Key Product Features
- A single damper model for all partitions: easy to choose.
- Ergonomic quick reset handle: 2 seconds are enough.
- Stainless steel spindle option for difficult environments.
- Remote control box option, 0.7m or 3m.
- ALDES SecurONE application for damper data collection and sharing.
- Unique mechanism, from the simplest to the most equipped damper: easy to choose, install, and maintain.
- Babyastall kit for easy installation in light partitions.
Operation Principle
The damper is open in standby position. It opens upon order from the CMSI (Fire Safety Control System) or thermal probe, moving to the safety (closed) position. It can be reset remotely via motorization.
Product Description
Fire dampers intended for tertiary buildings (ERP, IGH). They restore the fire resistance of partitions traversed by a ventilation duct. Equipped with a thermal fuse tripping at 70°C by default. Controllable by an electromagnetic coil (24/48VDC emission, 24VCC or 48VCC break) or a reset motor (24-48 VCC/VDC). Fire rating up to 120 minutes on all common partitions.
Available Sizes:
- ISONE® 2.1 Rectangular PM: (LxH): from 200x100 to 800x600 mm.
- ISONE® 2.1 Rectangular GM: (LxH): L≥800, H≥600, up to 1500x500 / 1000x1000 mm.
Application Areas
New construction, Renovation, Tertiary premises.
Implementation (Installation)
Installation without sealing on light partitions, even with a post-mounted frame. Recessed mounting on concrete/cellular concrete walls/slabs, plasterboard walls, and plasterboard type A (1h) and type F (2h). Remote mounting is possible on PROMAT / GEOSTAF using the EASYNSTAL kit. Positioning on light partitions is facilitated by installation brackets. The Easynstall kit simplifies the installation of rectangular dampers in light partition type A (60 minutes). An adaptation piece is available for connection to oblong ducts. Adherence to EXAP EN 15882-2:2015, rules X.45 and X.46 for extended recess dimensions is required. Fire classification reports must be respected during installation.
Main Characteristics
- Certified and compliant with NF S 61937-5 and NF537.
- CE marked according to EN 15650: 1812-CPR-1837.
- Class C airtightness according to EN 1751 standard.
- EI 120 S -500 Pa performance on concrete walls/slabs, cellular concrete, plasterboard type F, and PROMAT/Geostaff remote mounting.
- Compliant with EXAP EN 15882-2:2015: rules X.45 and X.46.
- Range covers dimensions from 200x100 mm to 1500x500 / 1000² mm.
Regulations & Conformity
CE PV Number: 1812-CPR-1837
Complementary Characteristics
- 100% evolvable mechanism.
- Unique damper adaptable to all partitions.
- Installation on light partition with post-mounted frame.
- Reset handle indicating damper position.
- Large electrical connection box.
- Stainless steel spindle option for hostile environments.
- Easynstall kit for easy installation in light partitions.
- Remote control box option.
- Low pressure drop.
Dimensional Data
Reference | E (mm) | F (mm) | G (mm) | H (mm) | L (mm) | ZA (mm) |
---|---|---|---|---|---|---|
11040020 | 25 | 169 | 71 | 300 | 500 | 112.50 |
Rectangular Enclosure Sizes:
- ISONE®2.1 GM: ≥800x600 to 1500x500 / 1000² mm.
- ISONE®2.1 PM: 200x100 to 800x600 mm.
Installation Requirements
Detailed opening dimensions are provided for different partition types:
- Concrete Wall: Required opening: X+80 x Y+80 mm.
- Concrete Slab: Required opening: X+145 x Y+145 mm.
- Plasterboard Partition (120 minutes): Required opening: X+70 x Y+70 mm.
- Light Partition (120 minutes): Required opening: X+70 x Y+70 mm, with a minimum clearance of 98 mm.
- Light Partition (60 minutes) with Easynstall kit: Required opening: X+70 x Y+70 mm, with a minimum clearance of 98 mm.
Principle of Operation - Component Breakdown
The damper's operation involves the following key components:
- 1: Installation bracket: Secures the damper to the partition.
- 2: Fire plate: The blade that closes to prevent fire spread.
- 3: ISONE®2.1 PM mechanism: The actuator and control system.
- 4: Blade: Available in 25mm thickness (PM model) or 50mm thickness (GM model).
- 5: Connection flange: A 30mm flange for duct connection.
For more information, contact your Aldes advisor. Visit www.aldes.com.