Series room air conditioners, covering safety considerations, accessories, site selection, indoor unit installation, refrigerant piping work, installation tips, wiring, drain piping, and trial operation and testing procedures.
Preview Daikin Room Air Conditioner R410A Split Series Installation Manual
Comprehensive installation guide for Daikin R410A Split Series Room Air Conditioners, covering safety precautions, site selection, indoor and outdoor unit installation, wiring, refrigerant piping, and testing procedures.
Preview Daikin Room Air Conditioner R410A Split Series Installation Manual
This installation manual provides comprehensive instructions for the safe and correct installation of Daikin R410A Split Series Room Air Conditioners. It covers essential safety precautions, site selection criteria, detailed steps for indoor and outdoor unit installation, wiring, refrigerant piping, pressure testing, and trial operation procedures.
Preview Daikin Indoor Ductless Wall Mounted AC/HP Repair Parts Manual
Comprehensive repair parts list for Daikin Indoor Ductless Wall Mounted AC/HP units, covering models FTK, FTKN, FTX, and FTXN series. Find part numbers, descriptions, and model applicability for servicing.
Preview Daikin Room Air Conditioner R410A Split Series Installation Manual
Comprehensive installation manual for Daikin R410A Split Series Room Air Conditioners, covering safety precautions, site selection, unit installation, wiring, refrigerant piping, and testing procedures for various models.